5.4.5. Automatic Stack Connection
Navigate to the
Dashboard
tab and click on the
Connect
button to initiate a pack connection. The
stack(s) that meet the pack connection criteria will be sequentially connected.
If all the stacks are connected, the dashboard screen will look like this:
Refer to the
Total Stacks
and the
Connected Stacks
values displayed to the right of the display. If
they are not equal in value, not all stacks could be connected due to an unbalanced number of
stack(s). Connecting these unbalanced stacks would have violated a stack connection current that
has been configured. The pack is now waiting for a charge/discharge operation from an external
Power Control System (PCS) to bring the connected stacks closer to the unconnected stack
voltage(s).
When the pack is in this partially connected state, the dashboard would appear like this: