Pearl™ Fire Alarm Control 
Panel Operating Manual

Содержание Fire Alarm Control Panel

Страница 1: ...997 670 000 2 Pearl Fire Alarm Control Panel Operating Manual...

Страница 2: ...1 Status Normal 3 1 3 2 Panel Controls and Menus 3 1 4 Enabling User Access Level 2 4 1 4 1 Passcode Entry 4 1 4 2 Keyswitch Entry 4 1 5 Navigating the Panel Menus 5 1 5 1 Disable Enable Menu 5 2 5 1...

Страница 3: ...Contents ii 997 670 000 2 Contents www notifierknowledge com Operating Manual 5 5 Commissioning Menus 5 19...

Страница 4: ...ontrol panel hereafter referred to as the panel is provided with all required indicators to allow the user to review the system status and with appropriate user keyholder access perform approved syste...

Страница 5: ...E PROTECTIONACTIVE FIRE PROTECTION FAULT DISABLED FIRE OUTPUT ACTIVE FIRE OUTPUT FAULT DISABLED POWER TECHNICAL ALARM DAY MODE See Section 1 2 3 LED Status Indicators Internal Buzzer This audible devi...

Страница 6: ...ed event In the event that more than one event has been detected some of the control keys keyholder access only can be used to scroll down the list of all current events to review those hidden from vi...

Страница 7: ...s illuminate Fault LED indications for individual zones are not provided Note The LCD backlight is turned off and pushbutton backlights are dimmed with the loss of the primary power i e mains supply...

Страница 8: ...y can be selected for example the EXTEND DELAY function during the first stage of an active two stage delay period 2 Menu Navigation option Selection Functions Keys With the panel at user access Level...

Страница 9: ...ULT Yellow A fault condition exists DISABLE Yellow One or more devices are disabled TEST Yellow A test condition has been entered PRE ALARM Yellow A pre alarm condition exists SYSTEM FAULT Yellow The...

Страница 10: ...n was configured during system commissioning Use the information provided by the LCD and the LEDs to understand quickly what action needs to be taken To assist this process the panel s LCD indicates t...

Страница 11: ...of sounders etc the detection of a fire may indicate a zone fire condition but without the FIRE LED being lit This indicates that a fire condition has been detected but the panel is waiting for anothe...

Страница 12: ...on that needs to be taken To assist this process the panel s LCD indicates the nature of the fault if it is a faulty detection device the zone location and the device s responsible for raising the fau...

Страница 13: ...n a clockwise direction or enter a valid user access Level 2 passcode and then press the RESET key The LCD will re display the Status Normal screen and all alarm or other event related indicators will...

Страница 14: ...on logo is displayed POWER LED green This is lit continuously when the panel is powered No other front panel LEDs are lit and the internal buzzer is silent 3 2 Panel Controls and Menus No control func...

Страница 15: ...e appropriate access passcode and press the key again to enter A correct passcode entry displays the main user level menu Main Menu Press the key to abandon an invalidated passcode entry attempt and r...

Страница 16: ...ghlighted With the Main Menu all the listed options are available and the first is highlighted Working Example Set Change the Date Time With the Main Menu displayed on the LCD press the numeric key 3...

Страница 17: ...anual Override if configured during commissioning 5 1 1 Zones and Devices Select option 1 Zones and Devices to disable enable a zone or select devices to disable individually Only configured zones are...

Страница 18: ...zone output devices such as sounders cannot be disabled individually 2 Todisable enabletheentirezone defaultselection pressthe key Each press of the key toggles the state of the zone disabled or enabl...

Страница 19: ...ic key 1 to select the Disable Enable option Press the 1 key on the numeric keypad to select Zones and Devices The list of all configured zones is displayed the first zone in the list is highlighted U...

Страница 20: ...e enable disable state is changed With the fault relay output in a disabled state the DISABLE LED is lit The DISABLE tab is displayed with disabled fault relay output Press the key to bring the DISABL...

Страница 21: ...enable disable state changes toggled Press the key at any time to exit 5 1 4 Delays to Outputs This option is only available when delays have been configured as part of one or more Cause Effect rules...

Страница 22: ...e DAY MODE LED is lit However if it has been overridden using this menu option the DAY MODE LED extinguishes until the next configured day mode period occurs or the Time of Day program if still active...

Страница 23: ...f the LCD see Section 5 2 5 LCD Test the internal buzzer see Section 5 2 6 Internal Buzzer 5 2 1 Zones To perform a zone walk test select option 1 Zones from the Test Menu press the 1 key on the alpha...

Страница 24: ...zones to be tested To view the status of the devices in any other zones in test use the navigation buttons to move from one zone to another OR 5 2 1 2 To Cancel a Zone Walk Test A zone walk test can o...

Страница 25: ...prompted for a node ID number even if the devices that require testing are connected to the current panel 2 Press the navigation buttons to highlight the first device in the list and then press the ke...

Страница 26: ...the Fire LED and working down first and then across to the last LEDs on the right The POWER LED is not tested as this will already be lit continously under normal conditions 2 The SHOW MORE ZONES IN F...

Страница 27: ...on button inverts the on or off state of the pixels This means that pixels previously not turned on are now turned on and the pixels that were turned on are now turned off This pixel state inversion h...

Страница 28: ...2 6 Internal Buzzer Select option 6 Buzzer from the Test Menu to test the panel s internal buzzer Press the 6 key on the alphanumeric keypad or if highlighted press the key When selected the buzzer is...

Страница 29: ...ock format As a number is entered the cursor moves one place to the right automatically However if an incorrect number was entered use the C key to clear the entry and enter it again When the time has...

Страница 30: ...imum of 50 000 can be logged and each event is time and date stamped With the View Status Menu screen displayed press the key to select option 1 Historic Log If it is not highlighted press the 1 key o...

Страница 31: ...option and press the key The user is then prompted through a number of steps to specifiy the loop number device type sensor or module and the loop address of the device If a device has been configure...

Страница 32: ...and select the correct address Should the data of another device need to be displayed when for example it is located on a different loop or it is of a different type such as a module or sensor then Us...

Страница 33: ...mory for later retrieval by the service engineer This menu option allows the alarm event total to be displayed on the LCD Using the numeric keypad press 3 to select option 3 Alarm Count Alternatively...

Страница 34: ...owledge com 997 670 000 2 Navigating the Panel Menus Operating Manual 5 5 Commissioning Menus Access to the commissioning menus requires the entry of an access Level 3 passcode These functions are not...