background image

24

26. 01. 22. Document Number  671829

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

BPS H-AT

Installation Manual

All coils sit in a common drip tray connected to the pre-fitted 
condensate pump.

The coil panel has been pre-drilled and fitted with appropriate 
grommets for pipe connections. Do not drill or cut the unit casing for 
this purpose.

Coils should have their finned surface examined for accumulation of 
dirt, lint and biological contaminants or similar. If necessary, wash 
down affected areas with a mild detergent solution and a soft brush. 
Care should be taken not to damage the finned surface, and any 
cleaning fluids should be rinsed away with water.

A compressed air line may be used to blow out any solids between 
fins. Do not probe the coil fin block with metal objects as damage 
may cause leaks. Drain lines should be checked to ensure that they 
are unobstructed and free draining. Drain pans should be flushed out 
periodically to remove contamination.

The unit application may require particular attention to this item – 
Check with Building Management personnel for details.

9.6 Legionella Check

Legionella risk management should be undertaken by a competent 
person appointed by the duty holder in accordance with the latest 
edition of the HSE approved code of practice L8 Legionnaires’ disease, 
the control of legionella bacteria in water systems. Particular attention 
should be given to:

Cooling coil.

Thermal Wheel.

Drain trays.

Water reservoirs.

9.7 Electric Heaters

An air handling unit would normally require no heater maintenance. 
However a periodic check is advised to ensure that the fasteners and 
electrical connections are operating correctly.

The electric heater unit is fitted with fail-safe thermal switches (self-
resetting) which will isolate the electric heater supply if a temperature 
of 80°C is detected. This action is performed independently of any 
controls fitted. Nuaire fitted controls will also stop heating if a fan or 
heater failure is detected.

9.8 Bulkhead Lights

Ensure that lights are switched off and isolated before checking or 
changing the lamp.

9.9 General

Inspect all internal and external surfaces to check for corrosion or 
peeling of painted surfaces.

Thoroughly clean affected areas with a wire brush, apply a coat of zinc 
rich primer or similar, and re-touch with suitable finishing paint. Ensure 
tightness of all nuts, bolts, and fixings.

Check all components for general condition.

9.10 Specialist Equipment

Contact Nuaire for maintenance of specialised equipment that 
would have been specified during design stage. A breakdown of the 
component parts can be found on the design specification documents, 
additional maintenance literature is available, please contact Nuaire.

This applies to any components not specifically mentioned in this 
document.

9.0 MAINTENANCE

It is important that maintenance checks are recorded and that the 
schedule is always adhered to, in all cases, the previous report should 
be referred to.

9.1 Fans

Please refer to general arrangement drawings for details of the type 
of fan and drive that is fitted. Maintenance guidelines for all fans are 
beyond this manual, please contact Nuaire for specific documents.

Before any work is carried out, please ensure that:

The power supply to the motor is switched off.

The fan impeller is at rest.

Measures are taken to ensure that the accidental, uncontrolled running 
of the fan is prevented during maintenance work.

In general, fans should be inspected twice a year, and care should be 
taken to ensure that any unusual vibration or sound is investigated as 
an urgent matter.

Access to the fan section is via hinged or lift-off panels. Cable entry 
must be made through the apertures provided. Screwed glands with 
cable restraint devices should be used.

9.2 General Fan Maintenance

Access to the fan is normally gained by opening the hinged access 
doors.

Care should be taken to remove any build up of dust (a light vacuum or 
light brushing will normally take care of this) Do not use a steam or any 
other high pressure cleaners.

Inspect the connection between the fan and unit for any damage or 
wear and tear.

9.3 Bearings

The bearings that are fitted will be (unless otherwise specified) “sealed 
for life”, therefore consequence maintenance is not required. 

Fan bearings are lifelong; up to 40,000 hours of operation. In cases of 
heavy duty operation, maintenance intervals are to be established by 
the operator.

9.4 Filters

When removing the filter access panels, pay attention to the airflow 
direction marked on the panel, this must be replaced to the exact 
position prior to being removed. Disposable filters should be checked, 
and changed when they become fully laden with dust. Washable filters 
should be removed and washed in a mild detergent, flushed with clean 
water and allowed to dry before refitting.

9.5 Coils

Coils should be connected to ensure that full counter flow exists i.e. the 
entering airflow meets the return connection.

All coils should be connected with the flow at the bottom and the 
return at the top unless otherwise advised. Drain and bleed valves are 
located on the coil, others may be required in the system pipe-work 
depending on the installation.

Frost protection must be incorporated on shut down and fresh air 
conditions to avoid coil freezing. Ideally, where the system is at risk of 
frost damage, the addition of a proprietary antifreeze solution to the 
water is recommended.

Pipe-work connections should be made to the unit using appropriate 
techniques, and must be independently supported. The connections 
should be pressure tested. 

Содержание BPS H-AT

Страница 1: ...nufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel b...

Страница 2: ...ion operation and maintenance for installers and users of the BOXER PACKAGED SOLUTION BPS AHU units with heat recovery The BPS AHU range is manufactured from Aluzinc corrosion resistant steel with 50m...

Страница 3: ...ust Right Handed for Horizontal PHX Units Frost Coil Electric 2 B AH FE R BPS size Frost Coil Electric 36kW Right Handed for Horizontal PHX Units B AH FE L BPS size Frost Coil Electric 36kW Left Hande...

Страница 4: ...m Only individual modules should be lifted or manoeuvred The units must not be lifted or manoeuvred pre assembled All base frame sections will have 50mm square lifting holes at the end of each side to...

Страница 5: ...tray may be inspected and cleaned if necessary The LPHW and Electrical heater settings coil bleed and drain and all other control adjustments are similarly accessible Side access where possible is pr...

Страница 6: ...s EXTRACT SUPPLY INTAKE DISCHARGE Access Shown from top Right hand R Access 600mm 600mm 10 Top View of Access For Right Hand Plate Heat Exchanger Units 5 2 Access Areas 5 2 1 Left Hand Plate Heat Exch...

Страница 7: ...for the units failing a site leakage test if the above have not been carried out correctly 6 3 Module Joints After unwrapping temporarily remove the rubber weatherproof cover strip and M10 base frame...

Страница 8: ...ixed with the bolts provided The equipment must not be exposed to the weather in an unassembled or partially assembled state All roof terminal ductwork sealing and assembly work must be completed befo...

Страница 9: ...t the requirement of removing the roof terminal Figure 17 6 11 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled for BPS sizes 07 12 and 17 on a double skinne...

Страница 10: ...8 A 35 A 13 9 A 13 9 A 35 A B 20H AT 12 8 A 12 8 A 53 A 17 3 A 17 3 A 53 A B820H AT 9 6 A 9 6 A 53 A 14 1 A 14 5 A 53 A Denotes any Character These heater models require a separate power supply for t...

Страница 11: ...ER UNIT Unit Isolator 21 Isolator Locations 7 6 3 Network Settings IP address 192 168 11 12 Subnet mask 255 255 255 0 LAN 011 node 012 7 7 Connection Chart Description iQ4E Terminal No 8DO Terminal No...

Страница 12: ...ocks 24 Removing a Conductor from a Terminal 7 9 4 Jumpers Terminal blocks can be commoned together to increase the number of terminals at the same potential using push in jumpers In these cases the t...

Страница 13: ...0 8 20 Section 7 10 3 Section 7 10 4 Section 7 10 6 Section 7 10 8 7 10 Wiring Diagrams A series of basic connection wiring diagrams have been provided to assist on site wiring In order to reference t...

Страница 14: ...Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 4 Unit Sizes 05 20 with Electric Heating No or CHW Cooling 31 Unit Sizes 07 22 with Electric Heatin...

Страница 15: ...671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 5 Unit Sizes 05 10 with No or LPHW Heating Reverse Cycle DX 32 Unit Sizes 07 12 with No or LP...

Страница 16: ...671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 6 Unit Sizes 15 20 with No or LPHW Heating Reverse Cycle DX 33 Unit Sizes 15 20 with No or LP...

Страница 17: ...r 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 7 Unit Sizes 05 10 with Electric Heating Reverse Cycle DX 34 Unit Sizes 05 10 with Electric...

Страница 18: ...r 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual 7 10 8 Unit Sizes 15 20 with Electric Heating Reverse Cycle DX 35 Unit Sizes 15 20 with Electric...

Страница 19: ...ed the unit will increase the fans speeds as required until the pressure differential between the extract air and atmosphere reaches the constant pressure setpoint The pressure sensor is a 0 10v 0 100...

Страница 20: ...dule module is provided in the Trend strategy When the schedule is on the heating output reverts to LPHW Electric heating The enable run on time must be set to 3 minutes for reverse cycle units This i...

Страница 21: ...ecirc Force Recirc damper to recirc mode On Off Off 52 Damper NoRecirc Force Recirc damper out of recirc mode On Off Off Knob No Name Description Range Default 2 Run on Time Run on timer value 0 3600...

Страница 22: ...maximum voltage to be supplied to the fan motor 6 10 v 10 v 41 CP Loop Gain Constant Pressure Loop Gain 0 50 0 5 42 IO Damper Delay Delay to allow inlet outlet dampers to open 0 300 sec 0 sec 43 Boos...

Страница 23: ...concentration and temperature of the air The space sensors have additional options of humidity monitoring and a 4 digit display The display will show the measured values in succession The duct sensor...

Страница 24: ...literature is available please contact Nuaire This applies to any components not specifically mentioned in this document 9 0 MAINTENANCE It is important that maintenance checks are recorded and that t...

Страница 25: ...commissioning the unit ensure that all equipment has been assembled in accordance with the installation procedure all instances where the unit is in operation the access doors should remain closed at...

Страница 26: ...s See interconnection section for details No external connections are required Electric heater elements are protected by a fail safe over temperature switch which will disconnect the heater supply if...

Страница 27: ...ner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other paper compon...

Страница 28: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...

Страница 29: ...29 26 01 22 Document Number 671829 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H AT Installation Manual NOTES...

Отзывы: