NTI E-ACLM-V/-P AC LINE MONITOR
8
USE AND OPERATION
For instruction on how to monitor and use the data provided by the E-ACLM-V / -P Line Monitors, see the ENVIROMUX manual.
Most of the features configurable on the E-ACLM-V and -P Line Monitors are common to all sensors and are described in the
manual for the ENVIROMUX. This manual will introduce features that are new and not described in that manual.
The sensor status page for the E-ACLM-V and –P includes a chart detailing information not found in the primary status bar. The
chart includes:
the last reading taken for the line frequency
number of swells,sags, and spikes that have occurred
the current setting of the spike threshold.
the current status of the outlet relay (ACLM-P only)
The E-ACLM-P additionally displays the present current draw and either the input voltage or the power consumption depending
on whether the sensor status being viewed is the “Power Status” or the “Voltage Status” respectively, as seen in the images
below.
Figure 7- Status windows for E-ACLM sensors
primary status bar
Added information
chart
ACLM-P Power Status Page
ACLM-P Voltage Status Page
ACLM-V Voltage Sensor Status Page
ACLM-V (or P) Frequency Sensor Status
Note: For E-ACLM-P18 only, the relay state
while ON and powering a device will be
“Open”, not “Closed”