Operation
86
89217391 Rev. A
©2022 nVent
10.6.15 Page 7682, pump speed PID settings
/ Unit / Setup /
Controller parameters / Pump speed PID
•
Adjustment of process-relevant parameters.
Screen contents:
Description
PID pump speed
Setpoint
Diff. pump press.
[bar]
Setpoint setting in the "differential pump pressure" mode
Set diff. sys. pr.
[bar]
Setpoint setting in "differential system pressure" mode
Flow rate
[l/min]
Setpoint setting in the "flow rate" mode
Temperature
[°C]
Setpoint setting in the "temperature" mode
Pr. contr.
Flow controller
Temp. controller
Contr. Kp
-
Contr. gain
Contr. Ti
[s]
Integral action time of the controller
Contr. Td
[s]
Derivative action time of the controller
D-factor mean value
[s]
Time range over which the mean value of the D-part of the
controller is calculated
Contr. min. speed
[%]
Min. speed of the pumps in the selected mode.
Contr. max. speed
[%]
Max. speed of the pumps in the selected mode.