NTI E-ACLM-V/-P AC LINE MONITOR 

 

3

 
E-ACLM-Pxx-V2

 

The E-ACLM-P12,-P18 and –P8 (ACLM-P) are triple sensors for the E-16D/5D/2D (ENVIROMUX) capable of monitoring 

AC line input voltages between 50~250V AC, the Frequency (Hertz) between 47~63Hz, and the Power (Current) up to 12 
amperes (for –P12), 8 amperes (for –P8) or 18 amperes (for –P18) from a single AC line. It will report the current RMS AC 
Voltage, AC Frequency and RMS AC Power to the ENVIROMUX. The ACLM-P will also monitor the number of short term Swells

1

 

and Sags

2

 as well as the number of Spikes

3

.    

  The ACLM-P12-V2 is rated for 12A of continuous load, 15A max.   

  The ACLM-P8-V2 is rated for 8A of continuous load, 10A max.    

  The ACLM-P18-V2 is rated for 18A of continuous load, 20A max.     

 

The ACLM-P8/P12 uses a UL certified IEC 320 C14 inlet to connect to the AC line and a UL certified IEC 320 C13 socket 

to connect the AC load.   The ACLM-P18 uses a UL certified IEC 320 C20 inlet to connect to the AC line and a UL certified IEC 
320 C19 socket to connect the AC load. 

           The E-ACLM-P8/P12/P18 is connected to the ENVIROMUX through up to 1,000 ft of CAT5/5e/6 cable (

Exception

: When 

connected to the E-5D/2D the cable length is limited to 750 ft (24AWG min.) for E-ACLM-P18). Data is transmitted to and from the 
ENVIROMUX utilizing the RS485 protocol.  ACLM-P is installed between the power source and the load device, able to sense a 
maximum surge current of 20A and will calculate and report the RMS AC Power. The device utilizes standard connection sockets 
for easy user installation.  The ACLM-P is also equipped with a power interrupt feature, which allows power to be disconnected 
from the load device based on manual disconnect or configuration settings via the web interface.  

The ACLM-P includes a resettable circuit breaker to protect the sensor from damage in the event the load device 

exceeds the rating of the ACLM-Pxx circuits.   In the event the circuit breaker should trip, remove the overload condition and reset 
the circuit breaker.      

Note: The circuit breaker will not allow a reset until it has reached reset condition, which may take between 1 and 3 
minutes from the time the breaker tripped.  

Features & Functions: 

 

12 bit ADC resolution, 1% full scale ADC accuracy 

 

Measure AC Voltage ACLM-Pxx-V2 (

±1%FS at 32°F to 104°F (0°C to 40°C))

 

 

Measure AC Frequency (@1% accuracy) 

 

Monitors swells, sags, and spike events 

 

Measures AC Current and Power (2.7% accuracy) 

 

Optional Power Disconnect and Reconnect  

 

Auto-Configured upon connection with E-XD 

 

RJ45 Status LED’s for operating status 

 

User selectable data interpolation options 

 

Measuring the AC Voltage, AC Frequency, Power and Current Flow; Determining Swells, and Sags: 

The ACLM-P provides constant monitoring of the AC line with an active sampling rate of 12,000 samples per second. 

The measurement data is transmitted to the ENVIROMUX once every second. Each time data is sent, the ACLM-P will report the 
present AC line voltage, frequency, current and calculated power, as well as the number of sags, swells, and spikes that have 
occurred since the last data transmission. 

After the ACLM-P has transmitted data to the ENVIROMUX, any stored values in the ACLM-P will be erased as new data 

is acquired. 

If a swell, sag, or spike event lasts longer than 1 second  (5 seconds, for example)  it will be counted as multiple events 

by the ENVIROMUX because the ENVIROMUX will reset the data record to 0 each time the ACLM-P reports the data to the 
ENVIROMUX.    The count displayed on the screen will be updated based on the configured Refresh Rate.      

Measuring Spikes: 

The ACLM-P is also capable of recording the number of Spike events with a peak greater than 50V, 250V, 500V, or 1KV 

as configured by the user.   For example, if the spike threshold is set at 500V and the sensor records a spike exceeding 500V for 
at least 5 microseconds, the ENVIROMUX will report a spike above 500V. 

The User Interface: 

From the Web Interface of the ENVIROMUX, the ACLM-P sensor can be customized and monitored. The user can define 

the maximum and minimum threshold values for AC power and frequency, and configure the ENVIROMUX to send alerts based 
on the power thresholds or disconnect power based on the voltage, current, frequency or power thresholds. The user may also 
define the threshold for spike measurement. 

 

 

 

 

Содержание ENVIROMUX Series

Страница 1: ...NE MONITORS Installation and Operation Manual ENVIROMUX Series NETWORK TECHNOLOGIES INCORPORATED Tel 330 562 7070 Fax 330 562 1999 1275 Danner Dr Aurora OH 44202 www networktechinc com NTI R E ACLM V V2 Front and Rear View E ACLM P12 V2 Front and Rear View ...

Страница 2: ...E ACLM V P the E xD that it is connected to must first have firmware version 4 5 or later installed In order for the E xD to add the Frequency sensor of the E ACLM V P to the list of sensors any previously installed E ACLM V or ACLM P must first be deleted from the E xD Summary page Within 30 seconds the E xD will re sense the E ACLM V P and will include the Frequency sensor in the list of sensors...

Страница 3: ... 13 TABLE OF FIGURES Figure 1 Rotate the tabs for Zero RU mounting 4 Figure 2 Connect ACLM V to voltage source s 5 Figure 3 Connect E ACLM P12 to voltage source and load 6 Figure 4 Connect E ACLM P18 to voltage source and load 6 Figure 5 Connect sensor to E 16D Sensor Cable 7 Figure 6 CAT5 Cable pinout 7 Figure 7 Status windows for E ACLM sensors 8 Figure 8 Configurations page for sensors 9 Figure...

Страница 4: ...20 C14 to IEC 320 C13 Cord Set for connection to AC load Materials supplied for E ACLM P18 V2 NTI E ACLM P18 V2 1 Line cord L6 20p to IEC 320 C19 1 Device cord L6 20r to IEC 320 C20 2 Mounting tabs for Zero RU mounting pre assembled to back of E ACLM P18 see page 4 2 10 32 x 3 4 pan head screws and 10 32 cage nuts server cabinet mounting hardware URL slip with location of this manual Materials Not...

Страница 5: ...based on the configured Refresh Rate Measuring Spikes The ACLM V is also capable of recording the number of Spike events with a peak greater than 50V 250V 500V or 1KV as configured by the user For example if the spike threshold is set at 500V and the sensor records a voltage exceeding 500V for at least 5 microseconds the ENVIROMUX will report a spike above 500V The User Interface From the Web Inte...

Страница 6: ...until it has reached reset condition which may take between 1 and 3 minutes from the time the breaker tripped Features Functions 12 bit ADC resolution 1 full scale ADC accuracy Measure AC Voltage ACLM Pxx V2 1 FS at 32 F to 104 F 0 C to 40 C Measure AC Frequency 1 accuracy Monitors swells sags and spike events Measures AC Current and Power 2 7 accuracy Optional Power Disconnect and Reconnect Auto ...

Страница 7: ... relay Note As a result of the data transmission rate of the ACLM P once per second and the browser refresh rate of the ENVIROMUX up to once per second the ACLM P will report Sags or Swells on the AC line that may not be reflected in the numeric voltage display MOUNTING The E ACLM V or P can be placed on a solid surface mounted to a wall or mounted to an accessible surface within a rack Zero RU To...

Страница 8: ...tage source 50 250VAC 47 63Hz to the ACLM V at AC IN 2 Note The voltage source connected to AC IN 1 does not need to be the same voltage or frequency as the voltage source connected to AC IN 2 Figure 2 Connect ACLM V to voltage source s NOTE A maximum of fourteen 14 E ACLM V may be connected to an E 16D seven 7 on RJ45 Sensor ports 1 8 and seven 7 on RJ45 Sensor ports 9 16 ...

Страница 9: ...evice to the AC OUT that is compatible with the voltage source connected to AC IN The device connected to AC OUT must be rated at 12A or less for model P12 8A or less for P8 or 18A or less for P18 Figure 3 Connect E ACLM P12 to voltage source and load Figure 4 Connect E ACLM P18 to voltage source and load The use of E ACLM P18 requires E xD firmware version 2 35 or newer ...

Страница 10: ...MUX and the Cat5 port on the ACLM V P sensor is terminated with RJ45 connectors and must be wired according to the EIA TIA 568 B industry standard Wiring is as per the table and drawing below Pin Wire Color Pair 1 White Orange 2 2 Orange 2 3 White Green 3 4 Blue 1 5 White Blue 1 6 Green 3 7 White Brown 4 8 Brown 4 Figure 6 CAT5 Cable pinout T 1 R 2 T 3 R 4 T 5 R 6 T 7 R 8 Pair 2 Pair 1 Pair 4 Pair...

Страница 11: ... last reading taken for the line frequency number of swells sags and spikes that have occurred the current setting of the spike threshold the current status of the outlet relay ACLM P only The E ACLM P additionally displays the present current draw and either the input voltage or the power consumption depending on whether the sensor status being viewed is the Power Status or the Voltage Status res...

Страница 12: ...ers of the sensor Note Configuration options on this page are similar to those of other ENVIROMUX sensors and are covered at length in the ENVIROMUX manual Figure 8 Configurations page for sensors Maximum and Minimum Critical Threshold values define what will be counted as a Swell and Sag respectively ...

Страница 13: ...disconnect power through the relay the Disconnect Type must be set to Manual Reconnect on normal Select if the outlet should be powered ON when the reading has returned to the normal operating range provided the Disconnect Type isn t set to Manual Enable Min Threshold Select if the outlet should power OFF when the minimum threshold setting is reached Minimum Threshold Define what the minimum thres...

Страница 14: ...are version 4 5 when an E ACLM Px V2 is connected an additional Power Relay sensor is installed The Power Relay gives user direct control over the ON OFF function of the relay The user can quickly change the state of the relay at any time provided the relay Disconnect Type above and previous page is set to Manual Figure 11 ACLM P V2 Power Relay Sensor The user can select Deactivate or Activate pre...

Страница 15: ... V2 8A Continuous Current ACLM P18 V2 18A Maximum Current ACLM P12 V2 15A Maximum Current ACLM P8 V2 10A Maximum Current ACLM P18 V2 20A Current Accuracy 2 7 Voltage Supply 12VDC from E XD Max Current Consumption ACLM P12 P8 V2 130mA Max Current Consumption ACLM V V2 70mA Max Cable Length from Sensor to E 16D 1000 ft Max Cable Length from Sensor to E 2D 5D ACLM V V2 1000ft ACLM P8 12 V2 1000ft ACL...

Страница 16: ...ot refreshed Updated E xD with version 2 29 or later Delete the E ACLM V P from the Summary page and wait 30 seconds for sensor to be re sensed by the E xD See Note below Note In order for the E xD to add the Frequency sensor of the E ACLM V P to the list of sensors any previously installed E ACLM V or ACLM P must first be deleted from the E xD Summary page Within 30 seconds the E xD will re sense...

Отзывы: