Lx Series Installation and Operation Instructions
│
Trinity Lx
43
10.0
BOILER AND HEATING SYSTEM PIPING
The heat exchanger of the Trinity boiler is designed to attain the highest level of heat transfer in a compact
design. To accomplish this, the heating water flows through a series of fin shaped tubes, designed to maximize
the heat transfer area. To maintain the efficient and reliable operation of the heat exchanger, and to avoid heat
exchanger failure, it is critical to ensure the rules and guidelines in this section are followed.
Failure to follow the instructions provided in this section will void the NTI warranty and
may result in property damage, fire, serious injury or death.
Boiler System Preparation
Prior to connecting plumbing to the boiler, flush the entire system to ensure it is free of sediment, flux, solder,
scale, debris or other impurities that may be harmful to the system and boiler.
During the assembly of the
heating system, it is important to keep the inside of the piping free of any debris including construction and
copper dust, sand and dirt.
For retrofits, all system piping including radiators, must be cleansed of all build-up including sludge and scale.
All systems, old and new, must be cleansed to remove flux, grease and carbon residue. NTI recommends
cleansing the boiler system with “Fernox F3 Cleaner”. For retrofit applications with heavy limescale and sludge
deposits, a heavier duty cleaner may be required; NTI recommends the use of “Fernox DS-40 System Cleaner”.
For information on performing the cleansing, follow the instructions included with the Fernox DS-40 System
Cleaner. See Table 10-1 for a list of recommended boiler cleansing products.
Failure to rid the heating system of the contaminants listed above will void your NTI
warranty and may result in premature heat exchanger failure and property damage.
Table 10-1 Boiler System Cleansers and Corrosion Inhibitors
Application
Fernox Product
NTI Part # Description
Boiler Water Treatment
F1 Protector
83448
Corrosion inhibitor.
Cleanser for new and old systems
F3 Cleaner
83449
Removes flux, grease and carbon residue.
Cleanser for Retrofits
DS-40 System Cleaner
83450
Removes heavy limescale and sludge deposits.
Boiler Water
Pressure -
The Trinity boilers are intended solely for use in pressurized closed loop heating systems operating
with a minimum pressure of 15 PSI at the boiler outlet. To obtain the minimum system design pressure,
follow the piping diagrams illustrated in this section.
Oxygen Elimination
- This boiler may only be installed in a pressurized closed-loop heating system, free of air
(oxygen) and other impurities. To avoid the presence of oxygen, ensure all of the air is removed from the
system during commissioning via strategically placed adequately sized air-removal devices, located
throughout the heating system. See figures in this section detailing the location of the primary air-removal
device required for the boiler. Immediately repair any leaks in the system plumbing to avoid the addition of
make-up water; make-up water provides a source of oxygen and minerals that may lead to heat exchanger
failure. Failure to follow these instructions will result in poor performance, unnecessary wear of system
components and premature failure.
The Trinity Lx is not approved for operation in an “open system”, thus it cannot be used
for direct potable water heating or process heating of any kind.
Water Chemistry
– The installer of the Trinity Lx boiler must consider the condition of the water in the heating
system. Ensure the condition of the boiler water falls within the following parameters:
PH – between 7.5 and 9.5.
Iron – less than 0.5mg/l.
Chloride – less than 125mg/l.
Copper – less than 0.1mg/l.
Conductivity – 100 to 300µS/cm (at 25ºC); [TDS 50 to 150ppm or Total Hardness 3 to 9grains/USgal.]
Содержание Trinity Lx 150
Страница 61: ...Lx Series Installation and Operation Instructions Trinity Lx 61 Figure 13 1 b Ladder Logic Diagram Lx150 400...
Страница 62: ...Trinity Lx Installation and Operation Instructions Lx Series 62 Figure 13 2 a Connection Diagram Lx500 800...
Страница 63: ...Lx Series Installation and Operation Instructions Trinity Lx 63 Figure 13 2 b Ladder Logic Diagram Lx500 800...
Страница 103: ...Lx Series Installation and Operation Instructions Trinity Lx 103 NOTES...