80-9357-0130-020 Rev. A
8
U.L. Listing
Underwriters Laboratories, Inc. listed for use on
fire and smoke barrier door assemblies when the
120VAC (60Hz) power input is supplied through
the normally closed alarm contacts of a
compatible U.L. Listed alarm system or alarm
panel.
AmericansWith Disabilities Act (A.D.A.)
ANSI Standards
ANSI A117.1
providing
accessibility and usability for physically
handicapped people"
• ANSI A156.19
"for power assist and low energy power
operated doors"
These door operators can be installed and adjusted to conform with
A.D.A. regulations.
– These door operators permit door
assemblies to conform to the requirements of this
specification "for buildings and facilities –
.
– These products are designed to conform to this
specification
.
– "PAS" Function is designed to meet or exceed all of the
requirements for the "Power Assist Door".
– "POR" Function is designed to meet or exceed all of the
requirements for the "Low Energy Power Operated Door".
C
US
UL
®
An ASSA ABLOY Group Co.
1902 Airport Road, Monroe, NC
Telephone:(800)-438-1951; Fax: (800)-338-0965
www.nortondoorcontrols.com
Door Controls
An ASSA ABLOY Group Co.
Fail Safe Electromagnetic Lock 24VDC Wiring
1
2
3
4
1
2
3
4
120VAC
Supplied by
Others
-
+
24VDC Out
Wall Switch, Card
Reader, Key Switch,
etc.
Normally Open Momentary
dry contacts
View of Jumper in
Normally Closed
Position
Jumper
(top pin
open)
Operation:
Door is normally closed and latched.
Activating switch will cut power to mag lock and
the door will automatically open. Door will close
after hold open time delay has elapsed.
The door will
during power failure.
unlock
Notes:
1. Power input Door Operator Unit is at
Power Input Terminal Strip (not shown)
120VAC 60Hz.
2. Current draw must not exceed 1.200
amps at Accessory Terminal 3.
+
-
24VDC Electromagnetic Lock
(Fail Safe)
A.D.A / UL
Normally
Open
Relay