N1200HC Controller 

NOVUS AUTOMATION 

3/12 

For a negative SPA1 value, the Differential alarm triggers when the 

value of PV is 

within

 the range defined above. 

 

difl

 – Alarm of Minimum Differential Value 

It triggers when the value of PV is 

below

 the defined point by: 

(SP – SPA1) 

Using the Alarm 1 as example.

 

 

difk

 – Alarm of Maximum Differential Value 

Triggers when the value of PV is above the defined point by: 

(SP + SPA1) 

Using the Alarm 1 as example. 

SCREEN 

TYPE 

ACTUATION 

Off 

Inoperative 

Output is not used as alarm. 

Ierr 

Open sensor  

(

i

nput 

Err

or) 

Activated when the input signal of PV is 

interrupted, out of the range limits or Pt100 

in short-circuit. 

Rs 

Event (

r

amp and 

S

oak) 

Activated in a specific segment of program. 

Lo 

Minimum value 

(

Lo

w) 

 

SPAn 

PV 

 

Ki 

Maximum value 

(

Hi

gh) 

 

SPAn 

PV 

 

Dif 

Differential 

(

diF

erential) 

 

SP 

PV 

SP + SPAn 

 

SP - SPAn 

 

 

 

SP 

PV 

SP - SPAn 

 

SP + SPAn 

 

 

Positive SPAn  

Negative SPAn      

Difl 

Minimum 

Differential 

(

diF

erential 

L

ow) 

Positive SPAn             Negative SPAn 

 

SP 

PV 

SP - SPAn 

     

 

SP 

PV 

SP - SPAn 

 

Difk 

Maximum 

differential 

(

diF

erential 

H

igh) 

 

SP 

PV 

SP + SPAn 

 

 

SP 

PV 

SP + SPAn 

 

Positive SPAn      

Negative SPAn      

Table 3

 – Alarm functions 

Where SPAn refers to Setpoints of Alarm 

SPA1

SPA2

SPA3

 and 

SPA4

ALARM TIMER MODES 

The controller alarms can be configured to perform 3 timer modes: 

 

One pulse with defined duration; 

 

Delayed  activation; 

 

Repetitive pulses. 

The illustrations in 

Table 4

 show the behavior of the alarm output for 

various combinations of times 

t1

 and 

t2

. The timer functions can be 

configured in parameters 

A1t1

A1t2

A2t1

A2t2

A3t1

A3t2

A4t1

 and 

A4t2

OPERATION 

t 1 

t 2 

ACTION 

Normal 

Operation 

 

Alarm Event 

Alarm 

Output 

 

Activation for a 

defined time  1 to 6500 s 

Alarm Event

Alarm

Output

T1

 

Activation with 

delay 

1 to 6500 s 

Alarm Event

Alarm

Output

T2

 

Intermittent 

Activation  1 to 6500 s 1 to 6500 s 

Alarm Event

Alarm

Output

T1

T2

T1

 

Table 4

 - Temporization Functions for the Alarms 

The leds associated with the alarm light up when an alarm condition 

exists regardless of the status of the alarm output. 

INITIAL BLOCKING OF ALARM 

The 

initial blocking

 option inhibits the alarm from being recognized 

if an alarm condition is present when the controller is first energized. 

The alarm will be enabled only after the occurrence of a non-alarm 

condition followed by a new occurrence for the alarm. 
The initial blocking is useful, for instance, when one of the alarms is 

configured as a minimum value alarm, causing the activation of the 

alarm soon upon the process start-up, an occurrence that may be 

undesirable. 
The initial blocking is disabled for the sensor break alarm function. 

CONTROL MODE 

The controller can operate in two different manners: Automatic mode 

or Manual mode. In automatic mode the controller defines the 

amount of power to be applied on the process, based on defined 

parameters (SP, PID, etc.).  In the manual mode the user himself 

defines this amount of power. The parameter 

(trl

  defines the 

control mode to be adopted. 

PID AUTOMATIC MODE 

For the Automatic mode, there are two different strategies of control: 

PID control and ON/OFF control. 
The PID control, available only for the 

Control 1

, has its action 

based on a control algorithm that works on the basis of the deviation 

of PV relative to SP, based on 

Pb

Ir

 and 

Dt

 setting parameters. 

The Control 2 has only Proportional (

Pb

) action. 

On the other hand, the ON/OFF control (obtained when Pb=0) 

operates with 0 % or 100 % of power, when PV deviates from SP. 
The determination of the PID parameters (

Pb

Ir

  and 

Dt

) is 

described in the item DETERMINATION OF PID PARAMETERS of 

this manual. 

CONTROL 2 

A second independent control output (control output 2) may be used. 

This output, with only proportional action is  typically used in the 

cooling process where the heating is controlled by the control output 

1. 
In case the application requires simultaneous heating and cooling, 

you must configure the 

Act

 = 

re

 and adjust the parameters (

OLAP

overlap to define the type of operation. 
There are three cases: 

OLAP

 

> 0; when there are overlapping activities of power between 

heating and cooling. 

 

Control Output 

Process Variable 

Overlap 

Pb1 

Pb2 

Output 1 

Output 2 

Set Point 

 

OLAP

 < 0; when there is a dead zone of power actuation between 

heating and cooling. 

 

Control Output 

Process Variable 

Dead Zone 

Pb1 

Pb2 

Output 1 

Output 2 

Set Point 

 

OLAP 

= 0; When there is no overlap or dead zone. At the point 

where the PV reaches the SP there is no actuation of any output. 

 

Control Output 

Process Variable 

Pb1 

Pb2 

Output 1 

Output 2 

Set Point 

 

Содержание N1200HC

Страница 1: ...asic version with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments each with the ability to be linked together for a total of 180 segments Password...

Страница 2: ...as the control setpoint Available for I O5 or I O3 and I O4 when available Closed remote SP Open uses main SP kprg Digital Input with Hold Program function Defines channel as Digital Input with the function of commanding the execution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts execution of the ...

Страница 3: ...n the controller is first energized The alarm will be enabled only after the occurrence of a non alarm condition followed by a new occurrence for the alarm The initial blocking is useful for instance when one of the alarms is configured as a minimum value alarm causing the activation of the alarm soon upon the process start up an occurrence that may be undesirable The initial blocking is disabled ...

Страница 4: ...ed The LDB is useful in system supervision and troubleshooting allowing early detection of problems in the actuator power source or load SAFE OUTPUT VALUE WITH SENSOR FAILURE A function that sets the control output 1 in a safe condition for the process when is identified an error in the input sensor When the controller identifies a failure in the sensor input it forces the value of MV1 applying th...

Страница 5: ...er cable length compensation use conductors of same gauge and length For 4 wires Pt100 leave one conductor disconnected at the controller For 2 wire Pt100 short circuit terminals 11 and 12 T C 0 50mV Pt100 Figure 3a Connection of T C 0 50mV Figure 3b Connection of three wire Pt100 4 20 mA The connections for current signals 4 20 mA must be carried out according to Figure 4a 4 20mA Figure 4a Curren...

Страница 6: ...ues are saved when the keys or are pressed after changing a parameter value The value of SP is saved upon pressing the key or every 25 seconds CONFIGURATION PARAMETERS OPERATION LEVEL PV AND SP INDICATION The upper display shows the current value of PV The lower display indicates the value of the control SP in automatic mode If PV exceeds the limits established or the input is open the upper displ...

Страница 7: ...unit of the input type If set a negative value the overlap shall be treated as dead band dead zone Lbd t Loop break detection time Time interval of the LBD function Maximum time interval for the response of PV to commands from the control output in minutes sfst SOFT START Time in seconds during which the controller limits the value of control output 1 progressively from 0 to 100 Starts when the co...

Страница 8: ...the MV Safe Output function is adopted If equal to 0 zero the function is disabled and the outputs turn off when a sensor failure occurs bavd Digital communication Baud Rate selection in kbps 1 2 2 4 4 8 9 6 19 2 38 4 57 6 and 115 2 prty Parity of the serial communication none Without parity Ewem Even parity 0dd Odd parity Addr Address Slave address selection Identifies the controller in the netwo...

Страница 9: ...last three digits of the serial number of the controller added to the number 9000 As an example for the equipment with serial number 07154321 the master password is 9 3 2 1 PROGRAMS OF RAMP AND SOAK This feature allows the creation of a behavior profile for the process Each profile is built by up to 9 segments and is named RAMPS AND SOAKS PROGRAM and is defined by setpoint values and time interval...

Страница 10: ...OFF an automatic tuning is immediately initiated by the controller if the controller is not in RUN YES the tuning will begin when it passes into this condition The accomplishment of this automatic tuning is essential for the correct operation of the auto adaptative tuning The methods of automatic tuning and auto adaptative tuning are appropriate for most of the industrial processes However there m...

Страница 11: ... improves the performance of the communication Terminal 18 CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION Two parameters must be configured for using the serial type bavd Communication speed prty Parity of the communication addr Communication address for the controller REDUCED REGISTERS TABLE FOR SERIAL COMMUNICATION COMMUNICATION PROTOCOL The MOSBUS RTU slave is implemented All configurable...

Страница 12: ...61326 1 1997 and EN 61326 1 A1 1998 SAFETY EN61010 1 1993 and EN61010 1 A2 1995 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 MM FRONT PANEL IP65 POLYCARBONATE UL94 V 2 CASE IP30 ABS PC UL94 V 0 STARTS UP OPERATION after 3 seconds connected to the power supply CERTIFICATIONS CE UL FILE E300526 IDENTIFICATION N1200HC ...

Отзывы: