background image

Document 15094     Rev C     11/20/95 15094:C

Page 20

Type of Circuit

Devices/Ratings

Circuit Ratings

Connections

SLC Loop

LIB-200 Board: Employs intelligent
detectors and addressable modules -
SDX-551, SDX-551TH, FDX-551,
CPX-551, MMX-1, MMX-2, MMX-101,
CMX-1, BGX-10L, XPP-1, ISO-X.Ten
SLC Loops max per AM2020 system,
two per AFP1010.

24 Volts DC nominal, 27.6 volts DC max.
Maximum length is 10,000 ft. per channel (NFPA
Style 4) or 10,000 ft. total twisted pair length
(NFPA Style 6 and 7).  Maximum loop current is
200mA (short circuit) or 100 mA (normal).
Maximum loop resistance is 40 ohms.
Supervised and power-limited.

NFPA Style 4:  LIB-200
Channel A - Term. 1 (+) 3 (-);
Channel B - Term. 5 (+), 7 (-).
NFPA Style 6, 7: LIB-200
Terminals 1, 5 (+); 3,7 (-).

A circuit or path directly over

which multiple signals are

transmitted and received.

EIA-485 Interface

and EIA-232 Interface

SIB-2048/NET Serial Interface Board:
Employs AMG-1 Audio Message
Generator and annunciator modules -
ACM-16AT (AEM-16AT), ACM-32A
(AEM-32A).

+/- 5 volts peak-to-peak. Supervised and
power-limited.  6000 ft. max distance.
Terminating resistor = 120 ohms, 1/4-watt (Part
# 71244).  Characteristic impedance of the
wiring is 120 ohms.Transmission rate = 20.833
Kbps

SIB-2048/NET  P5, Terminal 5 (+) and 6
(-) to  AMG-1 Connector P3, Terminal 6
(+) and 4 (-).   SIB-2048 P5, Terminal 5
(+) and 6 (-) to ACM-16AT or ACM-32A
Connector TB2, Terminal 3,4 (-) and
1,2 (+).

SIB-2048/NET and SIB-232 Serial
Interface Boards: Employs CRT-1 with
Keyboard and CRT-1 without keyboard.

+/- 12 volts peak-to-peak.  Supervised and
power-limited.  Max distance limited by
capacitance of wire (refer to EIA-232E
Standard).  Transmission rate of 2400 bps.

For SIB-2048 and SIB-232, see Chapter
One, Figures 5-2 and 5-3 of the
AM2020/AFP1010 Manual.  For
SIB-NET see Section 1.5 of this manual.

SIB-2048/NET and SIB-232 Serial
Interface Boards: Employs PRN-3 and
Keltron P-40 printers.

+/- 12 volts peak-to-peak.  Power-limited but not
supervised.  Max distance limited by
capacitance of wire (refer to EIA-232E
Standard). Transmission rate of 2400 bps.

For SIB-2048 and SIB-232, see Chapter
One, Figures 5-2 and 5-3 of the
AM2020/AFP1010 Manual.  For
SIB-NET see Section 1.5 of this manual.

SIB-2048/NET and SIB-232 Serial
Interface Boards: Employs UL EDP
listed equipment (display monitors and
printers).

+/- 12 volts peak-to-peak.  Power-limited but not
supervised.  Max distance limited by
capacitance of wire (refer to EIA-232E
Standard). Transmission rate of 2400 bps

For SIB-2048 and SIB-232, see Chapter
One, Figure 5-2 and 5-3 of the
AM2020/AFP1010 Manual.  For
SIB-NET see Section 1.5 of this manual.

Initiating Device Circuit

MMX-1 Monitor Module: Employs
contact-type devices only - manual pull
stations, heat detectors, supervisory or
waterflow switches, and 4-wire smoke
detectors.

ELR = 47K, 1/2, Part # A2143-20 (N-ELR in
Canada).  NFPA Style B or Style D  field wiring.
20 ohms max loop resistance.  Supervised and
power-limited (210 uA).

NFPA Style B: MMX-1 Terminals 7 (+),
6 (-) NFPA Style D: MMX-1 Terminals
7,8 (+), 6,9 (-)

MMX-101 Monitor Module: Employs
contact-type devices only - manual pull
stations, heat detectors, supervisory or
waterflow switches, and 4-wire smoke
detectors.

ELR = 47K, 1/2, Part # A2143-20 (N-ELR in
Canada).  NFPA Style B or Style D  field wiring.
20 ohms max loop resistance.  Supervised and
power-limited (210 uA).

NFPA Style B: MMX-101 Red Wire (+),
White Wire (-)

A circuit to which automatic or

manual signal-initiating devices

are connected where the signal

received does not identify the

individual device being

operated.

XP Transponder XPM-8 module:
Employs 2-wire smoke detectors and
contact-type devices  - manual pull
stations, heat detectors, supervisory or
waterflow switches, and 4-wire smoke
detectors.

24 VDC (nominal), 200mV ripple.  ELR = 2.2K,
1/2 watt, Part #R-2.2K (N-ELR in Canada).
NFPA Style B or Style D field wiring. 100 ohms
max loop resistance. Supervised and
power-limited (50 uA).  See Notifier Device
Compatibility Document, 15378, for a list of
compatible 2-wire detectors.

NFPA Style B (8 zones on XPM-8 P2):

 NFPA Style D (4 zones on XPM-8 P2):.

XP Transponder XPM-8L module:
Employs dry-contact type devices only -
manual pull stations, heat detectors,
supervisory or waterflow switches, and
4-wire smoke detectors.

24 VDC. ELR=10K, 1/2 watt, Part # R-10K
(N-ELR in Canada). NFPA Style B field wiring.
1000 ohms max loop resistance. Supervised
and power-limited.

NFPA Style B (8 zones on XPM-8L P2)

MMX-2 Monitor Module:  Maximum of
40 MMX-2 modules per LIB-200.
Employs dry-contact type devices only -
manual pull stations, heat detectors,
supervisory or waterflow switches, and
4-wire smoke detectors.

24VDC Input 12-18 AWG.  See Document
M500-03-00 for limits.  Supervised.  Power
limiting is a function of the 24 VDC source.

MMX-2 Terminal 3(-) and 4(+)

NFPA Style B or D Initiating Device Circuit
12-18 AWG 25 ohms max (including 24VDC
input wiring above). Supervised and power
limited (90mA). 3.9K, 1/2 W end-of-line resistor
required at terminals 8 and 9 for NFPA Style D
operation. See Document M500-03-00 for
additional limits. See Notifier Device
Compatibility Document for a list of compatible
2-wire detectors.

NFPA Style B MMX-2 Terminal 6(-) and
7(+)
NFPA Style D MMX-2 Terminals 6,9(-)
and 7, 8(+)

www.PDF-Zoo.com

Содержание AM2020/AFP1010

Страница 1: ...AM2020 AFP1010 with SIB NET C P N 15094 C ECN 95 210 Document 15094 11 20 95 Rev www PDF Zoo com...

Страница 2: ...rol with remote notification capability can provide early warn ing of a developing fire Such a system however does not assure protection against property damage or loss of life resulting from a fire A...

Страница 3: ...6 Figure 1 2 Mounting the ICA 4L and System Boards 7 Figure 1 3 Connecting Two ICA 4Ls using Expansion Power Cable 75142 8 Section 1 3 Mounting the Serial Interface Board 9 Figure 1 4 SIB NET Termina...

Страница 4: ...at the AM2020 AFP1010 The SIB NET replaces the SIB 2048 in existing systems which connect to NOTI FIRE NET The SIB NET supports all features of the SIB 2048 including ACS annunciators printers and CR...

Страница 5: ...nstructions 15337 The Notifier Device Compatibility Document 15378 Analog Fire Panel AFP 200 15511 Canadian Requirements for the AM2020 AFP1010 15631 The NIB 96 Network Interface Board 15666 The NR45...

Страница 6: ...ion consult the factory This software is not compatible with earlier versions of CGAS AMNET AUTOPLEXOR and VGAS UNINET systems Software in these items must be upgraded for compatibility Section 1 2 Mo...

Страница 7: ...8 has 16 positions which will connect properly with the ICA 4L If the newer cable 75378 is used with the older ICA 4 chassis there will be an extra 16th socket position on the cable This empty cable s...

Страница 8: ...cing the cabinet door see Figure 1 3 15 positions for old cable part number 71030 to the ICA 4 15 positions for old cable part number 71020 to the ICA 4L with extra pin see Figure 1 2 16 positions for...

Страница 9: ...AM2020 AFP1010 system connects to and interfaces to the network through the MIB and the SIB NET The MIB mounts onto the SIB NET The chassis is compatible with the ICA 4 For more information on the ICA...

Страница 10: ...onitor EIA 232 Reference CTS from AUX Monitor Figure 1 4 SIB NET Terminal Designations Terminals 1 4 Provide wiring for one PRN printer to this unsupervised circuit Terminals 5 8 Provide connection to...

Страница 11: ...is provided through an EIA 232 interface on the Serial Interface Board SIB Assemble a custom cable for connection to the EIA port on the CRT Connect additional CRTs with installer provided cables AUX...

Страница 12: ...e the first in a chain and must be in the same room as the AM2020 AFP1010 The CRT 2 can be located remotely Figure 1 5 CRT to SIB Connections NOTES 1 Outputs are power limited for device circuit ratin...

Страница 13: ...r feed paper Installation Remote printers require 120 VAC 50 60Hz primary power A secondary power source battery backup is not provided Recommendation Use a separate Un interruptable Power Supply UPS...

Страница 14: ...from Printer nc Twisted pair Twisted pair Keltron Printer Model No VS4095 5 Refer to note 4 below Figure 1 7 Keltron Printer Connections NOTES 1 Outputs are power limited and are not supervised 2 Make...

Страница 15: ...mitations NOTE If the SIB NET is not the first device on the EIA 485 circuit set SW1 on the SIB NET to the out position The EIA 485 Reference P5 1 for the SIB NET must be connected to any ACS device w...

Страница 16: ...Device Circuit 12 18 AWG Maximum loop wire resistance is 20 ohms MMX 1 MMX 101 or 100 ohms XPM 8 5 000 4 000 2 438 1 613 Belden 9586 12 AWG West Penn 999 Belden 9581 14 AWG West Penn 995 Belden 9575...

Страница 17: ...are not power limited TB2 Term 1 Term 2 MPS 24B Main Power Supply 2 9 amps max draw in alarm 25 0 amp max screw terminal contact rating Supervised Battery leads are not power limited TB2 Term 5 Term 6...

Страница 18: ...ng is a function of the signaling power source NFPA Style Y supervised polarity CMX Terminals 7 6 CMX 2 Control Module fed from an AA 30 or AA 120 Model A2143 20 coupling capacitor 10uA leakage max is...

Страница 19: ...2 13 14 15 16 Four wire circuits 4 telephone circuits on XPC 8 P2 Term 1 3 2 4 5 7 6 8 9 11 10 12 13 15 14 16 XPC to Telephone Jacks Low Level Audio Riser AA 30 AA 100 AA 120 ATG 2 ACT 1 fed from an A...

Страница 20: ...5 3 of the AM2020 AFP1010 Manual For SIB NET see Section 1 5 of this manual Initiating Device Circuit MMX 1 Monitor Module Employs contact type devices only manual pull stations heat detectors supervi...

Страница 21: ...necticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or...

Отзывы: