Document 15094 Rev C 11/20/95 15094:C
Page 12
nc
nc
Twisted-pair
Twisted-pair
Twisted-pair
Twisted-pair
To EIA Port
of next CRT
CRT
CRT without keyboard
Up to 24 max in chain. Allow 50 feet
maximum (typical) between CRTs.
To EIA Port of CRT
with keyboard
T
o AUX Port of
CRT
SIB-NET
50 feet (typical)
Wiring distance limited by cable
capacitance. Refer to the EIA-
232E standard.
9
EIA-232 Reference
10
Transmit to CRT
11
EIA-232 Reference
12
Receive from CRT
SIB-NET (Connector P3)
CRT with Keyboard
One maximum – the CRT-1 must be the first in a chain
and must be in the same room as the AM2020/AFP1010.
The CRT-2 can be located remotely.
Figure 1-5: CRT to SIB Connections
NOTES:
1)
Outputs are power limited (for device/circuit ratings, refer to Appendix A).
2)
Make connections with overall foil/braided-shield twisted-pair cable.
3)
Apply power to the CRTs before start-up of the system beginning with the last CRT in the chain.
4)
A total of 25 CRTs can be installed. Only one keyboard (shipped with each CRT) can be used in the entire
system and installed on the first CRT in a chain. For all applications, use the keyboard to program the
FACP. When finished programming the system, remove the keyboard or keep the keyboard in a locked
enclosure.