N1200HC Controller 

NOVUS AUTOMATION 

2/12 

FUNCTION OF I/O 

CODE 

TYPE OF I/O 

Without Function 

OFF 

Output 

Output of Alarm 1 

A1 

Output 

Output of Alarm 2 

A2 

Output 

Output of Alarm 3 

A3 

Output 

Output of Alarm 4 

A4 

Output 

LBD - 

Loop break detection

 

Lbd 

Output 

Control Output 

1

 (Relay or Digital Pulse) 

(TR1 

Output 

Control Output 

2

 (Relay or Digital Pulse) 

(TR2 

Output 

Automatic / Manual mode selection 

mAN 

Digital Input 

Run / Stop mode selection 

RVN 

Digital Input 

Remote SP selection 

RSP 

Digital Input 

Program freezes 

KPRG 

Digital Input 

Program 1 selection 

PR 1 

Digital Input 

Control output 

(0 to 20 mA) 

(.0.20 

Analogical Output 

Control output 

(4 to 20 mA) 

(.4.20 

Analogical Output 

Control output 

(0 to 20 mA) 

2.0.20 

Analogical Output 

Control output 

(4 to 20 mA) 

2.4.20 

Analogical Output 

Retransmission of PV in 0 to 20 mA 

P.0.20 

Analogical Output 

Retransmission of PV in 4 to 20 mA 

P.4.20 

Analogical Output 

Retransmission of SP 0 to 20 mA 

S.0.20 

Analogical Output 

Retransmission of SP 4 to 20 mA 

S.4.20 

Analogical Output 

Table 2

 - Types of functions for the I/O channels 

During the configuration of the I/O channels, only the valid options for 

each channel will  be shown on the display. These functions are 

described below: 

 

off

 - Without function 

The I/O channel programmed with code off will not be used by the 

controller. Although without function, this channel is available through 

the serial communication as digital I/O (command 5 MODBUS). 

 

a1

a2

a3

a4

 - Alarm Outputs 

Defines that the programmed I/O channel acts as alarm outputs. 

Available for all the I/O channels. 

 

Lbd

 – 

Loop break detector 

function. 

Assigns the output of the Loop Break Detector alarm to an I/O 

channel. Available to all I/O channels. 

 

(tr1

 - 

(tr2

 -

 

Control 

Defines the I/O channel to be used as the control output (relay or 

digital pulse). Available for all the I/O channels. The digital pulse is 

available on I/O5 or on I/O3 and I/O4 (when the DIO optional is 

installed). Check the specifications of each channel. 

 

mAn

 - Digital Input with Auto/Manual function 

Defines the I/O channel as Digital Input with the function of switching 

the control mode between 

Automatic and Manual

. Available on I/O5 

or on I/O3 and I/O4 (when the DIO optional is installed). 

Closed

 = Manual control 

Open

    = Automatic  

 

rvn

  - Digital Input with RUN function 

Defines channel as Digital Input with the function of 

enabling/disabling the control and alarm outputs (

RvN

YES

 / 

no

). 

Available for I/O5 or I/O3 and I/O4, when installed. 

Closed

 = outputs enabled 

Open

 = control and alarms output shut off  

 

rsp

 - Digital Input with Remote SP function 

Defines channel as Digital Input with the function of selecting the 

remote SP as the control setpoint. Available for I/O5 or I/O3 and 

I/O4, when available. 

Closed

 = remote SP 

Open

 = uses main SP 

 

kprg

 - Digital Input with Hold Program function 

Defines channel as Digital Input with the function of commanding the 

execution of the selected setpoint profile 

program

. Available for I/O5 

or I/O3 and I/O4, when available. 

Closed

 = Enables execution of the program 

Open

 = Interrupts execution of the program 

Note

:  Even  when the execution of the program is interrupted, the 

control output remains active and controlling the process at the point 

(Setpoint) of interruption. The program will resume its normal execution 

starting from this same point when the digital input is closed. 

 

Pr 1

 - Digital Input with function to Execute Program 1 

Defines the IO channel as Digital Input with the function of 

commanding the execution of the setpoing profile 

program 1

Available for I/O5 or I/O3 and I/O4, when available. 
Useful function for  switching between the main setpoint and a 

secondary one defined by the 

program 1

Closed

 = selects program 1; 

Open

 = selects main 

setpoint

 

 

(.0.20

 - 

(.4.20

 – 0-20 / 4-20 mA control output 1  

Set the channel to serve as control output 1, in analog mode. 

Available for I/O 5 only. 

 

2.0.20

 - 

2.4.20

 - 0-20 / 4-20 mA control output 2 

Set the channel to serve as control output 2 in analog mode. 

Available for I/O 5 only. 

 

P.0.20

 – 0-20 mA PV retransmission 

Set the channel to serve as Retransmission output of PV values. 

Available for I/O 5 only. 

 

P.4.20

 – 4-20 mA PV retransmission 

Set the channel to serve as Retransmission output of PV values. 

Available for I/O 5 only. 

 

s.0.20

 – 0-20 mA SP (Setpoint) retransmission 

Set the channel to serve as Retransmission output of SP values. 

Available for I/O 5 only. 

 

s.4.20

 – 4-20 mA SP (Setpoint) retransmission 

Set the channel to serve as Retransmission output of SP values. 

Available for I/O 5 only. 

CONFIGURATION OF ALARMS 

The controller has 4 independent alarms. These alarms can be 

configured to operate with nine different functions, as shown in 

Table 3

 

off

 – Alarms turned 

off

 

ierr

 – Open Sensor alarms – (

sensor break alarm

The open sensor alarm acts whenever the input sensor is broken or 

badly connected. 

 

rs

 – Program Event Alarm 

Configures the alarm to act in (a) specific segment(s) of the 

programs of ramps and baselines to be created by the user. 

 

lo

 – Alarm of Absolute Minimum Value 

Triggers when the value of measured PV is 

below

 the value defined 

for alarm Setpoint. 

 

ki

 – Alarm of Absolute Maximum Value 

Triggers when the value of measured PV is 

above

 the value defined 

for alarm Setpoint. 

 

dif

 – Alarm of Differential Value 

In this function the parameters 

SPA1

SPA2

SPA3

  and 

SPA4

 

represent the Deviation of PV in relation to the SP. 
Using the Alarm 1 as example: for Positive SPA1 values, the 

Differential alarm triggers when the value of PV is 

out

 of the range 

defined for: 

(SP – SPA1) to (SP + SPA1) 

Содержание N1200HC

Страница 1: ...asic version with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments each with the ability to be linked together for a total of 180 segments Password...

Страница 2: ...as the control setpoint Available for I O5 or I O3 and I O4 when available Closed remote SP Open uses main SP kprg Digital Input with Hold Program function Defines channel as Digital Input with the function of commanding the execution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts execution of the ...

Страница 3: ...n the controller is first energized The alarm will be enabled only after the occurrence of a non alarm condition followed by a new occurrence for the alarm The initial blocking is useful for instance when one of the alarms is configured as a minimum value alarm causing the activation of the alarm soon upon the process start up an occurrence that may be undesirable The initial blocking is disabled ...

Страница 4: ...ed The LDB is useful in system supervision and troubleshooting allowing early detection of problems in the actuator power source or load SAFE OUTPUT VALUE WITH SENSOR FAILURE A function that sets the control output 1 in a safe condition for the process when is identified an error in the input sensor When the controller identifies a failure in the sensor input it forces the value of MV1 applying th...

Страница 5: ...er cable length compensation use conductors of same gauge and length For 4 wires Pt100 leave one conductor disconnected at the controller For 2 wire Pt100 short circuit terminals 11 and 12 T C 0 50mV Pt100 Figure 3a Connection of T C 0 50mV Figure 3b Connection of three wire Pt100 4 20 mA The connections for current signals 4 20 mA must be carried out according to Figure 4a 4 20mA Figure 4a Curren...

Страница 6: ...ues are saved when the keys or are pressed after changing a parameter value The value of SP is saved upon pressing the key or every 25 seconds CONFIGURATION PARAMETERS OPERATION LEVEL PV AND SP INDICATION The upper display shows the current value of PV The lower display indicates the value of the control SP in automatic mode If PV exceeds the limits established or the input is open the upper displ...

Страница 7: ...unit of the input type If set a negative value the overlap shall be treated as dead band dead zone Lbd t Loop break detection time Time interval of the LBD function Maximum time interval for the response of PV to commands from the control output in minutes sfst SOFT START Time in seconds during which the controller limits the value of control output 1 progressively from 0 to 100 Starts when the co...

Страница 8: ...the MV Safe Output function is adopted If equal to 0 zero the function is disabled and the outputs turn off when a sensor failure occurs bavd Digital communication Baud Rate selection in kbps 1 2 2 4 4 8 9 6 19 2 38 4 57 6 and 115 2 prty Parity of the serial communication none Without parity Ewem Even parity 0dd Odd parity Addr Address Slave address selection Identifies the controller in the netwo...

Страница 9: ...last three digits of the serial number of the controller added to the number 9000 As an example for the equipment with serial number 07154321 the master password is 9 3 2 1 PROGRAMS OF RAMP AND SOAK This feature allows the creation of a behavior profile for the process Each profile is built by up to 9 segments and is named RAMPS AND SOAKS PROGRAM and is defined by setpoint values and time interval...

Страница 10: ...OFF an automatic tuning is immediately initiated by the controller if the controller is not in RUN YES the tuning will begin when it passes into this condition The accomplishment of this automatic tuning is essential for the correct operation of the auto adaptative tuning The methods of automatic tuning and auto adaptative tuning are appropriate for most of the industrial processes However there m...

Страница 11: ... improves the performance of the communication Terminal 18 CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION Two parameters must be configured for using the serial type bavd Communication speed prty Parity of the communication addr Communication address for the controller REDUCED REGISTERS TABLE FOR SERIAL COMMUNICATION COMMUNICATION PROTOCOL The MOSBUS RTU slave is implemented All configurable...

Страница 12: ...61326 1 1997 and EN 61326 1 A1 1998 SAFETY EN61010 1 1993 and EN61010 1 A2 1995 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 MM FRONT PANEL IP65 POLYCARBONATE UL94 V 2 CASE IP30 ABS PC UL94 V 0 STARTS UP OPERATION after 3 seconds connected to the power supply CERTIFICATIONS CE UL FILE E300526 IDENTIFICATION N1200HC ...

Отзывы: