XBC+ with Ecosmart Connect (C) Control

Installation Manual

6.14.7 Heat Boost

LCD Browser 
Page

BACnet Object

Description

Object 
Type

Object 
ID

Default 
Value

Units

30

Heat Boost

Software enabled Heater boost

MSV

10205

Off

(1)Off (2)On

11

Heat Boost Setpoint

Heater Boost Setpoint

AV

10276

35

Degrees-Celsius

6.14.8 Extract Setback

44

Extract Setback

Puts the extract fan to setback speed

MSV

17769

Off

(1)Off (2)On

19

Extract Setback 

Speed

The extract fan speed when Extract Setback 

is enabled.

AV

18258

30

Percent

6.14.9 Fan Outputs

6

Supply Fan Output

The 0-10v signal to the supply fan

AO

10182

N/A

Volts

6

Extract Fan Output

The 0-10v signal to the extract fan

AO

10176

N/A

Volts

21

Fan Enabled Cmd

The state of the fan enabled relay.

BO

10191

N/A

(1)Off (2)On

6.14.10 Fan Commissioning

9

Extract Fan Max

Individual fan maximum speed setting

AV

10268

100

Percent

10

Extract Fan Min

Individual fan minimum speed setting

AV

10270

20

Percent

15

Supply Fan Max

Individual fan maximum speed setting

AV

10312

100

Percent

15

Supply Fan Min

Individual fan minimum speed setting

AV

10314

20

Percent

6.14.11 Temperature Controls

14

Software Setpoint

Software Setpoint

AV

10309

22

Degrees-Celsius

9

Deadband

Dead band for temp control

AV

10266

3

Degrees-Celsius

32

SetPoint Op

Setpoint operation

MSV

10214

Software 

Setpoint Only

(1)Last Changed (2)Software 

Only (3)Last Changed with 

Timeout 

19

Setpoint Timeout

The time before reverting to software 

setpoint when last changed with timeout is 

selected.

AV

17971

3600

Seconds

27

Setpoint Schedule

A schedule for setpoint adjustment.

SCH

18215

N/A

0

19

Setpoint Schedule

Current state of the Setpoint Schedule 

object.

AV

18215-

22

Degrees-Celsius

32

T Sens. Op

Temperature sensor operation

MSV

10215

NS Average

(1)NS Average (2)Return Air 

Only (3)NS & Return Average

33

0-10v Temp Range

Temperature sensor range

MSV

10216

0 to 50°C

(1)0 to 50°C (2)0 to 40°C 

(3)0 to 100°C (4)0 to 80°C 

(5)0 to 90°C 

35

Temp Control Mode

Temperature control mode

MSV

10245

Supply Temp

(1)Supply Temp (2)Room 

Temp

14

STC H/C Pref

STC Heat/Cool Pref

AV

10310

50

No units

15

STC HX Efficiency

STC HX Efficiency

AV

10311

0.8

No units

13

RTC Boost Band

The Return Temperature Control Boost Band AV

10306

15

Degrees-Celsius

14

RTC Max Supply 

Temp

Maximum supply temp when in RTC mode

AV

10307

35

Degrees-Celsius

14

RTC Min Supply 

Temp

Minimum supply temp when in RTC mode

AV

10308

12

Degrees-Celsius

6.14.12 Heating Output

30

Heating Type

Set the type of heating fitted.

MSV

10206

As per Build 

(1)None (2)LPHW (3)Electric 

(4)3rd-Party

6

Heating Output

The 0-10v signal to the heating output

AO

10179

N/A

Percent

22

Heating Demand 

Cmd

The state of the heating demand relay.

BO

10197

N/A

(0)Off (1)On

Содержание Xboxer xbc+ Ecosmart Connect Control

Страница 1: ...ust be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open fl...

Страница 2: ...ent person to determine if any additional PPE is required 2 0 INTRODUCTION The information contained in this document provides details of installation operation and maintenance for installers and user...

Страница 3: ...BOXER 2 HX Type C Counterflow E Enthalpy 3 Unit Size 10 15 25 45 55 65 4 Unit Layout H Horizontal 5 Filter Grade A 6 Heating Type E Electric L LPHW N No Heating 7 Heater Size H High Duty L Low Duty N...

Страница 4: ...ring the offloading from the vehicle or on the site thereafter All claims for damage and or incomplete delivery must be reported to Nuaire within two days of receipt of the equipment following Nuaire...

Страница 5: ...panels it is recommended that electrical and plumbing service connections to the unit are run at 90 degrees to the main air flow axis Control circuit connections must be segregated i e routed separate...

Страница 6: ...C D SUPPLY DISCHARGE Unit Code Dimensions to Hole Centres mm A B C XBC10HA 1068 830 385 XBC15HA 1068 830 385 XBC25HA 1232 884 415 XBC45HA 1332 1020 447 XBC55HA 1632 1052 424 XBC65HA 1644 1054 430 Unit...

Страница 7: ...250 471 302 76 XBC25 HE MS12 1250 252 302 59 XBC25 HS MS16 1600 471 302 99 XBC25 HE MS16 1600 252 302 73 XBC45 HS MS10 1050 531 360 69 XBC45 HE MS10 1050 270 360 49 XBC45 HS MS12 1250 531 360 88 XBC45...

Страница 8: ...471 64 XBC25 HE MBS S 421 402 275 421 402 342 302 292 252 40 XBC25 HE MBS L 992 973 846 421 402 342 302 292 252 54 XBC45 HS MBS S 700 681 415 700 681 400 360 571 531 60 XBC45 HS MBS L 1070 1051 785 70...

Страница 9: ...ds should be secured to the Unistrut channel and extended to be fixed to the four piece support brackets to be used on the underside of the attenuators Figure 15 Note once the attenuators are supporte...

Страница 10: ...5 XBC65 EXHAUST RT XBC65 INTAKE RT 3 12 2 Optional Exhaust Intake Terminals 3 12 3 Terminal Part Codes 16 17 Weatherproof Kit Installation Motorised Damper Installation 3 13 Motorised Dampers If match...

Страница 11: ...t at the connection points and to make sure that they run without any kinks 18 19 Damper Wiring Switch Wiring S1 S2 S3 S1 S2 S3 1 0 1 0 1 0 0 1 230V Auxiliary switch Notes Caution Power supply voltage...

Страница 12: ...Unit Condensate drain connection 8 mm flexible pipe Control box Coil connections 40mm centres Access to Condensate tray and Pump IMPORTANT The condensate pump incorporates an alarm function If the wat...

Страница 13: ...ure Units must not be operated without all access panels in place damage to equipment or injury to personnel may result Units must not be operated unless control interlocks are in place damage to equi...

Страница 14: ...riginal CAGE CLAMP terminals blocks 5 7 4 Fitting Jumpers Terminal blocks can be connected together to increase the number of terminals at the same potential using push in jumpers In these cases the t...

Страница 15: ...E G F H I 5 8 Unit Hardware Positions Diagram 29 30 Hardware Positions I O Damper Wiring 5 8 1 Hardware Position Key A Supply fan drive health B Delivery air temperature sensor C Extract air temperat...

Страница 16: ...20 Document Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 31 Basic Unit Connection 5 10 Basic Unit Connection...

Страница 17: ...1 07 20 Document Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 32 Controller Layout 5 11 Controller Layout Dia...

Страница 18: ...ber 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 5 12 Wiring Diagrams 5 12 1 Unit Sizes 10 15 with No Heating 33 Siz...

Страница 19: ...cument Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 5 12 2 Unit Sizes 25 65 with No Heating 34 Sizes 25 65 wi...

Страница 20: ...ment Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 5 12 3 Unit Sizes 10 15 with LPHW Heating 35 Sizes 10 15 wi...

Страница 21: ...ment Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 5 12 4 Unit Sizes 25 65 with LPHW Heating 36 Sizes 25 65 wi...

Страница 22: ...Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 37 Sizes 10 15 with Electric Heating 5 12 5 Unit Sizes 10 15 wi...

Страница 23: ...Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual 38 Sizes 25 65 with Electric Heating 5 12 6 Unit Sizes 25 65 wi...

Страница 24: ...Sensor When a Room Module PIR sensor is connected via the SA bus the control will automatically use this as an enable signal by default There is a non adjustable minimum run on time of 15mins for Roo...

Страница 25: ...0V input is scaled to 0 100 fan speed demand This is available on IN5 only The fan speed can be adjusted in software using the LCD or a BACnet connection by adjusting the Fan Speed Demand object Fan S...

Страница 26: ...turn air temperature the outside air temperature and the heat exchanger efficiency e g 13 C outside air temperature with a 23 C return air temperature will give a supply air temperature of 20 5 C The...

Страница 27: ...ce in critical alarm state the unit will drive all heating and cooling outputs to 0V In the event of fan fail other functions continue as normal The critical alarm is latched and requires power cycle...

Страница 28: ...Enable The state of the enable input IN8 BI 10161 N A 0 Off 1 On 9 Run on Enable Run on timer value AV 10267 0 Seconds 24 Local Calendar 0 CAL 10496 N A 0 33 Enable via Schedule Enabled via Schedule M...

Страница 29: ...d Dead band for temp control AV 10266 3 Degrees Celsius 32 SetPoint Op Setpoint operation MSV 10214 Software Setpoint Only 1 Last Changed 2 Software Only 3 Last Changed with Timeout 19 Setpoint Timeou...

Страница 30: ...Speed Schedule Current state of the Fan Speed Demand Schedule object AV 17830 0 Percent 44 Fan Override Operation Chooses the operation of the 3 speed fan override MSV 17975 Override Has Priority 1 Ov...

Страница 31: ...A Degrees Celsius 4 RM201 Humidity The Humidity at RM address 201 AI 10077 N A Percent Relative Humidity 7 RM201 Setpoint The setpoint at RM address 201 AV 10083 N A Degrees Celsius 3 RM202 Temp The t...

Страница 32: ...he state of Alarm Circuit 1 BI 10167 N A 0 Alarm 1 Normal 20 Alarm Circuit 2 The state of Alarm Circuit 2 BI 10170 N A 0 Alarm 1 Normal 11 High Temp Alarm Supply temp which will trip the high supply a...

Страница 33: ...to be changed The instance number range is 1 4 194 303 222 Ecosmart Connect controllers use a MSTP network for communication and are assigned a MSTP address 4 127 by the dip switch located on the fro...

Страница 34: ...e 7 Case 5 Priority 1 Null Priority 2 Null Priority 3 Null Priority 4 Null Priority 5 Null Priority 6 Null Priority 7 Null Priority 8 Null Priority 9 Null Priority 10 Null Priority 11 Null Priority 12...

Страница 35: ...nstance 10185 Object Type AO Present Value 0 State Text Volts Object Properties Object Name Enable Object Instance 10288 Object Type MSV Present Value On State Text Off On Object Properties Object Nam...

Страница 36: ...has a USB 2 0 Type B receptacle which is only used to obtain power from a computer or USB adapter A mains adapter and cable is supplied The router connects to the FC bus via screwed terminals 8 2 BACn...

Страница 37: ...49 ESCO LCD Navigating the ESCO LCD 8 5 Navigation Cancel Quit and moves to the previous section Home Shortcut to the configured Home Page Back Moves to the previous page in the same section Forward...

Страница 38: ...bject within the entire network 8 7 1 Choosing A Target Object To choose a target object Navigate to the settings page Select the right arrow four times to reach the Select Target Device screen Enter...

Страница 39: ...the settings page Select the right arrow twice to reach the display settings screen Change the user password a 4 digit number The user password will now be requested each time a locked object is writt...

Страница 40: ...n be accessed by selecting the alarm icon Alarm events are logged with a date and time Nor represents a change to a normal state Ala represents a change to an alarm state The text in parentheses denot...

Страница 41: ...he value of the Max_Master property of the node s Device object 127 APDU Time The APDU Timeout property defines the amount of time in seconds the FAD waits for responses from other devices 3 8 8 2 Dis...

Страница 42: ...hen accessing the Network View the FAD launches a Network Discovery function The purpose of this function is to find other BACnet devices residing on the same MS TP trunk The maximum number of devices...

Страница 43: ...s 9 2 4 Room Humidity The ESC RM 2 TDH 120 model includes a push button on the face of the network sensor to allow occupants to view the temperature and relative humidity of the zone Pressing the push...

Страница 44: ...dard Sensor Small Room Module Dimensions Large Room Module Dimensions CO2 Sensor SA SA Bus Com SA Power from Controller 15 VDC SA Bus Screw Terminal Block Network Sensor COM SA PWR Screw Terminal Bloc...

Страница 45: ...YES YES YES YES 199 fixed Max of 1 per controller Group 2 Max of 4 Per Controller ESCO TS 80x80 YES 200 203 ESCO THS 80x80 YES YES 200 203 ESCO TDS 80x80 YES YES 200 203 ESCO TDHS 80x80 YES YES YES 2...

Страница 46: ...Angular Degrees up to a distance of 15 ft 4 6m Based on a clear line of sight Ambient Operating Conditions 10 to 30 C 10 to 90 RH Temp Probe 10 to 60 C Ambient Storage Conditions 20 to 60 C t to 95 R...

Страница 47: ...adaptor 3 way female RJ12 adaptor RJ12 Sensor jack Cable Type Pre fabricated 3 twisted pair with RJ12 Plugs 26AWG Room Module Room Module RJ12 Plug RJ12 Plug Room Module Sensor SA Bus RJ 12 Modular Ja...

Страница 48: ...trickle the fans at all times 10 1 4 Setting Supply Air Temperature If a room module is fitted with an integral LCD the air off temperature is set by the end user via the adjustment dial e g ESCO TDS...

Страница 49: ...ocessed in energy from waste centres Remaining Items can be further segregated and processed in accordance with the zero waste hierarchy Please call After Sales Support for further information on item...

Страница 50: ...re supplied with the specified equipment e g wall mounting brackets They are to be used to support the equipment only Other system components must have separate provision for support 4 3 Flanges and c...

Страница 51: ...51 21 07 20 Document Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual NOTES...

Страница 52: ...52 21 07 20 Document Number 671954 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Connect C Control Installation Manual NOTES...

Отзывы: