Fire and Fault Events - What to do
Operating Manual
1
4
7
2
5
8
0
3
6
9
c
ABC
DEF
GHI
JKL
TUV
WXYZ
MNO
PQRS
2.3 RESET Key
The RESET key is used to clear all fire and fault status indications
on the panel and return it to its normal condition.
Note:
The RESET key must not be used to clear fire or fault
indications without the appropriate actions having been taken
to investigate and remedy the cause of any such events.
The RESET key can only clear fire or fault event indications when
they have been satisfactorily removed from the system.
To perform a reset action, either insert the key and turn through 90° in
a clockwise direction or enter a valid user access Level 2 passcode
and then press the RESET key. The LCD will re-display the Status
Normal screen and all alarm or other event-related indicators will
be extinguished.
After pressing the RESET key any conditions still present in the
system will, once again, cause the panel to display and indicate the
existence of such events until they have been satisfactorily remedied.
The POWER LED does not extinguish.
MUTE BUZZER
EXTEND DELAY
END DELAY
RESET
DISABLE FIRE OUTPUT
DISABLE ALARMS
DISABLE FIRE PROTECTION
SILENCE ALARMS
SOUND ALARMS
RESET key
KEYSWITCH
(to enable user access Level 2)
Non-
quiescent
Condition
Remove the access Level 2 entry key or, if a passcode was used,
press the key until the Status Normal screen appears. When the
Status Normal screen re-appears, the panel has been returned to
access Level 1.