MC-II
Plus
WP-PM Flow Analyzer
Appendix D
D-2
May
2005
Prompt
Where
Displayed
Definition
CodE
Upper line
The display prompts to enable or disable the
requirement for a security code by toggling the
on
or
oFF
selection shown on the lower line of the display.
div d.P
Upper line
When
USEr
defined unit of measure was previously
selected, the display prompts for entry of the pulses
per unit volume decimal point. The present decimal
point placement is shown on the lower line of the
display.
Ent div
Upper line
When
USEr
defined unit of measure was previously
selected, the display prompts for entry of the divisor
in pulses per unit volume. The present divisor is
displayed on the lower line of the display.
Ent F
Upper line
When MCF was previously selected for the volume
units of measure, the display prompts for the entry of
the average flowing temperature in degrees
Fahrenheit. The present flowing temperature entry is
displayed on the lower line of the display.
Ent FPv
Upper line
When MCF was previously selected for the volume
units of measure, the display prompts for the entry of
the average supercompressibility factor (Fpv). The
presently entered super-compressibility factor is
shown on the lower line of the display. (Enter
1.00000 if supercompressibility factor is not known)
Ent.CodE
Upper line
The display prompts for the entry of a 4-digit security
code to be entered on the lower line of the display
(only if the
CodE
function is enabled).
Ent.P.ACF
Upper line
When MCF was previously selected for units of
measure, the display prompts for the entry of the
meter factor in pulses per actual cubic foot. The
present meter factor entry is displayed on the lower
line of the display.
Ent.P.gAL
Upper line
When the volume units of liquid measure were
previously selected (BBL, GAL M3), the display
prompts for entry of the meter factor in pulses per
gallon. The present meter factor entry is displayed
on the lower line of the display.
Ent.PSig
Upper line
When MCF was previously selected for the volume
units of measure, the display prompts for the entry of
the average flowing pressure in Pounds per Square
Inch. The average flowing pressure entry is
displayed on the lower line of the display.
Error
Lower line
Is displayed when there is an error detected by the
MC-II
Plus
firmware. Pressing any key while in the
Run Mode will display the type of error on the upper
line of the display.
Содержание MC-II Plus Panel Mount
Страница 41: ...Appendix A1 MC II Plus WP PM Flow Analyzer May 2005 A1 7 Dimensions in inches mm MC II Plus DIN Panel Mount...
Страница 44: ...MC II Plus WP PM Flow Analyzer Appendix A1 A1 10 May 2005 Flow Meter Input Wiring...
Страница 46: ...MC II Plus WP PM Flow Analyzer Appendix A1 A1 12 May 2005 External Power Wiring...
Страница 47: ...Appendix A1 MC II Plus WP PM Flow Analyzer May 2005 A1 13 4 4 to 20mA Rate Output Wiring...
Страница 49: ...Appendix A1 MC II Plus WP PM Flow Analyzer May 2005 A1 15 Reset Input with Power Supply and Reset Switch...
Страница 50: ...MC II Plus WP PM Flow Analyzer Appendix A1 A1 16 May 2005 Reset Using MC II Plus Battery and Reset Switch...
Страница 52: ...MC II Plus WP PM Flow Analyzer Appendix A1 A1 18 May 2005...
Страница 60: ...MC II Plus WP PM Flow Analyzer Appendix A2 A2 8 May 2005 Remote Mount Mounting Dimensions Horizontal Pole Mount...
Страница 62: ...MC II Plus WP PM Flow Analyzer Appendix A2 A2 10 May 2005...
Страница 65: ...Appendix C MC II Plus WP PM Flow Analyzer May 2005 C 1 Appendix C MC II Plus WP PM Configuration Menu Flowchart...
Страница 67: ...Appendix C MC II Plus WP PM Flow Analyzer May 2005 C 3 Appendix C MC II Plus WP PM Configuration Menu Flowchart...
Страница 68: ...MC II Plus WP PM Flow Analyzer Appendix C C 4 May 2005 Appendix C MC II Plus WP PM Configuration Menu Flowchart...
Страница 69: ...Appendix C MC II Plus WP PM Flow Analyzer May 2005 C 5 Appendix C MC II Plus WP PM Configuration Menu Flowchart...
Страница 70: ...MC II Plus WP PM Flow Analyzer Appendix C C 6 May 2005 Appendix C MC II Plus WP PM Configuration Menu Flowchart...
Страница 71: ...Appendix C MC II Plus WP PM Flow Analyzer May 2005 C 7 Appendix C MC II Plus WP PM Configuration Menu Flowchart...
Страница 72: ...MC II Plus WP PM Flow Analyzer Appendix C C 8 May 2005 NOTES...
Страница 78: ...MC II Plus WP PM Flow Analyzer Appendix D D 6 May 2005 NOTES...
Страница 92: ......