3 Operation Theory
PCS-978 Transformer Relay
3-183
Date: 2013-01-16
Tripping output contacts
10 groups of independent tripping output contacts can be defined to trip HV side, MV side, and
LVS side etc. Each group of tripping contacts can correspond to certain amount of contacts on
binary output plug-in modules.
Tripping logic settings
Tripping logic settings are used to specify which breakers will be tripped when some protection
element operates. This logic setting comprises 16 binary bits as follows and is expressed by a
hexadecimal number of 4 digits from 0000H to FFFFH. The tripping logic setting of the equipment
is specified as follows:
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Fu
n
c
ti
o
n
N/A
Trp
O
u
tp
u
t1
5
Trp
O
u
tp
u
t1
4
Trp
O
u
tp
u
t1
3
Trp
O
u
tp
u
t1
2
Trp
O
u
tp
u
t1
1
Trp
O
u
tp
u
t1
0
Trp
O
u
tp
u
t0
9
Trp
O
u
tp
u
t0
8
Trp
O
u
tp
u
t0
7
Trp
O
u
tp
u
t0
6
Trp
O
u
tp
u
t0
5
Trp
O
u
tp
u
t0
4
Trp
O
u
tp
u
t0
3
Trp
O
u
tp
u
t0
2
Trp
O
u
tp
u
t0
1
NOTE
!
“TrpOutput01” just means to drive 1st group of tripping output contacts to pickup
and please refer to
Chapter “Hardware”
for details. The tripping outputs are recorded as
“T01~T15” by the protection equipment when they operate, and “Txx” (xx=01, 02, …, 15)
represents “Tripoutputxx” (xx=01, 02, …, 15).
The bit corresponding to the breaker to be tripped shall be set as“1” and other bits shall be “0”.
For example, if differential protection operates to make “TrpOutput1”, “TrpOutput2”, “TrpOutput3”
conta
cts pickup, the bit “1” and bit “2” and bit “3” positions shall be filled with “1” and other bit
positions shall be filled with “0”. Then a hexadecimal number 0007H is formed as the tripping
output logic setting, i.e. [87T.OutMap] shall be set as “0007H”.
3.27.3 Programmable Tripping Output Element
10 programmable tripping output elements with inputs, outputs and settings are provided for
visualization programming of user level.
Users can program output of function elements in the device by visualization programming
software if tripping map of protection element provided by protective equipment cannot meet
application requirements completely.
For example, if user need stage 1 of overcurrent protection of HV side operate to issue trip
command after its operation cr
iterion is satisfied “AND” receiving a binary input which can be a
blocking signal from other protection equipment, users can complete the function configuration as
following steps.
1) Set tripping logic setting of stage 1 of overcurrent protection of HV side
as “0”, i.e.
[87T.OutMap]=0000H.
2) Finish required logic programming by visualization programming tool.
Содержание PCS-978
Страница 1: ...PCS 978 Transformer Relay Instruction Manual NR Electric Co Ltd ...
Страница 2: ......
Страница 6: ...Preface PCS 978 Transformer Relay IV Date 2013 01 16 ...
Страница 10: ...Preface PCS 978 Transformer Relay VIII Date 2013 01 16 ...
Страница 62: ...3 Operation Theory PCS 978 Transformer Relay 3 p Date 2013 01 16 ...
Страница 250: ...4 Supervision PCS 978 Transformer Relay 4 b Date 2013 01 16 ...
Страница 264: ...4 Supervision PCS 978 Transformer Relay 4 14 Date 2013 01 16 ...
Страница 266: ...5 Management PCS 978 Transformer Relay 5 b Date 2013 01 16 ...
Страница 272: ...5 Management PCS 978 Transformer Relay 5 6 Date 2013 01 16 ...
Страница 334: ...6 Hardware Description PCS 978 Transformer Relay 6 60 Date 2013 01 16 ...
Страница 370: ...8 Human Machine Interface PCS 978 Transformer Relay 8 d Date 2013 01 16 ...
Страница 404: ...8 Human Machine Interface PCS 978 Transformer Relay 8 34 Date 2013 01 16 ...
Страница 406: ...9 Configurable Function PCS 978 Transformer Relay 9 b Date 2013 01 16 ...
Страница 446: ...10 Communication PCS 978 Transformer Relay 10 26 Date 2013 01 16 ...
Страница 448: ...11 Installation PCS 978 Transformer Relay 11 b Date 2012 10 09 ...
Страница 456: ...11 Installation PCS 978 Transformer Relay 11 8 Date 2012 10 09 ...
Страница 458: ...12 Commissioning PCS 978 Transformer Relay 12 b Date 2012 12 07 ...
Страница 468: ...12 Commissioning PCS 978 Transformer Relay 12 10 Date 2012 12 07 ...
Страница 470: ...13 Maintenance PCS 978 Transformer Relay 13 b Date 2012 10 09 ...
Страница 474: ...13 Maintenance PCS 978 Transformer Relay 13 4 Date 2012 10 09 ...
Страница 476: ...14 Decommissioning and Disposal PCS 978 Transformer Relay 14 b Date 2012 10 09 ...
Страница 478: ...14 Decommissioning and Disposal PCS 978 Transformer Relay 14 2 Date 2012 10 09 ...
Страница 480: ...15 Manual Version History PCS 978 Transformer Relay 15 2 Date 2013 01 16 ...