Document 15094     Rev C     11/20/95 15094:C

Page 12

nc

nc

Twisted-pair

Twisted-pair

Twisted-pair

Twisted-pair

To EIA Port

of next CRT

CRT 

CRT without keyboard

Up to 24 max in chain. Allow 50 feet
maximum (typical) between CRTs.

To EIA Port of CRT

with keyboard

T

o AUX Port of

CRT

SIB-NET

50 feet (typical)

Wiring distance limited by cable
capacitance.  Refer to the EIA-
232E standard.

9

EIA-232 Reference

10

Transmit to CRT

11

EIA-232 Reference

12

Receive from CRT

     SIB-NET (Connector P3)

CRT with Keyboard
One maximum – the CRT-1 must be the first in a chain
and must be in the same room as the AM2020/AFP1010.
The CRT-2 can be located remotely.

Figure 1-5: CRT to SIB Connections

NOTES:
1)

Outputs are power limited (for device/circuit ratings, refer to Appendix A).

2)

Make connections with overall foil/braided-shield twisted-pair cable.

3)

Apply power to the CRTs before start-up of the system beginning with the last CRT in the chain.

4)

A total of 25 CRTs can be installed.  Only one keyboard (shipped with each CRT) can be used in the entire
system and installed on the first CRT in a chain.  For all applications, use the keyboard to program the
FACP.  When finished programming the system, remove the keyboard or keep the keyboard in a locked
enclosure.

www.PDF-Zoo.com

Содержание AM2020/AFP1010

Страница 1: ...AM2020 AFP1010 with SIB NET C P N 15094 C ECN 95 210 Document 15094 11 20 95 Rev www PDF Zoo com...

Страница 2: ...rol with remote notification capability can provide early warn ing of a developing fire Such a system however does not assure protection against property damage or loss of life resulting from a fire A...

Страница 3: ...6 Figure 1 2 Mounting the ICA 4L and System Boards 7 Figure 1 3 Connecting Two ICA 4Ls using Expansion Power Cable 75142 8 Section 1 3 Mounting the Serial Interface Board 9 Figure 1 4 SIB NET Termina...

Страница 4: ...at the AM2020 AFP1010 The SIB NET replaces the SIB 2048 in existing systems which connect to NOTI FIRE NET The SIB NET supports all features of the SIB 2048 including ACS annunciators printers and CR...

Страница 5: ...nstructions 15337 The Notifier Device Compatibility Document 15378 Analog Fire Panel AFP 200 15511 Canadian Requirements for the AM2020 AFP1010 15631 The NIB 96 Network Interface Board 15666 The NR45...

Страница 6: ...ion consult the factory This software is not compatible with earlier versions of CGAS AMNET AUTOPLEXOR and VGAS UNINET systems Software in these items must be upgraded for compatibility Section 1 2 Mo...

Страница 7: ...8 has 16 positions which will connect properly with the ICA 4L If the newer cable 75378 is used with the older ICA 4 chassis there will be an extra 16th socket position on the cable This empty cable s...

Страница 8: ...cing the cabinet door see Figure 1 3 15 positions for old cable part number 71030 to the ICA 4 15 positions for old cable part number 71020 to the ICA 4L with extra pin see Figure 1 2 16 positions for...

Страница 9: ...AM2020 AFP1010 system connects to and interfaces to the network through the MIB and the SIB NET The MIB mounts onto the SIB NET The chassis is compatible with the ICA 4 For more information on the ICA...

Страница 10: ...onitor EIA 232 Reference CTS from AUX Monitor Figure 1 4 SIB NET Terminal Designations Terminals 1 4 Provide wiring for one PRN printer to this unsupervised circuit Terminals 5 8 Provide connection to...

Страница 11: ...is provided through an EIA 232 interface on the Serial Interface Board SIB Assemble a custom cable for connection to the EIA port on the CRT Connect additional CRTs with installer provided cables AUX...

Страница 12: ...e the first in a chain and must be in the same room as the AM2020 AFP1010 The CRT 2 can be located remotely Figure 1 5 CRT to SIB Connections NOTES 1 Outputs are power limited for device circuit ratin...

Страница 13: ...r feed paper Installation Remote printers require 120 VAC 50 60Hz primary power A secondary power source battery backup is not provided Recommendation Use a separate Un interruptable Power Supply UPS...

Страница 14: ...from Printer nc Twisted pair Twisted pair Keltron Printer Model No VS4095 5 Refer to note 4 below Figure 1 7 Keltron Printer Connections NOTES 1 Outputs are power limited and are not supervised 2 Make...

Страница 15: ...mitations NOTE If the SIB NET is not the first device on the EIA 485 circuit set SW1 on the SIB NET to the out position The EIA 485 Reference P5 1 for the SIB NET must be connected to any ACS device w...

Страница 16: ...Device Circuit 12 18 AWG Maximum loop wire resistance is 20 ohms MMX 1 MMX 101 or 100 ohms XPM 8 5 000 4 000 2 438 1 613 Belden 9586 12 AWG West Penn 999 Belden 9581 14 AWG West Penn 995 Belden 9575...

Страница 17: ...are not power limited TB2 Term 1 Term 2 MPS 24B Main Power Supply 2 9 amps max draw in alarm 25 0 amp max screw terminal contact rating Supervised Battery leads are not power limited TB2 Term 5 Term 6...

Страница 18: ...ng is a function of the signaling power source NFPA Style Y supervised polarity CMX Terminals 7 6 CMX 2 Control Module fed from an AA 30 or AA 120 Model A2143 20 coupling capacitor 10uA leakage max is...

Страница 19: ...2 13 14 15 16 Four wire circuits 4 telephone circuits on XPC 8 P2 Term 1 3 2 4 5 7 6 8 9 11 10 12 13 15 14 16 XPC to Telephone Jacks Low Level Audio Riser AA 30 AA 100 AA 120 ATG 2 ACT 1 fed from an A...

Страница 20: ...5 3 of the AM2020 AFP1010 Manual For SIB NET see Section 1 5 of this manual Initiating Device Circuit MMX 1 Monitor Module Employs contact type devices only manual pull stations heat detectors supervi...

Страница 21: ...necticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or...

Отзывы: