background image

4

26. 01. 22. Document Number  671829

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

BPS H-AT

Installation Manual

4.0 DELIVERY & RECEIPT OF EQUIPMENT

All equipment is inspected prior to despatch and leaves the factory in 
good condition. Upon receipt of the equipment an inspection should be 
made and any damage indicated on the delivery note.

Particulars of damage and/or incomplete delivery should be endorsed 
by the driver delivering the goods before offloading by the purchaser.

No responsibility will be accepted for damage sustained during the 
offloading from the vehicle or on the site thereafter.

All claims for damage and/or incomplete delivery must be reported to 
Nuaire within two days of receipt of the equipment.

4.1 Unit Offloading and Handling

The weight of unit modules and palletised items is displayed on the 
packaging. Some of the modules have an uneven weight distribution 
and this will be indicated by labelling where appropriate. 

Offloading and positioning of the equipment is the responsibility of 
the purchaser, and should only be performed by competent personnel 
following an appropriate risk assessment.

To ensure that the delivery vehicle is loaded according to the 
planned method of offloading, Nuaire must be notified to ensure 
coordination.

 When offloading, care must be taken to ensure that the 

AHU is kept level at all times.

To ensure that no roof damage occurs additional timber packaging 
must be used.

4.2 Base Frame Lifting Points

When units are constructed of multiple modules each module will have 
it’s own individual base frame, which is then connected to the next to 
assemble the full system. 

Only individual modules should be lifted 

or manoeuvred. The units must not be lifted or manoeuvred pre-
assembled.

All base frame sections will have 50mm square lifting holes at the 
end of each side to enable lifting. In addition to this, covered fork 
lifting channels are located across the width of the base frame, if the 
module length is sufficient to allow this. For shorter modules the fork 
lifting points will be along the length of the section, without a covered 
channel (Figure 3). 

Palletised.

Forklift.

Assembly with 

base frame.

Typical Methods of Lifting

Slings via spreaders fitted to

unit with base frame.

4.3 Unit Packaging

Unless otherwise specified, unit sections will be delivered to site 
covered in “shrink wrap”  polythene, which should provide a more than 
adequate level of protection against inclement weather.

Should alternative methods of unit protection be required (i.e. timber, 
Corex, or flame retardant materials), Nuaire Limited should be notified 
of the specific requirements at the pre- contract stage. Waste must 
be disposed of by a registered waste carrier in accordance to national 
regulations.

4.4 Unit Storage

The equipment must be stored in a dry, internal location. Ductwork 
connection apertures should be sealed against the ingress of dust, 
water and vermin. Note that units that are intended for external 
locations are generally not fully weatherproofed until their installation, 
including ductwork connections, is complete.

If the storage period is to exceed two months, contact Nuaire for 
guidance on the appropriate ‘mothballing’ procedures. Do not stack 
units, modules or components.

Base Frame Detail

Section length

Section length

Section length

50.0

Se

ct

ion w

id

th

50.0

50

.0

50

.0

50

.0

100

.0

100.0

100.0

150

Overall unit length

A (1:5)

50.0

50

.0

50mm x 50mm Lifting hole

CENTRE SUPPORT CAN BE ON EITHER SIDE OF CENTRE LINE

A

Содержание BPS H-AT

Страница 1: ...nufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel b...

Страница 2: ...ion operation and maintenance for installers and users of the BOXER PACKAGED SOLUTION BPS AHU units with heat recovery The BPS AHU range is manufactured from Aluzinc corrosion resistant steel with 50m...

Страница 3: ...ust Right Handed for Horizontal PHX Units Frost Coil Electric 2 B AH FE R BPS size Frost Coil Electric 36kW Right Handed for Horizontal PHX Units B AH FE L BPS size Frost Coil Electric 36kW Left Hande...

Страница 4: ...m Only individual modules should be lifted or manoeuvred The units must not be lifted or manoeuvred pre assembled All base frame sections will have 50mm square lifting holes at the end of each side to...

Страница 5: ...tray may be inspected and cleaned if necessary The LPHW and Electrical heater settings coil bleed and drain and all other control adjustments are similarly accessible Side access where possible is pr...

Страница 6: ...s EXTRACT SUPPLY INTAKE DISCHARGE Access Shown from top Right hand R Access 600mm 600mm 10 Top View of Access For Right Hand Plate Heat Exchanger Units 5 2 Access Areas 5 2 1 Left Hand Plate Heat Exch...

Страница 7: ...for the units failing a site leakage test if the above have not been carried out correctly 6 3 Module Joints After unwrapping temporarily remove the rubber weatherproof cover strip and M10 base frame...

Страница 8: ...ixed with the bolts provided The equipment must not be exposed to the weather in an unassembled or partially assembled state All roof terminal ductwork sealing and assembly work must be completed befo...

Страница 9: ...t the requirement of removing the roof terminal Figure 17 6 11 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled for BPS sizes 07 12 and 17 on a double skinne...

Страница 10: ...8 A 35 A 13 9 A 13 9 A 35 A B 20H AT 12 8 A 12 8 A 53 A 17 3 A 17 3 A 53 A B820H AT 9 6 A 9 6 A 53 A 14 1 A 14 5 A 53 A Denotes any Character These heater models require a separate power supply for t...

Страница 11: ...ER UNIT Unit Isolator 21 Isolator Locations 7 6 3 Network Settings IP address 192 168 11 12 Subnet mask 255 255 255 0 LAN 011 node 012 7 7 Connection Chart Description iQ4E Terminal No 8DO Terminal No...

Страница 12: ...ocks 24 Removing a Conductor from a Terminal 7 9 4 Jumpers Terminal blocks can be commoned together to increase the number of terminals at the same potential using push in jumpers In these cases the t...

Страница 13: ...0 8 20 Section 7 10 3 Section 7 10 4 Section 7 10 6 Section 7 10 8 7 10 Wiring Diagrams A series of basic connection wiring diagrams have been provided to assist on site wiring In order to reference t...

Страница 14: ...Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 4 Unit Sizes 05 20 with Electric Heating No or CHW Cooling 31 Unit Sizes 07 22 with Electric Heatin...

Страница 15: ...671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 5 Unit Sizes 05 10 with No or LPHW Heating Reverse Cycle DX 32 Unit Sizes 07 12 with No or LP...

Страница 16: ...671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 6 Unit Sizes 15 20 with No or LPHW Heating Reverse Cycle DX 33 Unit Sizes 15 20 with No or LP...

Страница 17: ...r 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 7 Unit Sizes 05 10 with Electric Heating Reverse Cycle DX 34 Unit Sizes 05 10 with Electric...

Страница 18: ...r 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 8 Unit Sizes 15 20 with Electric Heating Reverse Cycle DX 35 Unit Sizes 15 20 with Electric...

Страница 19: ...ed the unit will increase the fans speeds as required until the pressure differential between the extract air and atmosphere reaches the constant pressure setpoint The pressure sensor is a 0 10v 0 100...

Страница 20: ...dule module is provided in the Trend strategy When the schedule is on the heating output reverts to LPHW Electric heating The enable run on time must be set to 3 minutes for reverse cycle units This i...

Страница 21: ...ecirc Force Recirc damper to recirc mode On Off Off 52 Damper NoRecirc Force Recirc damper out of recirc mode On Off Off Knob No Name Description Range Default 2 Run on Time Run on timer value 0 3600...

Страница 22: ...maximum voltage to be supplied to the fan motor 6 10 v 10 v 41 CP Loop Gain Constant Pressure Loop Gain 0 50 0 5 42 IO Damper Delay Delay to allow inlet outlet dampers to open 0 300 sec 0 sec 43 Boos...

Страница 23: ...concentration and temperature of the air The space sensors have additional options of humidity monitoring and a 4 digit display The display will show the measured values in succession The duct sensor...

Страница 24: ...literature is available please contact Nuaire This applies to any components not specifically mentioned in this document 9 0 MAINTENANCE It is important that maintenance checks are recorded and that t...

Страница 25: ...commissioning the unit ensure that all equipment has been assembled in accordance with the installation procedure all instances where the unit is in operation the access doors should remain closed at...

Страница 26: ...s See interconnection section for details No external connections are required Electric heater elements are protected by a fail safe over temperature switch which will disconnect the heater supply if...

Страница 27: ...ner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other paper compon...

Страница 28: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...

Страница 29: ...29 26 01 22 Document Number 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual NOTES...

Отзывы: