Type of Circuit

Devices/Ratings

Circuit Ratings

Connections

Notification Appliance

Circuit

CMX Control Module fed from an MPS-24A,
MPS-24B, AVPS-24, or other 24 VDC
power supplies listed for Fire Protective
Signaling.  WARNING:  See list of AVPS-24
compatible devices in the Device
Compatibility Document, 15378.

Operating voltage supplied dependent on
the signal power source employed.
ELR=47K, 1/2 watt, Part #47K (N-ELR) in
Canada. NFPA Style Y or Style Z field
wiring. Max Load is 2 amps Resistive @ 24
VDC. Most Notification Appliances are
resistive. Certain electromechanical
devices exhibit inductive loading
characteristics. For these types of devices,
derate the outputs to 1 amp @ 30 VDC
(0.6pf). Size wiring for no more than 1.2
volt drop at last device on circuit.
Supervised. Power limiting is a function of
the power source.

NFPA Style Y Activated Polarity CMX
Terminal 6 (+), 7 (-)
NFPA Style Z Activated Polarity CMX
Terminals 6, 9 (+); 7, 8 (-)

A circuit or path directly

connected to a

notification appliance.

XP Transponder XPC-8 module fed from an
MPS-24A, MPS-24B, AVPS-24, or other
24VDC listed power supply.
WARNING:  See list of AVPS-24
compatible devices.

Operating voltage supplied dependent on
the power source employed.  ELR = 47K,
1/2 watt, Part # R-47K (N-ELR in Canada).
NFPA Style Y or Style Z  field wiring. Max
Load is 2 amps Resistive @ 24 VDC. Most
Notification Appliances are resistive.
Certain electromechanical devices exhibit
inductive loading characteristics. For these
types of devices, derate the outputs to 1
amp @ 30 VDC (0.6pf). Size wiring for no
more than a 1.2-volt drop at last device on
circuit.  Supervised.  Power limiting is a
function of the signaling power source.

NFPA Style Y Activated Polarity (8 zones
on XPC-8 P2): Term.1 (+), 2 (-); 3 (+), 4
(-); 5 (+), 6 (-); 7 (+), 8 (-); 9 (+), 10 (-); 11
(+), 12 (-);  13 (+), 14 (-); 15 (+), 16 (-).

NFPA Style Z Activated Polarity (4 zones
on XPC-8 P2): Term. 1 ,3 (+), 2 ,4 (-);
5,7 (+), 6,8 (-); 9,11 (+), 10,12 (-); 13,15
(+), 14,16 (-).

Speaker

Circuits

CMX-1 Control Module fed from an AA-30
or AA-120.

Operating voltage dependent on amplifier
employed.  Max of 40 mA total speaker
leakage current due to coupling capacitors.
48 watts max @ 25 VRMS max.  ELR=
47K, 1/2 watt, Part # A2143-20 (N-ELR in
Canada). Max line resistance dependent
upon wattage required at each speaker.
NFPA Style Y  field wiring. Supervised.
Power-limiting is a function of the signaling
power source.

NFPA Style Y supervised polarity: CMX
Terminals 7 (+), 6 (-)

CMX-2 Control Module fed from an AA-30
or AA-120. Model A2143-20 coupling
capacitor (10uA leakage max.) is required
for NFPA Style Z connection. Refer to the
CMX-2 Installation Instructions  for more
details.

Operating voltage dependent on amplifier
employed. 43.75 watts max., up to 70.7
VRMS. Max of 40 uA total speaker leakage
current due to coupling capacitors.
ELR=47K, 1/2 watt, Part # A2143-00
(N-ELR in Canada). Max. line resistance
dependent upon wattage required at each
speaker. NFPA Style Y or Z field wiring.
Supervised. Power-limiting is a function of
the signaling power source.

NFPA Style Y supervised polarity: CMX
Terminals 7 (+), 6 (-).

NFPA Style Z supervised polarity: CMX
Terminals 7,8 (+); 6,9 (-).

XP Transponder XPC-8 module fed from an
AA-30 or AA-120.

Operating voltage dependent on amplifier
employed. 48 watts max @ 70.7 Vrms
max.  ELR=47K,   1/2 watt, Part # R-47K
(N-ELR in Canada). Max line resistance
dependent upon wattage required at each
speaker.  NFPA Style Y or Style Z  field
wiring. Supervised. Power-limiting is a
function of the signal source.

NFPA Style Y supervised polarity (8
zones on XPC-8 P2):Term.1 (-), 2 (+); 3
(-), 4 (+); 5 (-), 6 (+); 7 (-), 8 (+); 9 (-), 10
(+); 11 (-), 12 (+);  13 (-), 14 (+); 15 (-), 16
(+).
NFPA Style Z supervised polarity (4
zones on XPC-8 P2):Term. 1 ,3 (-), 2 ,4
(+);  5,7 (-), 6,8 (+); 9,11 (-), 10,12
(+);13,15 (-), 14,16 (+).

Speaker Power

(High-level Audio)

AA-30 or AA-120 Audio Amplifier feeding
signal to a CMX Control Module or an XP
Transponder XPC-8 Module. Use only
UL-listed speakers rated for a minimum 25
VRMS (30 watts max with AA-30, 120 watts
max with AA-120) or 70.7 VRMS min when
using the AA-120 with T-70 option. (100
watts max)

25 Vrms audio amplifier output (70.7 Vrms
for AA-120 with T-70 option).  AA-30:  30
watts max.  AA-120:  120 watts max.
AA-120 with T-70 option:  100 watts max.
Frequency response:  800 Hz to 2800 Hz.
Two wire high level audio circuit is not
supervised. Four-wire high level audio
circuit is supervised (except when T-70 is
used). AA-30, AA-120 and T-70 are
power-limited. Maximum wiring distance
limited by wattage required at each
speaker.

AA-30 and AA-120 Connector P6 to
XPC-8 Connector P3.  AA-30 Connector
P6 {or P8.5 (-) and P8.6 (+)} to CMX
Term. 3 (-) and 4 (+).  Wire optional
supervisory return loop from CMX Term 3
(-) and 4 (+) to AA-30 Connector P7 or
P8.2(-), P8.3 (+) or AA-120 P8.2 (-), P8.3
(+). AA-120 with T-70 option: connect 25
VRMS output P7.3 and P7.4 to
transformer input P7.1 and P7.2 to obtain
70.7 VRMS output at P8.7 and P8.8.
Connection not supervised.

www.PDF-Zoo.com

Содержание AM2020/AFP1010

Страница 1: ...AM2020 AFP1010 with SIB NET C P N 15094 C ECN 95 210 Document 15094 11 20 95 Rev www PDF Zoo com...

Страница 2: ...rol with remote notification capability can provide early warn ing of a developing fire Such a system however does not assure protection against property damage or loss of life resulting from a fire A...

Страница 3: ...6 Figure 1 2 Mounting the ICA 4L and System Boards 7 Figure 1 3 Connecting Two ICA 4Ls using Expansion Power Cable 75142 8 Section 1 3 Mounting the Serial Interface Board 9 Figure 1 4 SIB NET Termina...

Страница 4: ...at the AM2020 AFP1010 The SIB NET replaces the SIB 2048 in existing systems which connect to NOTI FIRE NET The SIB NET supports all features of the SIB 2048 including ACS annunciators printers and CR...

Страница 5: ...nstructions 15337 The Notifier Device Compatibility Document 15378 Analog Fire Panel AFP 200 15511 Canadian Requirements for the AM2020 AFP1010 15631 The NIB 96 Network Interface Board 15666 The NR45...

Страница 6: ...ion consult the factory This software is not compatible with earlier versions of CGAS AMNET AUTOPLEXOR and VGAS UNINET systems Software in these items must be upgraded for compatibility Section 1 2 Mo...

Страница 7: ...8 has 16 positions which will connect properly with the ICA 4L If the newer cable 75378 is used with the older ICA 4 chassis there will be an extra 16th socket position on the cable This empty cable s...

Страница 8: ...cing the cabinet door see Figure 1 3 15 positions for old cable part number 71030 to the ICA 4 15 positions for old cable part number 71020 to the ICA 4L with extra pin see Figure 1 2 16 positions for...

Страница 9: ...AM2020 AFP1010 system connects to and interfaces to the network through the MIB and the SIB NET The MIB mounts onto the SIB NET The chassis is compatible with the ICA 4 For more information on the ICA...

Страница 10: ...onitor EIA 232 Reference CTS from AUX Monitor Figure 1 4 SIB NET Terminal Designations Terminals 1 4 Provide wiring for one PRN printer to this unsupervised circuit Terminals 5 8 Provide connection to...

Страница 11: ...is provided through an EIA 232 interface on the Serial Interface Board SIB Assemble a custom cable for connection to the EIA port on the CRT Connect additional CRTs with installer provided cables AUX...

Страница 12: ...e the first in a chain and must be in the same room as the AM2020 AFP1010 The CRT 2 can be located remotely Figure 1 5 CRT to SIB Connections NOTES 1 Outputs are power limited for device circuit ratin...

Страница 13: ...r feed paper Installation Remote printers require 120 VAC 50 60Hz primary power A secondary power source battery backup is not provided Recommendation Use a separate Un interruptable Power Supply UPS...

Страница 14: ...from Printer nc Twisted pair Twisted pair Keltron Printer Model No VS4095 5 Refer to note 4 below Figure 1 7 Keltron Printer Connections NOTES 1 Outputs are power limited and are not supervised 2 Make...

Страница 15: ...mitations NOTE If the SIB NET is not the first device on the EIA 485 circuit set SW1 on the SIB NET to the out position The EIA 485 Reference P5 1 for the SIB NET must be connected to any ACS device w...

Страница 16: ...Device Circuit 12 18 AWG Maximum loop wire resistance is 20 ohms MMX 1 MMX 101 or 100 ohms XPM 8 5 000 4 000 2 438 1 613 Belden 9586 12 AWG West Penn 999 Belden 9581 14 AWG West Penn 995 Belden 9575...

Страница 17: ...are not power limited TB2 Term 1 Term 2 MPS 24B Main Power Supply 2 9 amps max draw in alarm 25 0 amp max screw terminal contact rating Supervised Battery leads are not power limited TB2 Term 5 Term 6...

Страница 18: ...ng is a function of the signaling power source NFPA Style Y supervised polarity CMX Terminals 7 6 CMX 2 Control Module fed from an AA 30 or AA 120 Model A2143 20 coupling capacitor 10uA leakage max is...

Страница 19: ...2 13 14 15 16 Four wire circuits 4 telephone circuits on XPC 8 P2 Term 1 3 2 4 5 7 6 8 9 11 10 12 13 15 14 16 XPC to Telephone Jacks Low Level Audio Riser AA 30 AA 100 AA 120 ATG 2 ACT 1 fed from an A...

Страница 20: ...5 3 of the AM2020 AFP1010 Manual For SIB NET see Section 1 5 of this manual Initiating Device Circuit MMX 1 Monitor Module Employs contact type devices only manual pull stations heat detectors supervi...

Страница 21: ...necticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or...

Отзывы: