Trinity Lx
│
Installation and Operation Instructions
Lx Series
6
2.0 SPECIFICATIONS
Table 2-1 Specifications
DESCRIPTION
Lx150
Lx150E
Lx200
Lx300
Lx400
Lx800
CSA Input Modulation
1
btu/hr [kw]
25,000-150,000
2
[7.3-44.0]
25,000-150,000
[7.3-44.0]
25,000-199,000
[7.3-58.3]
55,000-275,000
[16.1-80.5]
75,000-399,000
[21.9-117]
160,000-800,000
[46.9-234]
DOE Heating Capacity
1, 3
btu/hr [kw]
136,000
[39.8]
139,000
[40.7]
182,000
[53.3]
251,000
[73.5]
374,000
[109.6]
749,000
[219.5]
Net I=B=R Rating
1,3
btu/hr [kw]
118,000
[34.8]
121,000
[35.4]
158,000
[46.3]
213,000
[62.4]
325,000
[95.2]
650,000
[190.5]
DOE AFUE
3
%
95.1
97.0
95.1
95.1
94.0
6
94.0
6
Recovery Rating @
100
o
F Rise, gal/hr
-
-
224
310
450
902
Water Connections - NPT, in.
1
4
1
1
1-1/4
1-1/4
2
Gas Connection - NPT, in.
1/2
1/2
1/2
1/2
3/4
1
Vent/Air-Intake
Pipe
Dia.
respectively, in. [mm]
5
3
7
or 4
[ 76 or 102]
3
7
or 4
[ 76 or 102]
3
7
or 4
[ 76 or 102]
4 or 6
[102 or 152]
4 or 6
[102 or 152]
4 or 6
8
[102 or 152]
Vent/Air-Intake,
Max. Length, ft. [m]
105
7
[32]
105
7
[32]
105
7
[32]
100
[30.5]
100
[30.5]
100
9
[30.5]
Dimensions H x W x D
in. [mm]
29.5x17x18.5
[749x432x470]
29.5x17x18.5
[749x432x470]
29.5x17x18.5
[749x432x470]
36x17x21.5
[915x432x546]
36x17x24
[915x432x610]
37x17x63.5
[938
x
432
x
613]
Approx. Appliance Weight
with Water, lbs [kg]
100 [45.3]
125 [56.7]
125 [56.7]
180 [31.7]
225 [102]
450 [104]
Electrical Rating
120V / 1 Phase / 60 Hz / 12A
Notes:
1
Listed Input and Output ratings are at minimum vent lengths at Sea Level. Numbers will be lower with longer venting
and/or altitudes greater then 2000 feet [610 m].
2
The maximum output when operating on LP-Gas is limited to 145,000 Btu/hr [42.5 kW].
3
Based on rating plate input capacities, using standard test procedures prescribed by the U.S. Department of Energy.
Ratings have been confirmed by AHRI (GAMA), excluding Lx400 and Lx800.
4
Units sold in Canada are 3/4” NPT.
5
Trinity Lx require a special venting system, use only vent materials and methods detailed in these instructions.
6
Steady-State Efficiency Rating.
7
Models Lx150-200, when using 3" venting on LP, max. equivalent length = 50 feet.
8
Only 6” exhaust vent is permissible for the Lx800. Air intake pipe can be 4” or 6”.
9
Model Lx800 operates with Natural Gas only.
Wall mounted units requires two people to lift the appliance into place or property damage
and personal injury may result.
High Altitude Operation
The Trinity is designed to operate at its maximum listed capacity in installations less than or equal to 2000 ft
[610 m] above Sea Level. Since the density of air decreases as elevation increases, maximum specified capacity
should be de-rated for elevations above 2000 ft [610 m] in accordance with Table 2-2.
Table 2-2 De-rate % for High Altitudes
Elevations
2000 ft [610 m]
3000 ft [914 m]
4000 ft [1219 m]
4500 ft [1372 m]
5000 ft [1524 m]
In Canada
1
de-rate by 5%
de-rate by 5%
de-rate by 5%
de-rate by 5%
de-rate % may vary
In USA
2
-
de-rate by 4%
de-rate by 8%
-
de-rate by 12%
Notes:
1
Canada: Altitudes between 2000-4500 ft [610-1372 m], de-rate by 5%. Consult local authorities for de-rating capacities
for altitudes above 4500 ft [1372 m].
2
USA: De-rate capacity by 4% for every 1000 ft [305 m] over 2000 ft [610 m].
Combustion – At elevations above 2000 feet, the combustion of the appliance must be
checked with a calibrated combustion analyzer to ensure safe and reliable operation. It is
the Installers responsibility to check the combustion and to adjust the combustion in accordance to
Section 9.0. Failure to follow these instructions may result in property damage, serious injury, or death.