Trinity Lx
│
Installation and Operation Instructions
Lx Series
46
Refractory Ceramic Fibers (RFC)
Personal Protective Equipment Recommended - Read the following warnings and
handling instructions carefully before commencing any service work in the combustion
chamber. The insulating material on the inside of the burner door and at the back of the combustion chamber
contain Refractory Ceramic Fibers and should not be handled without personal protective equipment.
Potential Carcinogen - Use of Refractory Ceramic Fibers in high temperature
applications (above 1000
o
C) can result in the formation of Crystalline Silica
(cristobalite), a respirable silica dust. Repeated airborne exposure to crystalline silica dust may result in chronic
lung infections, acute respiratory illness, or death. Crystalline silica is listed as a (potential) occupational
carcinogen by the following regulatory organizations:
International Agency for Research on Cancer (IARC),
Canadian Centre for Occupational Health and Safety (CCOHS), Occupational Safety and Health Administration
(OSHA), and National Institute for Occupational Safety and Health (NIOSH). Failure to comply with handling
instructions in Table 14-1 may result in serious injury or death.
Crystalline Silica - Certain components confined in the combustion chamber may
contain this potential carcinogen. Improper installation, adjustment, alteration, service or
maintenance can cause property damage, serious injury (exposure to hazardous materials) or death. Refer to
Table 14-1 for handling instruction and recommended personal protective equipment. Installation and service
must be performed by a qualified installer, service agency or the gas supplier (who must read and follow the
supplied instructions before installing, servicing, or removing this appliance. This appliance contains materials
that have been identified as carcinogenic, or possibly carcinogenic, to humans).
Table 14-1 Handling Instructions for Refractory Ceramic Fibers (RCF)
Reduce the Risk of Exposure
Precautions and Recommended Personal Protective Equipment
Avoid contact with skin and eyes
•
Wear
long-sleeved clothing, gloves, and safety goggles or glasses
.
Avoid breathing in silica dust
•
Wear a respirator with a N95-rated filter efficiency or better.
1
•
Use water to reduce airborne dust levels when cleaning the combustion chamber.
•
Do not dry sweep silica dust. Pre-wet or use a vacuum with a high efficiency filter.
Avoid transferring contamination
•
When installing or removing RFCs, place the material in a sealable plastic bag.
•
Remove contaminated clothing after use. Store in sealable container until cleaned.
•
Wash contaminated
clothing separately from other laundry.
First Aid Measures
If irritation persists after implementing first aid measures consult a physician.
•
Skin - Wash with soap and water.
•
Eyes - Do not rub eyes; flush with water immediately.
•
Inhalation – Breathe in fresh air; drink water, sneeze or cough to clear irritated
passage ways.
Notes:
1
R
espirator recommendations based on CCOHS and OSHA requirements at the time this document was written. Consult
your local regulatory authority regarding current requirements for respirators, personal protective equipment, handling,
and disposal of RCFs.
For more information on Refractory Ceramic Fibers, the risks, recommended handling procedures and
acceptable disposal practices contact the organization(s) listed below:
Canada (CCOHS): Telephone directory listing
under Government Blue Pages Canada—Health and
Safety—Canadian Centre for Occupational Health
and Safety; or website http://www.ccohs.ca.
United States (OSHA): Telephone directory listing
under United States Government—Department of
Labor—Occupational Safety and Health
Administration; or website http://www.osha.gov.
Содержание Lx150-800
Страница 40: ...Trinity Lx Installation and Operation Instructions Lx Series 40 Figure 10 1 b Lx150 400 Ladder Logic Diagram...
Страница 41: ...Lx Series Installation and Operation Instructions Trinity Lx 41 Figure 10 2 a Lx800 Connection Diagram...
Страница 42: ...Trinity Lx Installation and Operation Instructions Lx Series 42 Figure 10 2 b Lx800 Ladder Logic Diagram...