NTI E-ACLM-V/-P AC LINE MONITOR
12
TECHNICAL SPECIFICATIONS
Sensor Performance Specifications
AC Inlet (ACLM-V-V2)....................................................................IEC 320 C14
AC Inlet (ACLM-P12/-P8-V2) .........................................................IEC 320 C14
AC Outlet (ACLM-P12/-P8-V2) ......................................................IEC 320 C13
AC Intlet (ACLM-P18-V2)...............................................................IEC 320 C20
AC Outet (ACLM-P18-V2)..............................................................IEC 320 C19
Maximum Spike Threshold ............................................................1kVAC
Voltage Range ...............................................................................50 to 250VAC
Voltage Frequency Range .............................................................47 to 63Hz
Voltage Accuracy .......................................................................... ±1%FS at 32°F to 104°F (0°C to 40°C)
Frequency Accuracy ...................................................................... ±1%
Measurable Current range......................................................... ...300mA to 20A
Continuous Current (ACLM-P12-V2) ............................................12A
Continuous Current (ACLM-P8-V2) ..............................................8A
Continuous Current (ACLM-P18-V2) ............................................18A
Maximum Current (ACLM-P12-V2) ...............................................15A
Maximum Current (ACLM-P8-V2) .................................................10A
Maximum Current (ACLM-P18-V2) ...............................................20A
Current Accuracy .......................................................................... ±2.7%
Voltage Supply..............................................................................12VDC from E-XD
Max Current Consumption (ACLM-P12/P8-V2).............................130mA
Max Current Consumption (ACLM-V-V2)......................................70mA
Max. Cable Length (from Sensor to E-16D)..................................1000 ft
Max. Cable Length (from Sensor to E-2D/5D)……...................….ACLM-V-V2 1000ft
ACLM-P8/12-V2 1000ft
ACLM-P18-V2 750ft (24AWG minimum)
Communication Type ....................................................................RS485
Data rate .......................................................................................96kbps max
General Specifications
Temperature Range......................................................................32° to 104° F (0° to 40° C)
Humidity Range ............................................................................20% to 80% RH
Enclosure Size (WxDxH) ..............................................................2.5” x 3.25" x 1.03”
Compliance Specifications
CE Mark........................................................................................BS EN55022: 2006+A1:2007
ESD Protection .............................................................................BS EN61000-4-2: 2009
RoHS ............................................................................................All parts comply with RoHS