Model
Block
Point Name
Address
Scale
Factor
Purpose
803
Fixed
BTotDCCur
40127
Yes
Total DC current of the battery system
803
Fixed
BMaxStrCur
40128
Yes
Largest DC current reported by a stack/string
803
Fixed
BMinStrCur
40129
Yes
Smallest DC current reported by a stack/string
803
Repeat
StrSoC
40135 +Index
No
State of charge for a stack/string
803
Repeat
StrSoH
40136 +Index
Yes
State of health for a stack/string
803
Repeat
StrCur
40137 +Index
Yes
Current of a stack/string
803
Repeat
StrMaxCellVol
40138 +Index
Yes
Maximum cell voltage of a stack/string
803
Repeat
StrMinCellVol
40139 +Index
Yes
Minimum cell voltage of a stack/string
803
Repeat
StrCellVolLoc
40140 +Index
No
Location of min/max cell voltages of a stack/string
803
Repeat
StrMaxModTmp
40141 +Index
Yes
Maximum module temperature of a stack/string
803
Repeat
StrMinModTemp
40142 +Index
Yes
Minimum module temperature of a stack/string
803
Repeat
StrModTmpLoc
40143 +Index
No
Location of min/max module temperatures of a
stack/string
803
Repeat
StrEvt1
40144 +Index
No
Alarms warnings and status bit field of a stack/string
The term Index in the Repeating block addresses used in the above table refers to a
calculation of
Index = Stack Index * Length of Repeating block
. By definition, the 803
Repeating block is 16 Modbus registers in length.
9.1.5. Accessing MESA Models
MESA models are located contiguously in the Modbus address space starting at a base address of
40000
. The Common Model is always located first in this space. The End Model is always last and is
used to denote the end of MESA Modbus registers. Each model located between the Common Model
and the End Model has a numeric identifier as well as a length. A handy tool that can be used to
explore the MESA Modbus registers for Nuvation Energy BMS is
modpoll.exe
. It is available for free
download at
http://www.modbusdriver.com/modpoll.html
.
Using
modpoll.exe
, the Common Model can be polled from a using the following command (assuming
the device has an IP address of
192.168.1.21
)
Nuvation Energy Battery Control Panel - Product Manual
Document ID: NE-PM-005
79
Rev 1.1, 2020-10-14
Curie Update 2