Novus N1200HC Скачать руководство пользователя страница 4

N1200HC Controller 

NOVUS AUTOMATION 

4/12 

The proportional band 2 (Pb2) and the level time of PWM 2 (Ct2) are 

independent. Here you must set the minimum and maximum power 

for control 2. 

 

Control Output 

Process Variable 

Pb1 

Hst 2 

Output 1 

Output 2 

OFF 

ON 

Set Point 

 

RUN

 MODE 

The RUN parameter (

rvn

) operates as a master switch of the 

controller outputs channels. It enables either the channels set to 

control output as the defined as an alarm output. When this 

parameter is settled to

 

YES

, the control outputs and alarm are able to 

operate on and off in accordance to the determinations of the 

controller. When it is settled to 

NO

, all outputs remain off, regardless 

of the needs of the process. In this condition, the display of the 

controller shows a 

STOP

  message alternately with the measured 

temperature value (PV). 

ANALOG RETRANSMISSION OF PV AND SP 

The analog output  (available in I/O5), when not used for control 

purposes, is available for retransmitting the PV and SP values in 0-

20 or 4-20 mA. This analog output is electrically isolated from other 

inputs and outputs. The analog output signal is scalable, with the 

output range defined by the values programmed in the parameters 

rtLL

” and “

rtkL

”. 

To obtain a voltage output, the user must install a resistor shunt 

(550 

Ω 

max.) to the current output terminals (terminals 7 and 8). 

The actual resistor value depends on the desired output voltage span. 

SOFT-START 

The soft-start feature avoids abrupt variations in the power delivered 

to the load regardless of the system power demand. 
This is accomplished by defining a limiting ramp for the control 

output. The output is allowed to reach maximum value (100 %) only 

after the time programmed in the soft-start parameter has elapsed. 
The Soft-start function is generally used in processes that require slow 

start-up, where the instantaneous application of 100 % of the available 

power to the load may cause damages to parts of the system. 
In order to disable this function, the soft-start parameter must be 

configured with 0 (zero). 

REMOTE SETPOINT 

The controller can have its Setpoint value defined by an analog, 

remotely generated signal. This feature is enabled through the 

channels I/O3, I/O4 or I/O5 when configured as digital inputs and 

configured with the function 

rsp

 (Remote SP selection) or through 

the parameter 

E.rsp

. The remote setpoint input accepts the signals 

0-20 mA, 4-20 mA, 0-5 V and 0-10 V.  
For the signals of 0-20 and 4-20 mA, a shunt resistor of 100 

 is 

required between terminals 9 and 10, as shown in 

Figure 4c

LBD - LOOP BREAK DETECTION 

The parameter defines a time interval, in minutes, within which the 

PV is expect to react to a control output signal. If the PV does not 

react properly within the time interval configured in 

lbd.t

, the 

controller interprets this as a control loop break and  signals this 

occurrence in the display. 
A LBD event may be sent to any I/O channel. Simply configure the 

LDB

 function to the desired I/O channel: the selected output will be 

activated when a 

LDB

  condition is detected. When the 

lbd.t

 

parameter is programmed with 0 (zero), the 

LDB

 function is disabled. 

The 

LDB

 is useful in system supervision and troubleshooting, allowing 

early detection of problems in the actuator, power source or load. 

SAFE OUTPUT VALUE WITH SENSOR FAILURE 

A function that sets the 

control output 1

 in a safe condition for the 

process when is identified an error in the input sensor. 
When the controller identifies a failure in the sensor (input), it forces 

the value of MV1 applying the percentage set by the user in 

parameter 

1E.ov

If the 

1E.ov

 parameter is set to 0 (zero) this function will be disabled 

and the control output will be simply switched off when sensor failure 

occurs. 

USB INTERFACE 

The USB interface is used for CONFIGURING or MONITORING the 

controller. The 

NConfig

 software must be used for the configuration. 

It makes it possible to create, view, save and open configurations 

from the equipment or files in your computer. The tool for saving and 

opening configurations in files makes it possible to transfer 

configurations between pieces  of equipment and to make backup 

copies. For specific models, the 

NConfig

  software also makes it 

possible to update the firmware (internal software) of the controller 

through the USB. 
For MONITORING purposes you can use any supervisory software 

(SCADA) or laboratory software that supports the MODBUS RTU 

communication on a serial communications port. When connected to 

the USB of a computer, the controller is recognized as a conventional 

serial port (COM x). Use the 

NConfig

  software or consult the 

DEVICE MANAGER in the Windows CONTROL PANEL to identify 

the COM port that was assigned to the controller. Consult the 

mapping of the MODBUS memory in the controller’s communications 

manual and the documentation of your supervisory software to 

conduct the MONITORING process. 
Follow the procedure below to use the USB communication of the 

equipment: 

 

Download the 

NConfig

 software from our website and install it on 

your computer. The USB drivers necessary for operating the 

communication will be installed together with the software. 

 

Connect the USB cable between the equipment and the 

computer. The controller does not have to be connected to a 

power supply. The USB will provide enough power to operate the 

communication (other equipment functions cannot operate). 

 

Open the 

NConfig

  software, configure the communication and 

start recognition of the device.  

 

 

The USB interface IS NOT SEPARATE from the 

signal input (PV) or the controller digital inputs and 

outputs. It is intended for temporary use during 

CONFIGURATION and MONITORING periods. For 

the safety of people and equipment, it must only be 

used when the piece of equipment is completely 

disconnected from the input/output signals. Using 

the USB in any other type of connection is possible 

but requires a careful analysis by the person 

responsible for installing it. When MONITORING for 

long periods of time and with connected inputs and 

outputs, we recommend using the RS485 interface, 

which is available or optional in most of our products. 

INSTALLATION / CONNECTIONS 

The controller must be fastened on a panel, following the sequence 

of steps described below: 

 

Prepare a panel cut-out of 45.5 x 45.5 mm; 

 

Remove the mounting clamps from the controller; 

 

Insert the controller into the panel cut-out; 

 

Slide the mounting clamp from the rear to a firm grip at the panel. 

Содержание N1200HC

Страница 1: ...asic version with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments each with the ability to be linked together for a total of 180 segments Password...

Страница 2: ...as the control setpoint Available for I O5 or I O3 and I O4 when available Closed remote SP Open uses main SP kprg Digital Input with Hold Program function Defines channel as Digital Input with the function of commanding the execution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts execution of the ...

Страница 3: ...n the controller is first energized The alarm will be enabled only after the occurrence of a non alarm condition followed by a new occurrence for the alarm The initial blocking is useful for instance when one of the alarms is configured as a minimum value alarm causing the activation of the alarm soon upon the process start up an occurrence that may be undesirable The initial blocking is disabled ...

Страница 4: ...ed The LDB is useful in system supervision and troubleshooting allowing early detection of problems in the actuator power source or load SAFE OUTPUT VALUE WITH SENSOR FAILURE A function that sets the control output 1 in a safe condition for the process when is identified an error in the input sensor When the controller identifies a failure in the sensor input it forces the value of MV1 applying th...

Страница 5: ...er cable length compensation use conductors of same gauge and length For 4 wires Pt100 leave one conductor disconnected at the controller For 2 wire Pt100 short circuit terminals 11 and 12 T C 0 50mV Pt100 Figure 3a Connection of T C 0 50mV Figure 3b Connection of three wire Pt100 4 20 mA The connections for current signals 4 20 mA must be carried out according to Figure 4a 4 20mA Figure 4a Curren...

Страница 6: ...ues are saved when the keys or are pressed after changing a parameter value The value of SP is saved upon pressing the key or every 25 seconds CONFIGURATION PARAMETERS OPERATION LEVEL PV AND SP INDICATION The upper display shows the current value of PV The lower display indicates the value of the control SP in automatic mode If PV exceeds the limits established or the input is open the upper displ...

Страница 7: ...unit of the input type If set a negative value the overlap shall be treated as dead band dead zone Lbd t Loop break detection time Time interval of the LBD function Maximum time interval for the response of PV to commands from the control output in minutes sfst SOFT START Time in seconds during which the controller limits the value of control output 1 progressively from 0 to 100 Starts when the co...

Страница 8: ...the MV Safe Output function is adopted If equal to 0 zero the function is disabled and the outputs turn off when a sensor failure occurs bavd Digital communication Baud Rate selection in kbps 1 2 2 4 4 8 9 6 19 2 38 4 57 6 and 115 2 prty Parity of the serial communication none Without parity Ewem Even parity 0dd Odd parity Addr Address Slave address selection Identifies the controller in the netwo...

Страница 9: ...last three digits of the serial number of the controller added to the number 9000 As an example for the equipment with serial number 07154321 the master password is 9 3 2 1 PROGRAMS OF RAMP AND SOAK This feature allows the creation of a behavior profile for the process Each profile is built by up to 9 segments and is named RAMPS AND SOAKS PROGRAM and is defined by setpoint values and time interval...

Страница 10: ...OFF an automatic tuning is immediately initiated by the controller if the controller is not in RUN YES the tuning will begin when it passes into this condition The accomplishment of this automatic tuning is essential for the correct operation of the auto adaptative tuning The methods of automatic tuning and auto adaptative tuning are appropriate for most of the industrial processes However there m...

Страница 11: ... improves the performance of the communication Terminal 18 CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION Two parameters must be configured for using the serial type bavd Communication speed prty Parity of the communication addr Communication address for the controller REDUCED REGISTERS TABLE FOR SERIAL COMMUNICATION COMMUNICATION PROTOCOL The MOSBUS RTU slave is implemented All configurable...

Страница 12: ...61326 1 1997 and EN 61326 1 A1 1998 SAFETY EN61010 1 1993 and EN61010 1 A2 1995 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 MM FRONT PANEL IP65 POLYCARBONATE UL94 V 2 CASE IP30 ABS PC UL94 V 0 STARTS UP OPERATION after 3 seconds connected to the power supply CERTIFICATIONS CE UL FILE E300526 IDENTIFICATION N1200HC ...

Отзывы: