Type of Circuit

Devices/Ratings

Circuit Ratings

Connections

Main Supply Circuit

A dedicated branch of the AC

service that supplies primary AC

power to the Fire Alarm Control

Panel.

MPS-24A Main Power Supply

120 VAC, 50/60 Hz, 1.8 amps

TB1: Term. 2 + 3 (Ground)

Term 4 + 5 (Neutral)

Term 6 + 7 (Hot)

MPS-24B Main Power Supply

120 VAC, 50/60 Hz, 1.8 amps

TB1: Term. 2 (Ground)

Term 3 (Neutral)

Term 4 (Hot)

AVPS-24 Audio/Visual Power Supply

120 VAC, 50/60 Hz, 1.0 amps

TB1: Term. 1 + 6 (Ground)

Term 4 (Neutral)

Term 5 (Hot)

AA-30 Audio Amplifier

120 VAC, 50/60 Hz, 1.0 amps

Plug P2: Term. 1 + 8 (Ground)

Term 3 + 4 (Neutral)

Term 5 + 6 (Hot)

AA-120 Audio Amplifier

120 VAC, 50/60 Hz, 1.85 amps

Plug P2: Term. 1 + 8 (Ground)

Term 5 + 6 (Neutral)

Term3 +4 (Hot)

Battery Charger Circuit

Charges and maintains the

secondary supply during non-fire

alarm conditions.

MPS-24A Main Power Supply and two

PS-12250 (12 volt, 25 AH) batteries.

27.6 VDC. Float type battery charger 2.0A

Max.  Supervised and power-limited.

TB2: Term. 1 (+), Term 2 (-)

MPS-24B Main Power Supply

27.6 VDC. Float type battery charger (750 mA

max). Supervised and power-limited.

TB2: Term. 5 (+), Term 6 (-)

NR45-24 Remote battery charger with

two LA-55 (12 volt, 55 AH) batteries.

120 VAC, 50/60 Hz, 1.0 amps

Term. 1 (Hot), Term 2 (Neutral),

Chassis ground.

27.6 VDC. Float type battery charger (2.0

amps max). Supervised and power-limited.

Term. 3 (+), Term 4 (-)

Battery Discharge Circuit

or

Secondary Power Input

Supplies power to the Fire Alarm

Control Panel during loss of

primary AC power.

AA-30 Audio Amplifier

3.0 amps max. draw in alarm. 25.0 amp max.

screw terminal contact rating. Supervised.

Battery leads are not power-limited.

Plug P1: Term. 1 (+), Term 4 (-)

AA-120 Audio Amplifier

7.3 amps max. draw in alarm. 25.0 amp max.

screw terminal contact rating. Supervised.

Battery leads are not power-limited.

Plug P1: Term. 3 + 4 (+),

Term 1 + 2 (-)

AVPS-24 Audio Visual Power Supply

3.0 amps max. draw in alarm. 25.0 amp max.

screw terminal contact rating. Supervised.

Battery leads are not power-limited.

TB1: Term. 2 (+), Term 3 (-)

MPS-24A Main Power Supply

6.0 amps max. draw in alarm. 25.0 amp max.

screw terminal contact rating. Supervised.

Battery leads are not power-limited.

TB2: Term. 1 (+), Term 2 (-)

MPS-24B Main Power Supply

2.9 amps max. draw in alarm. 25.0 amp max.

screw terminal contact rating. Supervised.

Battery leads are not power-limited.

TB2: Term. 5 (+), Term 6 (-)

Notification Appliance Power

Provides power for Notification

Appliance Circuits and remote

signaling devices.

MPS-24A Main Power Supply: use

with any UL listed 24 VDC fire alarm

Notification Appliance.

20.4 - 26.4 VDC (3.0 amps max.)

Power-limited and supervised.

TB3: Term. 3 (+), Term 4 (-)

MPS-24B Main Power Supply: use

with any UL listed 24 VDC fire alarm

Notification Appliances.

20.4 - 26.4 VDC (2.0 amps max. of regulated
current available in alarm only) Power-limited

and supervised with a UL listed relay.

TB2: Term. 3 (+), Term 4 (-)

AVPS-24 Audio/Visual Power Supply:

WARNING see list of compatible

devices in the Device Compatiblity

Document.

20.4 - 32.0 VRMS (3.0 amps max.) Full-wave,

unfiltered.  Power-limited and supervised with

an A77-716 relay.

TB2: Term. 1 (+), Term 2 (-)

External Resettable Power

MPS-24A Main Power Supply

20.4 - 26.4 VDC (200 mV ripple). 1.0 amps

max. (draws from the total of 3.0 amps of

MPS-24A regulated current available in

standby or 6.0 amps available in alarm).

Power-limited and supervised with an

A77-716 relay.

TB3: Term. 1 (+), Term 2 (-)

20.4 - 26.4 VDC (200 mV ripple). 2.0 amps

max. (draws from the total of 3.0 amps of

MPS-24A regulated current available in

standby or 6.0 amps available in alarm).

Power-limited and supervised with an
A77-716 relay. Note: Optional jumper

selectable.

TB3: Term. 3 (+), Term 4 (-)

MPS-24B Main Power Supply

20.4 - 26.4 VDC (200 mV ripple). 200 mA

max. (draws from the total of 750 mA of

regulated current available in standby and

alarm. Power-limited and supervised with a

UL listed relay.

TB2: Term. 1 (+), Term 2 (-)

Municipal Box Circuit

CMX Control Module with an MBT-1

Municipal Box Trip device and an
A77-716 power supervision relay.

Local Energy Municipal Box connection.

Supervised and power-limited. (3.65 VDC

nominal). (10 ohms max. loop resistance. Trip

current = 250 mA.

Refer to Supervising an

Uninterruptable Power Supply in the

AM2020/AFP1010 Manual.

XP Transponder XPC-8 module with

an MBT-1 Municipal Box Trip device.

Local Energy Municipal Box connection.

Supervised and power-limited. (3.65 VDC

nominal). (10 ohms max. loop resistance. Trip

current = 250 mA.

Refer to Appendix A of the XP Series

Transponder Manual.

www.PDF-Zoo.com

Содержание AM2020/AFP1010

Страница 1: ...AM2020 AFP1010 with SIB NET C P N 15094 C ECN 95 210 Document 15094 11 20 95 Rev www PDF Zoo com...

Страница 2: ...rol with remote notification capability can provide early warn ing of a developing fire Such a system however does not assure protection against property damage or loss of life resulting from a fire A...

Страница 3: ...6 Figure 1 2 Mounting the ICA 4L and System Boards 7 Figure 1 3 Connecting Two ICA 4Ls using Expansion Power Cable 75142 8 Section 1 3 Mounting the Serial Interface Board 9 Figure 1 4 SIB NET Termina...

Страница 4: ...at the AM2020 AFP1010 The SIB NET replaces the SIB 2048 in existing systems which connect to NOTI FIRE NET The SIB NET supports all features of the SIB 2048 including ACS annunciators printers and CR...

Страница 5: ...nstructions 15337 The Notifier Device Compatibility Document 15378 Analog Fire Panel AFP 200 15511 Canadian Requirements for the AM2020 AFP1010 15631 The NIB 96 Network Interface Board 15666 The NR45...

Страница 6: ...ion consult the factory This software is not compatible with earlier versions of CGAS AMNET AUTOPLEXOR and VGAS UNINET systems Software in these items must be upgraded for compatibility Section 1 2 Mo...

Страница 7: ...8 has 16 positions which will connect properly with the ICA 4L If the newer cable 75378 is used with the older ICA 4 chassis there will be an extra 16th socket position on the cable This empty cable s...

Страница 8: ...cing the cabinet door see Figure 1 3 15 positions for old cable part number 71030 to the ICA 4 15 positions for old cable part number 71020 to the ICA 4L with extra pin see Figure 1 2 16 positions for...

Страница 9: ...AM2020 AFP1010 system connects to and interfaces to the network through the MIB and the SIB NET The MIB mounts onto the SIB NET The chassis is compatible with the ICA 4 For more information on the ICA...

Страница 10: ...onitor EIA 232 Reference CTS from AUX Monitor Figure 1 4 SIB NET Terminal Designations Terminals 1 4 Provide wiring for one PRN printer to this unsupervised circuit Terminals 5 8 Provide connection to...

Страница 11: ...is provided through an EIA 232 interface on the Serial Interface Board SIB Assemble a custom cable for connection to the EIA port on the CRT Connect additional CRTs with installer provided cables AUX...

Страница 12: ...e the first in a chain and must be in the same room as the AM2020 AFP1010 The CRT 2 can be located remotely Figure 1 5 CRT to SIB Connections NOTES 1 Outputs are power limited for device circuit ratin...

Страница 13: ...r feed paper Installation Remote printers require 120 VAC 50 60Hz primary power A secondary power source battery backup is not provided Recommendation Use a separate Un interruptable Power Supply UPS...

Страница 14: ...from Printer nc Twisted pair Twisted pair Keltron Printer Model No VS4095 5 Refer to note 4 below Figure 1 7 Keltron Printer Connections NOTES 1 Outputs are power limited and are not supervised 2 Make...

Страница 15: ...mitations NOTE If the SIB NET is not the first device on the EIA 485 circuit set SW1 on the SIB NET to the out position The EIA 485 Reference P5 1 for the SIB NET must be connected to any ACS device w...

Страница 16: ...Device Circuit 12 18 AWG Maximum loop wire resistance is 20 ohms MMX 1 MMX 101 or 100 ohms XPM 8 5 000 4 000 2 438 1 613 Belden 9586 12 AWG West Penn 999 Belden 9581 14 AWG West Penn 995 Belden 9575...

Страница 17: ...are not power limited TB2 Term 1 Term 2 MPS 24B Main Power Supply 2 9 amps max draw in alarm 25 0 amp max screw terminal contact rating Supervised Battery leads are not power limited TB2 Term 5 Term 6...

Страница 18: ...ng is a function of the signaling power source NFPA Style Y supervised polarity CMX Terminals 7 6 CMX 2 Control Module fed from an AA 30 or AA 120 Model A2143 20 coupling capacitor 10uA leakage max is...

Страница 19: ...2 13 14 15 16 Four wire circuits 4 telephone circuits on XPC 8 P2 Term 1 3 2 4 5 7 6 8 9 11 10 12 13 15 14 16 XPC to Telephone Jacks Low Level Audio Riser AA 30 AA 100 AA 120 ATG 2 ACT 1 fed from an A...

Страница 20: ...5 3 of the AM2020 AFP1010 Manual For SIB NET see Section 1 5 of this manual Initiating Device Circuit MMX 1 Monitor Module Employs contact type devices only manual pull stations heat detectors supervi...

Страница 21: ...necticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or...

Отзывы: