Troubleshooting
©2022 nVent
89217391 Rev. A
113
Fig. 45: Removal/installation of the actuator
Removal of the actuator
5.
When the locking mechanism (1) is pushed upwards, the connection
between the tappet (4) of the control valve (2) and the actuator (5) is opened
(unlocking of the lock).
6.
Loosen the screws (3) by turning them anti-clockwise with an Allen key.
7.
Take the actuator (5) off the control valve (2).
Installation of the actuator
8.
Attach the actuator (5) to the control valve (2) and align it with the "A" arrow.
9.
Tighten the screws (3) by turning them clockwise with an Allen key (4 Nm).
NOTE
Comply with the specified tightening torque.
14397
4 m m
“A“
5
4
3
2
1