Novus N1200HC Скачать руководство пользователя страница 8

N1200HC Controller 

NOVUS AUTOMATION 

8/12 

A1t2 
A2t2 
A3t2 
A4t2 

Alarm Time 

t2

 - Defines the temporization time 

t2

 

for the alarms time functions. In seconds. 
The value 0 (zero) disables the function. 

Flsh 

Flash  -  Allows visual signalization of an alarm 

occurrence by flashing the indication of PV in the 

operation level. The user chooses which alarms 

are to be associated with this feature. 

SCALE PARAMETER LEVEL 

Type 

Input Type. Selecting the input type used by the 

controller. See 

Table 1

Mandatorily the first parameter to be set.

 

fltr 

Digital Input Filter - Used to improve the stability of 

the measured signal (PV). Adjustable between 0 

and 20. In 0 (zero) it means filter turned off and 20 

means maximum filter. The higher the filter value, 

the slower is the response of the measured value. 

Dppo 

Decimal Point –  Defines the display of the 

decimal point. 

vnit

 

Unit – Defines the unit of temperature to be used: 
Celsius 

°

(

 or Fahrenheit 

°

Parameter displayed when used temperature 

sensors. 

0ffs 

Offset  –  Parameter that allows the user to make 

corrections in the PV value indicated. 

e.rsp 

Enables remote SP. 

 

YES

    Enables the Function; 

 

no

    Does not enable the Function; 

This parameter is not displayed when the remote 

SP selection is defined by a Digital Input. 

rsp 

Remote SP type - Defines the signal type for the 

remote SP. 

 

0-20

  Current of 0-20 mA; 

 

4-20

  Current of 4-20 mA; 

 

0-5

    Voltage of 0-5 V;

 

 

0-10

  Voltage of 0-10 V; 

Parameter displayed when remote SP is enabled. 

rsll 

Remote SP Low Limit - Sets the range of values of 

the remote SP. Determines the minimum value of 

this range. 
Parameter displayed when remote SP is enabled. 

rskl 

Remote SP High Limit - Sets the range of values of 

the remote SP. Determines the maximum value of 

this range. 
Parameter displayed when remote SP is enabled. 

Spll 

Setpoint Low Limit - Defines the SP lower limit of SP. 
For the linear analog input types available (0-20 mA, 

4-20 mA, 0-50 mV, 0-5 V and 0-10 V), defines the 

minimum PV indication range, besides limiting the 

SP adjustment. 

Spxl 

Setpoint High Limit -  Defines the upper limit for 

adjustment of SP. 
For the linear analog input types available (0-20 mA, 

4-20 mA, 0-50 mV, 0-5 V and 0-10 V), defines the 

maximum PV indication range, besides limiting the 

SP adjustment. 

1e.ov 

 

Percentage of the value to be applied when the 

MV Safe Output function is adopted. If equal to 0 

(zero) the function is disabled and the outputs turn 

off when a sensor failure occurs. 

bavd 

Digital communication Baud Rate selection, in 

kbps 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 and 115.2  

prty 

Parity of the serial communication. 

 

none

  Without parity 

 

Ewem

  Even parity 

 

0dd

  Odd parity 

Addr 

Address  -  Slave address selection: Identifies the 

controller in the network. The possible address 

numbers are from 1 to 247. 

I/OS PARAMETERS LEVEL (INPUTS AND OUTPUTS) 

Io 1 

Function of the channel I/O 1: Selection of the 

function used in the channel I/O 1, according to the 

Table 2

Io 2 

Function of the channel I/O 2: Selection of the 

function used in the channel I/O 2, according to the 

Table 2

Io 3 

Function of the channel I/O 2: Selection of the 

function used in the channel I/O 2, according to the 

Table 2

Io 4 

Function of the channel I/O 4: Selection of the 

function used in the channel I/O 4, according to the 

Table 2

Io 5 

Function of the channel I/O 5: Selection of the 

function used in the channel I/O 5, according to the 

Table 2.

 

CALIBRATION PARAMETERS LEVEL 
All types of input and output have been calibrated at the factory. 

If a recalibration is needed it must be performed by a qualified 

professional. If this level  is accidentally accessed, pass all 

parameters without making any changes in their values

.

 

pass 

Password - Input of the Access Password. 
This parameter is presented before the protected 

levels. See item 

Protection of Configuration

(al1b 

Calibration  -  Enables possibility of calibrating the 

controller. 

 

YES 

-  Calibrate the Controller 

 

NO  

- Do not Calibrate the Controller 

inL( 

Input Low Calibration - See section Maintenance / 

Input Calibration.  

Declaration of the range start calibration signal 

applied to the analog input. 

ink( 

Input High Calibration - See section Maintenance / 

Input Calibration.  

Declaration of the end-of-range calibration signal 

applied to the analog input. 

rsL( 

Declaration of the range start calibration signal 

applied to the remote SP input. 

rsk( 

Declaration of the end-of-range calibration signal 

applied to the remote SP input. 

0vL( 

Analog output calibration. Declaration of the lower 

value present in the analog output. 

0vk( 

Analog output calibration. Declaration of the higher 

value present in the analog output. 

rstr 

Restore  -  Restores the factory calibration for all 

inputs and outputs, disregarding modifications 

carried out by the user. 

(j 

Cold Junction -  Adjusts the of cold junction 

temperature value. 

Содержание N1200HC

Страница 1: ...asic version with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments each with the ability to be linked together for a total of 180 segments Password...

Страница 2: ...as the control setpoint Available for I O5 or I O3 and I O4 when available Closed remote SP Open uses main SP kprg Digital Input with Hold Program function Defines channel as Digital Input with the function of commanding the execution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts execution of the ...

Страница 3: ...n the controller is first energized The alarm will be enabled only after the occurrence of a non alarm condition followed by a new occurrence for the alarm The initial blocking is useful for instance when one of the alarms is configured as a minimum value alarm causing the activation of the alarm soon upon the process start up an occurrence that may be undesirable The initial blocking is disabled ...

Страница 4: ...ed The LDB is useful in system supervision and troubleshooting allowing early detection of problems in the actuator power source or load SAFE OUTPUT VALUE WITH SENSOR FAILURE A function that sets the control output 1 in a safe condition for the process when is identified an error in the input sensor When the controller identifies a failure in the sensor input it forces the value of MV1 applying th...

Страница 5: ...er cable length compensation use conductors of same gauge and length For 4 wires Pt100 leave one conductor disconnected at the controller For 2 wire Pt100 short circuit terminals 11 and 12 T C 0 50mV Pt100 Figure 3a Connection of T C 0 50mV Figure 3b Connection of three wire Pt100 4 20 mA The connections for current signals 4 20 mA must be carried out according to Figure 4a 4 20mA Figure 4a Curren...

Страница 6: ...ues are saved when the keys or are pressed after changing a parameter value The value of SP is saved upon pressing the key or every 25 seconds CONFIGURATION PARAMETERS OPERATION LEVEL PV AND SP INDICATION The upper display shows the current value of PV The lower display indicates the value of the control SP in automatic mode If PV exceeds the limits established or the input is open the upper displ...

Страница 7: ...unit of the input type If set a negative value the overlap shall be treated as dead band dead zone Lbd t Loop break detection time Time interval of the LBD function Maximum time interval for the response of PV to commands from the control output in minutes sfst SOFT START Time in seconds during which the controller limits the value of control output 1 progressively from 0 to 100 Starts when the co...

Страница 8: ...the MV Safe Output function is adopted If equal to 0 zero the function is disabled and the outputs turn off when a sensor failure occurs bavd Digital communication Baud Rate selection in kbps 1 2 2 4 4 8 9 6 19 2 38 4 57 6 and 115 2 prty Parity of the serial communication none Without parity Ewem Even parity 0dd Odd parity Addr Address Slave address selection Identifies the controller in the netwo...

Страница 9: ...last three digits of the serial number of the controller added to the number 9000 As an example for the equipment with serial number 07154321 the master password is 9 3 2 1 PROGRAMS OF RAMP AND SOAK This feature allows the creation of a behavior profile for the process Each profile is built by up to 9 segments and is named RAMPS AND SOAKS PROGRAM and is defined by setpoint values and time interval...

Страница 10: ...OFF an automatic tuning is immediately initiated by the controller if the controller is not in RUN YES the tuning will begin when it passes into this condition The accomplishment of this automatic tuning is essential for the correct operation of the auto adaptative tuning The methods of automatic tuning and auto adaptative tuning are appropriate for most of the industrial processes However there m...

Страница 11: ... improves the performance of the communication Terminal 18 CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION Two parameters must be configured for using the serial type bavd Communication speed prty Parity of the communication addr Communication address for the controller REDUCED REGISTERS TABLE FOR SERIAL COMMUNICATION COMMUNICATION PROTOCOL The MOSBUS RTU slave is implemented All configurable...

Страница 12: ...61326 1 1997 and EN 61326 1 A1 1998 SAFETY EN61010 1 1993 and EN61010 1 A2 1995 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 MM FRONT PANEL IP65 POLYCARBONATE UL94 V 2 CASE IP30 ABS PC UL94 V 0 STARTS UP OPERATION after 3 seconds connected to the power supply CERTIFICATIONS CE UL FILE E300526 IDENTIFICATION N1200HC ...