BPS H-AT

Installation Manual

8.17 Setpoints

Most of the following are user adjustable within engineered limits:

Switch 

No.

Name

Description

Range

Default

1

Enable

Software enable switch

On/Off

Off

3

Trickle Mode

When On, fans will trickle even with no enable signal

On/Off

Off

5

Wiring Verification

Factory Use Only

On/Off

Off

7

Boost

Software boost switch

On/Off

Off

10

Tachofitted

For units with tacho to digital converter. Fan fault will be ignored if fans are 
stopped intentionally.

On/Off

Off

11

Fan & Heater Test

Factory Use Only

On/Off

Off

12

ForceOverheat

Factory Use Only

On/Off

Off

13

Fan Only Test

Factory Use Only

On/Off

Off

14

DamperBypass

Force HX to Bypass

On/Off

Off

15

DamperOutOfBypass

Force HX to HX

On/Off

Off

22

Force Stop on Low Temp

Stops fans upon LOWTEMPALARM

On/Off

Off

23

Summer Night Free Cool Active

Set night cooling mode as active

On/Off

Off

33

Alarm Reset

Resets alarm on change of value

On/Off

Off

49

Enable Constant Pressure

Enabled constant pressure mode

On/Off

Off

50

IO Damper Fitted

Imposes fan delay to allow dampers to open.

On/Off

Off

51

DamperRecirc

Force Recirc damper to recirc mode

On/Off

Off

52

Damper NoRecirc

Force Recirc damper out of recirc mode

On/Off

Off

Knob 

No.

Name

Description

Range

Default

2

Run-on Time

Run-on timer value

0-3600 Sec

0 sec

4

SetTemp

Desired temperature setpoint

10-30 °C

22°C

5

UI4 Fun.1=CO2 2=Occ 3=FSC

Input 4 Function, 0 = None, 1 = CO2/T/D, 2 = Trend Occ, 3=FSC

0-3

0

6

Deadband

Dead-band for temp control

0-10 k

3k

7

UI5 Func.1=CO2 2=Occ 3=FSC

Input 5 Function, 0 = None, 1 = CO2/T/D, 2 = Trend Occ, 3=FSC

0-3

0

8

Supply Fan Max

Individual fan maximum speed setting

20-100%

100%

9

Supply Fan Min

Individual fan minimum speed setting. (Trickle speed)

0-100%

20%

10

Extract Fan Max

Individual fan maximum speed setting

20-100%

100%

11

Extract Fan Min

Individual fan minimum speed setting. (Trickle speed)

0-100%

20%

12

Supply Fan Boost

Supply fan boost speed

20-100%

100%

13

Extract Fan Boost

Extract fan boost speed

20-100%

100%

14

CO2 Target

The target setpoint for CO2 control

0-10000 PPM

650 PPM

15

CO2 Range Min

The lower limit CO2 value corresponding to the limit voltage

0-10000 PPM

0 PPM

16

CO2 Voltage Min

The lower limit voltage corresponding to the limit of range

0-10 v

0 v

17

CO2 Range Max

The upper limit CO2 value corresponding to the limit voltage

0-10000 PPM 2000 PPM

18

CO2 Voltage Max

The upper limit voltage corresponding to the limit of range

0-10 v

10 v

19

Alarm Delay

Alarm hold-off delay

0-300 Sec

15 sec

Содержание BPS H-AT

Страница 1: ...nufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel b...

Страница 2: ...ion operation and maintenance for installers and users of the BOXER PACKAGED SOLUTION BPS AHU units with heat recovery The BPS AHU range is manufactured from Aluzinc corrosion resistant steel with 50m...

Страница 3: ...ust Right Handed for Horizontal PHX Units Frost Coil Electric 2 B AH FE R BPS size Frost Coil Electric 36kW Right Handed for Horizontal PHX Units B AH FE L BPS size Frost Coil Electric 36kW Left Hande...

Страница 4: ...m Only individual modules should be lifted or manoeuvred The units must not be lifted or manoeuvred pre assembled All base frame sections will have 50mm square lifting holes at the end of each side to...

Страница 5: ...tray may be inspected and cleaned if necessary The LPHW and Electrical heater settings coil bleed and drain and all other control adjustments are similarly accessible Side access where possible is pr...

Страница 6: ...s EXTRACT SUPPLY INTAKE DISCHARGE Access Shown from top Right hand R Access 600mm 600mm 10 Top View of Access For Right Hand Plate Heat Exchanger Units 5 2 Access Areas 5 2 1 Left Hand Plate Heat Exch...

Страница 7: ...for the units failing a site leakage test if the above have not been carried out correctly 6 3 Module Joints After unwrapping temporarily remove the rubber weatherproof cover strip and M10 base frame...

Страница 8: ...ixed with the bolts provided The equipment must not be exposed to the weather in an unassembled or partially assembled state All roof terminal ductwork sealing and assembly work must be completed befo...

Страница 9: ...t the requirement of removing the roof terminal Figure 17 6 11 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled for BPS sizes 07 12 and 17 on a double skinne...

Страница 10: ...8 A 35 A 13 9 A 13 9 A 35 A B 20H AT 12 8 A 12 8 A 53 A 17 3 A 17 3 A 53 A B820H AT 9 6 A 9 6 A 53 A 14 1 A 14 5 A 53 A Denotes any Character These heater models require a separate power supply for t...

Страница 11: ...ER UNIT Unit Isolator 21 Isolator Locations 7 6 3 Network Settings IP address 192 168 11 12 Subnet mask 255 255 255 0 LAN 011 node 012 7 7 Connection Chart Description iQ4E Terminal No 8DO Terminal No...

Страница 12: ...ocks 24 Removing a Conductor from a Terminal 7 9 4 Jumpers Terminal blocks can be commoned together to increase the number of terminals at the same potential using push in jumpers In these cases the t...

Страница 13: ...0 8 20 Section 7 10 3 Section 7 10 4 Section 7 10 6 Section 7 10 8 7 10 Wiring Diagrams A series of basic connection wiring diagrams have been provided to assist on site wiring In order to reference t...

Страница 14: ...Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 4 Unit Sizes 05 20 with Electric Heating No or CHW Cooling 31 Unit Sizes 07 22 with Electric Heatin...

Страница 15: ...671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 5 Unit Sizes 05 10 with No or LPHW Heating Reverse Cycle DX 32 Unit Sizes 07 12 with No or LP...

Страница 16: ...671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 6 Unit Sizes 15 20 with No or LPHW Heating Reverse Cycle DX 33 Unit Sizes 15 20 with No or LP...

Страница 17: ...r 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 7 Unit Sizes 05 10 with Electric Heating Reverse Cycle DX 34 Unit Sizes 05 10 with Electric...

Страница 18: ...r 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 8 Unit Sizes 15 20 with Electric Heating Reverse Cycle DX 35 Unit Sizes 15 20 with Electric...

Страница 19: ...ed the unit will increase the fans speeds as required until the pressure differential between the extract air and atmosphere reaches the constant pressure setpoint The pressure sensor is a 0 10v 0 100...

Страница 20: ...dule module is provided in the Trend strategy When the schedule is on the heating output reverts to LPHW Electric heating The enable run on time must be set to 3 minutes for reverse cycle units This i...

Страница 21: ...ecirc Force Recirc damper to recirc mode On Off Off 52 Damper NoRecirc Force Recirc damper out of recirc mode On Off Off Knob No Name Description Range Default 2 Run on Time Run on timer value 0 3600...

Страница 22: ...maximum voltage to be supplied to the fan motor 6 10 v 10 v 41 CP Loop Gain Constant Pressure Loop Gain 0 50 0 5 42 IO Damper Delay Delay to allow inlet outlet dampers to open 0 300 sec 0 sec 43 Boos...

Страница 23: ...concentration and temperature of the air The space sensors have additional options of humidity monitoring and a 4 digit display The display will show the measured values in succession The duct sensor...

Страница 24: ...literature is available please contact Nuaire This applies to any components not specifically mentioned in this document 9 0 MAINTENANCE It is important that maintenance checks are recorded and that t...

Страница 25: ...commissioning the unit ensure that all equipment has been assembled in accordance with the installation procedure all instances where the unit is in operation the access doors should remain closed at...

Страница 26: ...s See interconnection section for details No external connections are required Electric heater elements are protected by a fail safe over temperature switch which will disconnect the heater supply if...

Страница 27: ...ner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other paper compon...

Страница 28: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...

Страница 29: ...29 26 01 22 Document Number 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual NOTES...

Отзывы: