7 Settings
PCS-978 Transformer Relay
7-15
Date: 2013-01-16
No
.
Setting Item
Range
Step
Unit
Description
19
x.21.ZG1.OutMap
0000~
FFFF
Tripping
logic
setting
of
stage
1
of
phase-to-earth impedance protection
20
x.21.ZG2.Z_Fwd
0.05~200
0.01
Ω
Forward impedance setting of stage 2 of
phase-to-earht impedance protection
21
x.21.ZG2.Z_Rev
-100~1000
0.01
Ω
Reverse impedance setting of stage 2 of
phase-to-earth impedance protection
22
x.21.ZG2.t_Op
0.05~20
0.001
s
Time delay of stage 2 of phase-to-earth
impedance protection
23
x.21.ZG2.En
0: disable
1: enable
1
Logic setting of enabling/disabling stage 2 of
phase-to-earth impedance protection
24
x.21.ZG2.OutMap
0000~
FFFF
Tripping
logic
setting
of
stage
2
of
phase-to-earth impedance protection
7.3.11 Phase Overcurrent Protection Settings
Table 7.3-11 Setting list of phase overcurrent protection (x=HVS, MVS, LVS) (stage n, n=1, 2, 3)
No.
Setting Item
Range
Step
Unit
Description
1
x.50/51P.Upp_VCE
2~200
0.001
V
Phase-to-phase undervoltage setting.
2
x.50/51P.U2_VCE
2~200
0.001
V
Negative-sequence overvoltage setting.
3
x.50/51P.RCA
0~360
1
deg
Relay characteristic angle of phase overcurrent
protection.
4
x.50/51P.K_Hm2
0.05~1.0
0.001
Harmonic blocking coefficient of phase overcurrent
protection.
5
x.50/51P.I_Rls_Hm
Blk
0.04~150
0.001
A
Current setting of releasing harmonic blocking
function of phase overcurrent protection.
6
x.50/51P.Opt_Hm_
Blk
0~1
1
Logic setting of selecting blocking mode of
harmonic.
“0”: phase segerated blocking mode;
“1”: phase crossing blocking mode.
7
x.50/51P.En_VTS_
Blk
0: disable
1: enable
1
Logic setting of enabling voltage controlled phase
overcurrent protection being blocked during VT
circuit failure.
8
x.50/51Pn.I_Set
0.04A~30In
0.001
A
Current setting of stage n of phase overcurrent
protection.
9
x.50/51Pn.t_Op
0~3600
0.001
s
Time delay of stage n of phase overcurrent
protection.
10
x.50/51Pn.En_VCE
0: disable
1: enable
Logic setting of enabling voltage control element for
phase overcurrent protection.
11
x.50/51Pn.Opt_Dir
0~2
1
Logic setting of selecting control mode of directional
element to stage n of phase overcurrent protection.
0: no direction;
Содержание PCS-978
Страница 1: ...PCS 978 Transformer Relay Instruction Manual NR Electric Co Ltd ...
Страница 2: ......
Страница 6: ...Preface PCS 978 Transformer Relay IV Date 2013 01 16 ...
Страница 10: ...Preface PCS 978 Transformer Relay VIII Date 2013 01 16 ...
Страница 62: ...3 Operation Theory PCS 978 Transformer Relay 3 p Date 2013 01 16 ...
Страница 250: ...4 Supervision PCS 978 Transformer Relay 4 b Date 2013 01 16 ...
Страница 264: ...4 Supervision PCS 978 Transformer Relay 4 14 Date 2013 01 16 ...
Страница 266: ...5 Management PCS 978 Transformer Relay 5 b Date 2013 01 16 ...
Страница 272: ...5 Management PCS 978 Transformer Relay 5 6 Date 2013 01 16 ...
Страница 334: ...6 Hardware Description PCS 978 Transformer Relay 6 60 Date 2013 01 16 ...
Страница 370: ...8 Human Machine Interface PCS 978 Transformer Relay 8 d Date 2013 01 16 ...
Страница 404: ...8 Human Machine Interface PCS 978 Transformer Relay 8 34 Date 2013 01 16 ...
Страница 406: ...9 Configurable Function PCS 978 Transformer Relay 9 b Date 2013 01 16 ...
Страница 446: ...10 Communication PCS 978 Transformer Relay 10 26 Date 2013 01 16 ...
Страница 448: ...11 Installation PCS 978 Transformer Relay 11 b Date 2012 10 09 ...
Страница 456: ...11 Installation PCS 978 Transformer Relay 11 8 Date 2012 10 09 ...
Страница 458: ...12 Commissioning PCS 978 Transformer Relay 12 b Date 2012 12 07 ...
Страница 468: ...12 Commissioning PCS 978 Transformer Relay 12 10 Date 2012 12 07 ...
Страница 470: ...13 Maintenance PCS 978 Transformer Relay 13 b Date 2012 10 09 ...
Страница 474: ...13 Maintenance PCS 978 Transformer Relay 13 4 Date 2012 10 09 ...
Страница 476: ...14 Decommissioning and Disposal PCS 978 Transformer Relay 14 b Date 2012 10 09 ...
Страница 478: ...14 Decommissioning and Disposal PCS 978 Transformer Relay 14 2 Date 2012 10 09 ...
Страница 480: ...15 Manual Version History PCS 978 Transformer Relay 15 2 Date 2013 01 16 ...