XBC+ with Ecosmart Connect (C) Control
Installation Manual
8.8.3 Select Target Device Page
Parameter Name
Description
Default Setting
Device Name
Name of the device where the object resides
MAC Address
The MSTP address of the device where the object resides
Device ID
The BACnet ID of the device where the object resides
Object Type
The object type
Object ID
The object BACnet ID
8.8.4 View Configuration
Parameter Name
Description
Default Setting
Name / Description
Chooses whether objects are described by their name or description
Name
Write
Allows editing of objects
Yes
ID
This will display the BACnet ID next to all BACnet objects on the
network, favourites and target pages
Yes
Function
(Favourite / Lock)
This option allows objects to be added to the favourite or locked list.
Once it is selected, navigate to the network page and choose which
objects are required.
A user password is required to change any locked object, if set. All
values are unlocked by default.
None
8.9 Multiple Controllers
When accessing the Network View the FAD launches a Network
Discovery function. The purpose of this function is to find other BACnet
devices residing on the same MS/TP trunk. The maximum number of
devices supported by the FAD discovery function is 32.
8.10 Controller Wiring
There are two ways of connecting the LCD.
•
Connected to the FC bus using screwed terminals. A separate
power supply is required.
•
If the controller is standalone, the LCD display can be connected
to the RJ12 FC bus port on the front of the FAC controller. This
FC port will also power the LCD, so in this case, a separate power
supply is not required.
57
Controller Wiring
ON
+
-
+
-
12...24 VAC
12...24 VAC
BACnet
MS/TP
1
2
3
4
5
6
7
1 2
One of the following cables is required to do this.
ESCO-LCD-3M
Ecosmart-Connect LCD RJ12 Connection Cable 3m
ESCO-LCD-5M
Ecosmart-Connect LCD RJ12 Connection Cable 5m
ESCO-LCD-10M
Ecosmart-Connect LCD RJ12 Connection Cable 10m
ESCO-LCD-20M
Ecosmart-Connect LCD RJ12 Connection Cable 20m
ESCO-LCD-30M
Ecosmart-Connect LCD RJ12 Connection Cable 30m
Network Page
Description
1-3
Unused
4
Power Supply (-) 12...24 VAC / VDC
5
Power Supply (+) 12...24 VAC / VDC
6
BACnet MS/TP Port (RT-)
7
BACnet MS/TP Port (RT+)
Programming USB Port
DIP Switch 1
BACnet MS/TP Line Terminator (End of Network
120
Ω
resistor switch).
DIP Switch 2
Unused