XBC+ with Ecosmart Connect (C) Control

Installation Manual

 

DECLARATION OF INCORPORATION AND INFORMATION FOR SAFE INSTALLATION,  

 

OPERATION AND MAINTENANCE

 

INFORMATION FOR SAFE INSTALLATION, OPERATION AND MAINTENANCE

 

OF NUAIRE VENTILATION EQUIPMENT

We declare that the machinery named below is intended to be assembled with 
other components to constitute a system of machinery. All parts except for 
moving parts requiring the correct installation of safety guards comply with the 
essential requirements of the Machinery Directive. The machinery shall not be 
put into service until the system has been declared to be in conformity with the 
provisions of the EC Machinery Directive 1.3.7 to 1.3.8.2 relating to guards / 
moving parts.  
The relevant technical documentation has been compiled in accordance with  
Annex VII, Part B of EC Machinery Directive 2006/42/EC. We undertake, in 
response to a reasoned request, to supply it in electronic form to the market 
surveillance authorities within a reasonable period.

 

To comply with EC Council Directives 2006/42/EC Machinery Directive and 2014/30/EU (EMC).
To be read in conjunction with the relevant product documentation (see 2.1)

1.0  

GENERAL

1.1  

The equipment referred to in this 

Declaration of Incorporation

 is supplied by Nuaire to be assembled into    

 

a ventilation system which may or may not include additional components. The entire system must be  

 

 

considered for safety purposes and it is the responsibility of the installer to ensure that all of the equipment is  

 

installed in compliance with the manufacturers recommendations and with due regard to current legislation   

 

and codes of practice.

2.0  

INFORMATION SUPPLIED WITH THE EQUIPMENT

2.1  

Each item of equipment is supplied with a set of documentation which provides the information required for   

 

the safe installation and maintenance of the equipment. This may be in the form of a Data   

 

 

sheet and/or Installation and Maintenance instruction.

2.2  

Each unit has a rating plate attached to its outer casing. The rating plate provides essential data relating to the  

 

equipment such as serial number, unit code and electrical data. Any further data that may be required will be  

 

found in the documentation. If any item is unclear or more information is required, contact Nuaire.

2.3 

Where warning labels or notices are attached to the unit the instructions given must be adhered to.

3.0  

TRANSPORTATION, HANDLING AND STORAGE

3.1  

Care must be taken at all times to prevent damage to the equipment. Note that shock to the unit may result in  

 

the balance of the impeller being affected.

3.2 

 When handling the equipment, care should be taken with corners and edges and that the weight distribution  

 

within the unit is considered. Lifting gear such as slings or ropes must be arranged so as not to bear on the    

 casing.
3.3  

Equipment stored on site prior to installation should be protected from the weather and steps taken to prevent  

 

ingress of contaminants.

4.0  

OPERATIONAL LIMITS

4.1  

It is important that the specified operational limits for the equipment are adhered to e.g. operational air  

 

 

temperature, air borne contaminants and unit orientation.

4.2  

Where installation accessories are supplied with the specified equipment e.g. wall mounting brackets. They    

 

are to be used to support the equipment only. Other system components must have separate provision for    

 support.
4.3  

Flanges and connection spigots are provided for the purpose of joining to duct work systems. They must not be  

 

used to support the ductwork.

4.4  

Local Environment - Humidity.

 Ambient humidity (the humidity at the unit’s installed location) shall be  

 

 

within the range: 10 to 95% (for controls, non-condensing). Air humidity (the humidity of    

 

 

the air passing through the unit) shall be within the range: 10 to 95% (for controls, non-condensing).

5.0  

INSTALLATION REQUIREMENTS

 

In addition to the particular requirements given for the individual product, the following general requirements  

 

should be noted.

5.1 

 Where access to any part of equipment which 

moves

, or can become 

electrically live

 are not prevented by   

 

the equipment panels or by fixed installation detail (e.g. ducting), then guarding to the appropriate standard    

 

must be fitted.

5.2 

 The electrical installation of the equipment must comply with the requirements of the relevant local electrical  

 

safety regulations.

5.3 

 For EMC all control and sensor cables should not be placed within 50mm or on the same metal cable tray as   

 

230V switched live, lighting or power cables and any cables not intended for use with this product.

6.0 

 COMMISSIONING REQUIREMENTS

6.1 

 General pre-commissioning checks relevant to safe operation consist of the following:

 

Ensure that no foreign bodies are present within the fan or casing.

 

Check electrical safety e.g. Insulation and earthing.

 

Check guarding of system.

 

Check operation of Isolators/Controls.

 

Check fastenings for security.

6.2 

 Other commissioning requirements are given in the relevant product documentation.

7.0 

 OPERATIONAL REQUIREMENTS

7.1  

Equipment access panels must be in place at all times during operation of the unit, and must be secured with  

 

the original fastenings.

7.2  

If failure of the equipment occurs or is suspected then it should be taken out of service until a competent  

 

 

person can effect repair or examination. (Note that certain ranges of equipment are designed to detect and    

 

compensate for fan failure).

8.0  

MAINTENANCE REQUIREMENTS

8.1  

Specific maintenance requirements are given in the relevant product documentation.

8.2  

It is important that the correct tools are used for the various tasks required.

8.3  

If the access panels are to be removed for any reason the electrical supply to the unit must be isolated.

8.4  

A minimum period of two minutes should be allowed after electrical disconnection before access panels are    

 

removed. This will allow the impeller to come to rest.

 

NB: Care should still be taken however since airflow generated at some other point in the system can    

 

cause the impeller to “windmill” even when power is not present.

8.5  

Care should be taken when removing and storing access panels in windy conditions.

Note: All standards used were current and valid at the date of signature.

Signature of manufacture representatives:

Name: 

  Position: 

  Date: 

1)A. 

Thomas 

  Engineering 

Director 

 

XX. XX. XX

2)C. 

Sargent 

  Manufacturing 

Director 

 

XX. XX. XX

Designation of machinery:  

XBOXER XBC+ with Ecosmart Connect (C) or No   

 

  (N) 

Controls. 

 

Machinery Types:    

Supply & Extract Fans with Heat Recovery

Relevant EC Council Directives: 

2006/42/EC (Machinery Directive)

 

Applied Harmonised Standards:

 BS EN ISO 12100:2010, EN60204-1,    

 

 

 

 

BS EN ISO 9001, BS EN ISO 13857

Applied National Standards: 

BS848 Parts 1, 2.2 and 5

Содержание Xboxer xbc+ Ecosmart Connect Control

Страница 1: ...ust be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open fl...

Страница 2: ...ent person to determine if any additional PPE is required 2 0 INTRODUCTION The information contained in this document provides details of installation operation and maintenance for installers and user...

Страница 3: ...BOXER 2 HX Type C Counterflow E Enthalpy 3 Unit Size 10 15 25 45 55 65 4 Unit Layout H Horizontal 5 Filter Grade A 6 Heating Type E Electric L LPHW N No Heating 7 Heater Size H High Duty L Low Duty N...

Страница 4: ...ring the offloading from the vehicle or on the site thereafter All claims for damage and or incomplete delivery must be reported to Nuaire within two days of receipt of the equipment following Nuaire...

Страница 5: ...panels it is recommended that electrical and plumbing service connections to the unit are run at 90 degrees to the main air flow axis Control circuit connections must be segregated i e routed separate...

Страница 6: ...C D SUPPLY DISCHARGE Unit Code Dimensions to Hole Centres mm A B C XBC10HA 1068 830 385 XBC15HA 1068 830 385 XBC25HA 1232 884 415 XBC45HA 1332 1020 447 XBC55HA 1632 1052 424 XBC65HA 1644 1054 430 Unit...

Страница 7: ...250 471 302 76 XBC25 HE MS12 1250 252 302 59 XBC25 HS MS16 1600 471 302 99 XBC25 HE MS16 1600 252 302 73 XBC45 HS MS10 1050 531 360 69 XBC45 HE MS10 1050 270 360 49 XBC45 HS MS12 1250 531 360 88 XBC45...

Страница 8: ...471 64 XBC25 HE MBS S 421 402 275 421 402 342 302 292 252 40 XBC25 HE MBS L 992 973 846 421 402 342 302 292 252 54 XBC45 HS MBS S 700 681 415 700 681 400 360 571 531 60 XBC45 HS MBS L 1070 1051 785 70...

Страница 9: ...ds should be secured to the Unistrut channel and extended to be fixed to the four piece support brackets to be used on the underside of the attenuators Figure 15 Note once the attenuators are supporte...

Страница 10: ...5 XBC65 EXHAUST RT XBC65 INTAKE RT 3 12 2 Optional Exhaust Intake Terminals 3 12 3 Terminal Part Codes 16 17 Weatherproof Kit Installation Motorised Damper Installation 3 13 Motorised Dampers If match...

Страница 11: ...t at the connection points and to make sure that they run without any kinks 18 19 Damper Wiring Switch Wiring S1 S2 S3 S1 S2 S3 1 0 1 0 1 0 0 1 230V Auxiliary switch Notes Caution Power supply voltage...

Страница 12: ...Unit Condensate drain connection 8 mm flexible pipe Control box Coil connections 40mm centres Access to Condensate tray and Pump IMPORTANT The condensate pump incorporates an alarm function If the wat...

Страница 13: ...ure Units must not be operated without all access panels in place damage to equipment or injury to personnel may result Units must not be operated unless control interlocks are in place damage to equi...

Страница 14: ...riginal CAGE CLAMP terminals blocks 5 7 4 Fitting Jumpers Terminal blocks can be connected together to increase the number of terminals at the same potential using push in jumpers In these cases the t...

Страница 15: ...E G F H I 5 8 Unit Hardware Positions Diagram 29 30 Hardware Positions I O Damper Wiring 5 8 1 Hardware Position Key A Supply fan drive health B Delivery air temperature sensor C Extract air temperat...

Страница 16: ...20 Document Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 31 Basic Unit Connection 5 10 Basic Unit Connection...

Страница 17: ...1 07 20 Document Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 32 Controller Layout 5 11 Controller Layout Dia...

Страница 18: ...ber 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 5 12 Wiring Diagrams 5 12 1 Unit Sizes 10 15 with No Heating 33 Siz...

Страница 19: ...cument Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 5 12 2 Unit Sizes 25 65 with No Heating 34 Sizes 25 65 wi...

Страница 20: ...ment Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 5 12 3 Unit Sizes 10 15 with LPHW Heating 35 Sizes 10 15 wi...

Страница 21: ...ment Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 5 12 4 Unit Sizes 25 65 with LPHW Heating 36 Sizes 25 65 wi...

Страница 22: ...Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 37 Sizes 10 15 with Electric Heating 5 12 5 Unit Sizes 10 15 wi...

Страница 23: ...Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 38 Sizes 25 65 with Electric Heating 5 12 6 Unit Sizes 25 65 wi...

Страница 24: ...Sensor When a Room Module PIR sensor is connected via the SA bus the control will automatically use this as an enable signal by default There is a non adjustable minimum run on time of 15mins for Roo...

Страница 25: ...0V input is scaled to 0 100 fan speed demand This is available on IN5 only The fan speed can be adjusted in software using the LCD or a BACnet connection by adjusting the Fan Speed Demand object Fan S...

Страница 26: ...turn air temperature the outside air temperature and the heat exchanger efficiency e g 13 C outside air temperature with a 23 C return air temperature will give a supply air temperature of 20 5 C The...

Страница 27: ...ce in critical alarm state the unit will drive all heating and cooling outputs to 0V In the event of fan fail other functions continue as normal The critical alarm is latched and requires power cycle...

Страница 28: ...Enable The state of the enable input IN8 BI 10161 N A 0 Off 1 On 9 Run on Enable Run on timer value AV 10267 0 Seconds 24 Local Calendar 0 CAL 10496 N A 0 33 Enable via Schedule Enabled via Schedule M...

Страница 29: ...d Dead band for temp control AV 10266 3 Degrees Celsius 32 SetPoint Op Setpoint operation MSV 10214 Software Setpoint Only 1 Last Changed 2 Software Only 3 Last Changed with Timeout 19 Setpoint Timeou...

Страница 30: ...Speed Schedule Current state of the Fan Speed Demand Schedule object AV 17830 0 Percent 44 Fan Override Operation Chooses the operation of the 3 speed fan override MSV 17975 Override Has Priority 1 Ov...

Страница 31: ...A Degrees Celsius 4 RM201 Humidity The Humidity at RM address 201 AI 10077 N A Percent Relative Humidity 7 RM201 Setpoint The setpoint at RM address 201 AV 10083 N A Degrees Celsius 3 RM202 Temp The t...

Страница 32: ...he state of Alarm Circuit 1 BI 10167 N A 0 Alarm 1 Normal 20 Alarm Circuit 2 The state of Alarm Circuit 2 BI 10170 N A 0 Alarm 1 Normal 11 High Temp Alarm Supply temp which will trip the high supply a...

Страница 33: ...to be changed The instance number range is 1 4 194 303 222 Ecosmart Connect controllers use a MSTP network for communication and are assigned a MSTP address 4 127 by the dip switch located on the fro...

Страница 34: ...e 7 Case 5 Priority 1 Null Priority 2 Null Priority 3 Null Priority 4 Null Priority 5 Null Priority 6 Null Priority 7 Null Priority 8 Null Priority 9 Null Priority 10 Null Priority 11 Null Priority 12...

Страница 35: ...nstance 10185 Object Type AO Present Value 0 State Text Volts Object Properties Object Name Enable Object Instance 10288 Object Type MSV Present Value On State Text Off On Object Properties Object Nam...

Страница 36: ...has a USB 2 0 Type B receptacle which is only used to obtain power from a computer or USB adapter A mains adapter and cable is supplied The router connects to the FC bus via screwed terminals 8 2 BACn...

Страница 37: ...49 ESCO LCD Navigating the ESCO LCD 8 5 Navigation Cancel Quit and moves to the previous section Home Shortcut to the configured Home Page Back Moves to the previous page in the same section Forward...

Страница 38: ...bject within the entire network 8 7 1 Choosing A Target Object To choose a target object Navigate to the settings page Select the right arrow four times to reach the Select Target Device screen Enter...

Страница 39: ...the settings page Select the right arrow twice to reach the display settings screen Change the user password a 4 digit number The user password will now be requested each time a locked object is writt...

Страница 40: ...n be accessed by selecting the alarm icon Alarm events are logged with a date and time Nor represents a change to a normal state Ala represents a change to an alarm state The text in parentheses denot...

Страница 41: ...he value of the Max_Master property of the node s Device object 127 APDU Time The APDU Timeout property defines the amount of time in seconds the FAD waits for responses from other devices 3 8 8 2 Dis...

Страница 42: ...hen accessing the Network View the FAD launches a Network Discovery function The purpose of this function is to find other BACnet devices residing on the same MS TP trunk The maximum number of devices...

Страница 43: ...s 9 2 4 Room Humidity The ESC RM 2 TDH 120 model includes a push button on the face of the network sensor to allow occupants to view the temperature and relative humidity of the zone Pressing the push...

Страница 44: ...dard Sensor Small Room Module Dimensions Large Room Module Dimensions CO2 Sensor SA SA Bus Com SA Power from Controller 15 VDC SA Bus Screw Terminal Block Network Sensor COM SA PWR Screw Terminal Bloc...

Страница 45: ...YES YES YES YES 199 fixed Max of 1 per controller Group 2 Max of 4 Per Controller ESCO TS 80x80 YES 200 203 ESCO THS 80x80 YES YES 200 203 ESCO TDS 80x80 YES YES 200 203 ESCO TDHS 80x80 YES YES YES 2...

Страница 46: ...Angular Degrees up to a distance of 15 ft 4 6m Based on a clear line of sight Ambient Operating Conditions 10 to 30 C 10 to 90 RH Temp Probe 10 to 60 C Ambient Storage Conditions 20 to 60 C t to 95 R...

Страница 47: ...adaptor 3 way female RJ12 adaptor RJ12 Sensor jack Cable Type Pre fabricated 3 twisted pair with RJ12 Plugs 26AWG Room Module Room Module RJ12 Plug RJ12 Plug Room Module Sensor SA Bus RJ 12 Modular Ja...

Страница 48: ...trickle the fans at all times 10 1 4 Setting Supply Air Temperature If a room module is fitted with an integral LCD the air off temperature is set by the end user via the adjustment dial e g ESCO TDS...

Страница 49: ...ocessed in energy from waste centres Remaining Items can be further segregated and processed in accordance with the zero waste hierarchy Please call After Sales Support for further information on item...

Страница 50: ...re supplied with the specified equipment e g wall mounting brackets They are to be used to support the equipment only Other system components must have separate provision for support 4 3 Flanges and c...

Страница 51: ...51 21 07 20 Document Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual NOTES...

Страница 52: ...52 21 07 20 Document Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual NOTES...

Отзывы: