Strain on the gas valve and fittings may result in vibration, premature component failure
and leakage and may result in a fire, explosion, property damage, serious injury or death.
Flexible gas piping cannot be used within the boiler cabinet and cannot pass through the
cabinet wall, use rigid piping as shown in Figure 7-1. Failure to follow these instructions
may result in fire, property damage, serious injury or death.
Do not use an open flame to test for gas leaks. Failure to follow these instructions may
result in fire, property damage, serious injury or death .
When performing a pressure test on the gas line piping, be sure the boiler is disconnected
or isolated if the test pressure is expected to exceed 1/2 PSI (14” w.c.), as damage to the
valve could occur resulting in
fire, property damage, serious injury or death.
Figure 7-1 Gas Line Connection (Typical)
Model Lx200 Illustrated
Manual Shutoff Valve
Union
Drip Leg
Rigid Gas Line Piping
Use only rigid gas line piping within the
appliance cabinet. Rigid piping must
protrude beyond the outside of the
cabinet wall.
Flexible Gas Line Piping
Recommended to eliminate strain
on the appliance gas components
(only use if acceptable by local
codes).
Manual Shutoff Valve
- Should
overheating occur or the gas
supply fail to shut off, turn off the
manual gas control valve to the
appliance.
Содержание Trinity Lx 150
Страница 61: ...Lx Series Installation and Operation Instructions Trinity Lx 61 Figure 13 1 b Ladder Logic Diagram Lx150 400...
Страница 62: ...Trinity Lx Installation and Operation Instructions Lx Series 62 Figure 13 2 a Connection Diagram Lx500 800...
Страница 63: ...Lx Series Installation and Operation Instructions Trinity Lx 63 Figure 13 2 b Ladder Logic Diagram Lx500 800...
Страница 103: ...Lx Series Installation and Operation Instructions Trinity Lx 103 NOTES...