XBC+ with Ecosmart Connect (C) Control
Installation Manual
6.14.7 Heat Boost
LCD Browser
Page
BACnet Object
Description
Object
Type
Object
ID
Default
Value
Units
30
Heat Boost
Software enabled Heater boost
MSV
10205
Off
(1)Off (2)On
11
Heat Boost Setpoint
Heater Boost Setpoint
AV
10276
35
Degrees-Celsius
6.14.8 Extract Setback
44
Extract Setback
Puts the extract fan to setback speed
MSV
17769
Off
(1)Off (2)On
19
Extract Setback
Speed
The extract fan speed when Extract Setback
is enabled.
AV
18258
30
Percent
6.14.9 Fan Outputs
6
Supply Fan Output
The 0-10v signal to the supply fan
AO
10182
N/A
Volts
6
Extract Fan Output
The 0-10v signal to the extract fan
AO
10176
N/A
Volts
21
Fan Enabled Cmd
The state of the fan enabled relay.
BO
10191
N/A
(1)Off (2)On
6.14.10 Fan Commissioning
9
Extract Fan Max
Individual fan maximum speed setting
AV
10268
100
Percent
10
Extract Fan Min
Individual fan minimum speed setting
AV
10270
20
Percent
15
Supply Fan Max
Individual fan maximum speed setting
AV
10312
100
Percent
15
Supply Fan Min
Individual fan minimum speed setting
AV
10314
20
Percent
6.14.11 Temperature Controls
14
Software Setpoint
Software Setpoint
AV
10309
22
Degrees-Celsius
9
Deadband
Dead band for temp control
AV
10266
3
Degrees-Celsius
32
SetPoint Op
Setpoint operation
MSV
10214
Software
Setpoint Only
(1)Last Changed (2)Software
Only (3)Last Changed with
Timeout
19
Setpoint Timeout
The time before reverting to software
setpoint when last changed with timeout is
selected.
AV
17971
3600
Seconds
27
Setpoint Schedule
A schedule for setpoint adjustment.
SCH
18215
N/A
0
19
Setpoint Schedule
Current state of the Setpoint Schedule
object.
AV
18215-
22
Degrees-Celsius
32
T Sens. Op
Temperature sensor operation
MSV
10215
NS Average
(1)NS Average (2)Return Air
Only (3)NS & Return Average
33
0-10v Temp Range
Temperature sensor range
MSV
10216
0 to 50°C
(1)0 to 50°C (2)0 to 40°C
(3)0 to 100°C (4)0 to 80°C
(5)0 to 90°C
35
Temp Control Mode
Temperature control mode
MSV
10245
Supply Temp
(1)Supply Temp (2)Room
Temp
14
STC H/C Pref
STC Heat/Cool Pref
AV
10310
50
No units
15
STC HX Efficiency
STC HX Efficiency
AV
10311
0.8
No units
13
RTC Boost Band
The Return Temperature Control Boost Band AV
10306
15
Degrees-Celsius
14
RTC Max Supply
Temp
Maximum supply temp when in RTC mode
AV
10307
35
Degrees-Celsius
14
RTC Min Supply
Temp
Minimum supply temp when in RTC mode
AV
10308
12
Degrees-Celsius
6.14.12 Heating Output
30
Heating Type
Set the type of heating fitted.
MSV
10206
As per Build
(1)None (2)LPHW (3)Electric
(4)3rd-Party
6
Heating Output
The 0-10v signal to the heating output
AO
10179
N/A
Percent
22
Heating Demand
Cmd
The state of the heating demand relay.
BO
10197
N/A
(0)Off (1)On