N1200HC Controller 

PROCESS CONTROLLER – INSTRUCTIONS MANUAL – V2.0x C 

SAFETY ALERTS 

The symbols below are used on the equipment and throughout this 

document to draw the user’s attention to important operational and 

safety information. 

 

 

CAUTION: 

Read the manual thoroughly 

before installing and operating the 

equipment. 

CAUTION OR DANGER:  

Electrical Shock Hazard 

All safety related instructions that appear in the manual must be 

observed to ensure personal safety and to prevent damage to either 

the instrument or the system. If the instrument is used in a manner not 

specified by the manufacturer, the protection provided by the 

equipment may be impaired. 

INTRODUCTION 

The N1200HC is an extraordinarily versatile process controller.  It 

accepts in a single model virtually all the sensors and signals used in 

the industry and provides the main output types required for the 

operation of diverse processes. 
The configuration can be performed directly on the controller or through 

the USB interface. The 

NConfig

  software (free) is the configuration 

management tool. Connected to the USB of a Windows computer, the 

controller is recognized as a serial communications port (COM) running 

with a Modbus RTU protocol. 
Through the USB interface, even if disconnected from the power 

supply, the configuration performed in a piece of equipment can be can 

be saved in a file and repeated in other pieces of equipment that 

require the same configuration.  
It is important that the users read carefully this manual before using the 

controller. Verify if the release of this manual matches the instrument 

version (the firmware version is shown when the controller is 

energized). The N1200HC main characteristics are: 

 

Multi-sensor universal input, with no hardware change; 

 

Protection for open sensor in any condition; 

 

Two separate control outputs: heating and cooling; 

 

Self-tuning of PID parameters; 

 

Automatic / Manual function with “bumpless”  transfer; 

 

Three alarm outputs in the basic version, with functions of 

minimum, maximum, differential (deviation), open sensor and 

event; 

 

Timer functions that can be associated to the alarms; 

 

Retransmission of PV or SP in 0-20 mA or 4-20 mA; 

 

Input for remote setpoint; 

 

Digital input with 5 functions; 

 

Programmable soft-start;

 

 

20 setpoint profile programs with 9 segments each, with the ability 

to be linked together for a total of 180 segments; 

 

Password for parameters protection; 

 

Universal power supply. 

CONFIGURATION / FEATURES 

INPUT TYPE SELECTION 

The type of input to be used by the controller is defined in the device 

configuration. 

Table 1

 shows all available options. 

TYPE 

CODE 

RANGE OF MEASUREMENT 

Tc j 

Range: -110 to 950 ºC (-166 to 1742 ºF) 

Tc k 

Range: -150 to 1370 ºC (-238 to 2498 ºF) 

Tc t 

Range: -160 to 400 ºC (-256 to 752 ºF) 

Tc n 

Range: -270 to 1300 ºC (-454 to 2372 ºF) 

Tc r 

Range: -50 to 1760 ºC (-58 to 3200 ºF) 

Tc s 

Range: -50 to 1760 ºC (-58 to 3200 ºF) 

Tc b 

Range: 400 to 1800 ºC (752 to 3272 ºF) 

Tc e 

Range:-90 to 730 ºC (-130 to 1346 ºF) 

Pt100 

Pt 

Range: -200 to 850 ºC (-328 to 1562 ºF) 

0-20 mA 

L0.20 

Linear Signals  

Programmable indication from -1999 to 9999. 

4-20 mA 

L4.20 

0–50 mV 

L0.50 

0-5 Vdc 

L0.5 

0-10 Vdc 

L0.10 

4-20 mA 

NON 

LINEAR 

ln j 

Non Linear Analog Signals  

Indication range depends on the selected sensor. 

Ln k 

ln t 

ln n 

ln r 

ln s 

ln b 

ln E 

Ln.Pt 

Table 1

 - Input types 

Note

: All input types are factory calibrated. 

CONFIGURATION OF OUTPUTS, ALARMS AND DIGITAL INPUTS 

The controller input and output channels (I/O) can assume multiple 

functions: control output 1 or 2, digital input, digital output, alarm 

output, retransmission of PV and SP. These channels are identified 

as 

I/O 1

I/O 2

I/O 3

I/O 4

 and 

I/O 5

The basic controller model comes loaded with the following features: 
  I/O 1-  output to Relay SPST-NA; 

  I/O 2-  output to Relay SPST-NA; 

I/O 5-  current output, digital output, digital input; 

Optionally, other features can be added, as shown under the item 

Identification

 in this manual: 

3R

:  I/O3 with output to SPDT relay; 

DIO

:  I/O3 and I/O4 as digital input and output channels; 

485

:  Serial Communication; 

The function to be used in each channel of I/O is defined by the user 

in accordance with the options shown in the 

Table 2

Содержание N1200HC

Страница 1: ...asic version with functions of minimum maximum differential deviation open sensor and event Timer functions that can be associated to the alarms Retransmission of PV or SP in 0 20 mA or 4 20 mA Input for remote setpoint Digital input with 5 functions Programmable soft start 20 setpoint profile programs with 9 segments each with the ability to be linked together for a total of 180 segments Password...

Страница 2: ...as the control setpoint Available for I O5 or I O3 and I O4 when available Closed remote SP Open uses main SP kprg Digital Input with Hold Program function Defines channel as Digital Input with the function of commanding the execution of the selected setpoint profile program Available for I O5 or I O3 and I O4 when available Closed Enables execution of the program Open Interrupts execution of the ...

Страница 3: ...n the controller is first energized The alarm will be enabled only after the occurrence of a non alarm condition followed by a new occurrence for the alarm The initial blocking is useful for instance when one of the alarms is configured as a minimum value alarm causing the activation of the alarm soon upon the process start up an occurrence that may be undesirable The initial blocking is disabled ...

Страница 4: ...ed The LDB is useful in system supervision and troubleshooting allowing early detection of problems in the actuator power source or load SAFE OUTPUT VALUE WITH SENSOR FAILURE A function that sets the control output 1 in a safe condition for the process when is identified an error in the input sensor When the controller identifies a failure in the sensor input it forces the value of MV1 applying th...

Страница 5: ...er cable length compensation use conductors of same gauge and length For 4 wires Pt100 leave one conductor disconnected at the controller For 2 wire Pt100 short circuit terminals 11 and 12 T C 0 50mV Pt100 Figure 3a Connection of T C 0 50mV Figure 3b Connection of three wire Pt100 4 20 mA The connections for current signals 4 20 mA must be carried out according to Figure 4a 4 20mA Figure 4a Curren...

Страница 6: ...ues are saved when the keys or are pressed after changing a parameter value The value of SP is saved upon pressing the key or every 25 seconds CONFIGURATION PARAMETERS OPERATION LEVEL PV AND SP INDICATION The upper display shows the current value of PV The lower display indicates the value of the control SP in automatic mode If PV exceeds the limits established or the input is open the upper displ...

Страница 7: ...unit of the input type If set a negative value the overlap shall be treated as dead band dead zone Lbd t Loop break detection time Time interval of the LBD function Maximum time interval for the response of PV to commands from the control output in minutes sfst SOFT START Time in seconds during which the controller limits the value of control output 1 progressively from 0 to 100 Starts when the co...

Страница 8: ...the MV Safe Output function is adopted If equal to 0 zero the function is disabled and the outputs turn off when a sensor failure occurs bavd Digital communication Baud Rate selection in kbps 1 2 2 4 4 8 9 6 19 2 38 4 57 6 and 115 2 prty Parity of the serial communication none Without parity Ewem Even parity 0dd Odd parity Addr Address Slave address selection Identifies the controller in the netwo...

Страница 9: ...last three digits of the serial number of the controller added to the number 9000 As an example for the equipment with serial number 07154321 the master password is 9 3 2 1 PROGRAMS OF RAMP AND SOAK This feature allows the creation of a behavior profile for the process Each profile is built by up to 9 segments and is named RAMPS AND SOAKS PROGRAM and is defined by setpoint values and time interval...

Страница 10: ...OFF an automatic tuning is immediately initiated by the controller if the controller is not in RUN YES the tuning will begin when it passes into this condition The accomplishment of this automatic tuning is essential for the correct operation of the auto adaptative tuning The methods of automatic tuning and auto adaptative tuning are appropriate for most of the industrial processes However there m...

Страница 11: ... improves the performance of the communication Terminal 18 CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION Two parameters must be configured for using the serial type bavd Communication speed prty Parity of the communication addr Communication address for the controller REDUCED REGISTERS TABLE FOR SERIAL COMMUNICATION COMMUNICATION PROTOCOL The MOSBUS RTU slave is implemented All configurable...

Страница 12: ...61326 1 1997 and EN 61326 1 A1 1998 SAFETY EN61010 1 1993 and EN61010 1 A2 1995 USB INTERFACE 2 0 CDC class virtual communications port MODBUS RTU protocol SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6 3 MM FRONT PANEL IP65 POLYCARBONATE UL94 V 2 CASE IP30 ABS PC UL94 V 0 STARTS UP OPERATION after 3 seconds connected to the power supply CERTIFICATIONS CE UL FILE E300526 IDENTIFICATION N1200HC ...

Отзывы: