8.7.3 Setting Favourites
The “Favourite” screen displays a list of favourite objects. To add or
remove favourites:
•
Navigate to the settings page.
•
Select the right arrow six times to reach the View Config screen.
•
Select the function tick box and favourite star.
•
Select the home icon.
•
Navigate to the network page.
•
Select the appropriate controller.
•
Navigate to the required object. See “Exposed BACnet Object List”
for a full list (pressing for 3 seconds on an object will display the
full name.)
•
Select the star to turn it black.
•
Navigate and select any other required favourites.
•
When finished, navigate back to the View Config screen in the
settings section and remove the function tick.
Favourites can be removed by browsing the favourites page, selecting
an object and then selecting the trashcan. Favourites can be re-
ordered by uploading the favourite settings to a USB memory stick and
changing the order of the items in the favourites.csv file. This file can
then be downloaded back to the LCD.
Enable
On
Fan Boost
Off
Heat Boost
Off
Trickle Mode
Off
Name
Write
ID
Description
Status
Function
53
54
Setting Favourites
Setting Passwords
Network Page Description
Object Type
Object ID
16
Room Air Temp
AV
11296
16
CO2 Level
AV
13980
16
Humidity
AV
14297
16
Active Setpoint
AV
14534
33
Enable
MSV
10218
26
Time Schedule
SCH
10496
27
Fan Speed Schedule
SCH
17798
34
Fan Boost
MSV
10240
30
Heat Boost
MSV
10205
1
Fresh Air Temperature AI
10008
14
Software Setpoint
AV
10309
8.7.4 Setting User Password
•
Navigate to the settings page.
•
Select the right arrow twice to reach the display settings screen.
•
Change the user password a 4 digit number.
•
The user password will now be requested each time a locked
object is written.
•
The user password is also needed to exit the target page (when
the homepage is set to target).
8.7.5 Setting Service Password
•
Navigate to the settings page.
•
Select the right arrow twice to reach the display settings screen.
•
Change the service password a 4 digit number.
•
The service password will now be requested each time the settings
page is accessed.
Network Page Description
Object Type
Object ID
33
Enable
MSV
10218
26
Time Schedule
SCH
10496
27
Time Schedule
SCH
10496
34
Fan Boost
MSV
10240
30
Heat Boost
MSV
10205
14
Software Setpoint
AV
10309
8.7.6 Disable Writing Of Values
•
Navigate to the settings page.
•
Select the right arrow six times to reach the View Config screen.
•
De-select the write tick box. All controller points are now read
only.
•
A service password will need to be set to stop users re-enabling
the write function.
8.7.7 Allow Basic Values To Be Written By User
•
Navigate to the settings page.
•
Select the right arrow six times to reach the View Config screen.
•
Select the function tick box and lock.
•
Select the home icon.
•
Navigate to the network page.
•
Select the appropriate controller.
•
Navigate to the required object. See “Exposed BACnet Object List”
for a full list.
•
Select any values that need password protection. A black lock
indicates a locked value.
•
When finished, navigate back to the View Config screen in the
settings section. Remove the Function tick and enable writing of
values.
•
A user password will need to be set to stop writing of locked
values. It is recommended that all values are locked except the
following;
Backlight
Home Page
Service Password
User Password
Stand by
Stand by Timer
Stand-by-OFF
Target
0
0
Dark
0
Select Target Device