Installation Sequence Continued

Step 9:

to increase door closing power. Door control is shipped
set at midpoint of power setting. Maximum closing
power can be achieved with 8 (360°) clockwise turns of
the power adjustment screw.

Adjust closing power of unit (See Fig. 3) - Using a 1/8”
allen wrench, turn the power adjustment shaft clockwise

Adjust Hydraulic valves using a 1/8” hex wrench to
obtain proper door closing speeds. See following

Step 10:

Power
Adjustment

1/8"

Hex

Key

Increase
Power

Decrease
Power

Closing Cycle – Make adjustments, as necessary, to the Sweep
Speed "S" valve and Latch Speed "L" valve. See Fig. 4 below for
location of valves. Turn valves clockwise to reduce speed, counter
clockwise to increase speed.

1/8"

Hex

Key

Slower
Closing

Faster
Closing

Closing Cycle

Closed

10°

L

a

tc

h

R

a

n

g

e

S

w

ee

p R

ang

e

Opening Cycle – Adjust Backcheck, "B" valve, as necessary, for
hydraulic resistance to door opening in the backcheck range. See
illustration at bottom of this page for location of valve.

1/8"

Hex

Key

Increase
Cushion

Decrease
Cushion

Opening Cycle

Backche

ck

O

p

e

ni

ng

NOTE:Too much Backcheck, "B" valve, can affect he operation

of the units pump, preventing units rom fully opening the
door. This valve may require fine tuning after all other
adjustments have been made.

t

f

Sweep Valve

Latch Valve

Backcheck

Valve

80-9357-0130-020 Rev. A

4

Step 13:

Step 13:

OFF

Step 14:

Step 15:

Step 16:

Step 17:

Step 18:

Step 19:

Step 20:

Step 21:

Step 22:

Turn power to unit on at the Unit Power Switch and turn the
Breaker Switch to “RESET”.

Using a short jumper cable, jump terminals 1 and 2, see Fig.
6 below, to activate unit. When door reaches 20 , switch
Breaker Switch to “

” position cutting power to the unit.

Allow door to fully close (door may be manually pulled
closed).

Once door has fully closed, manually open door slightly and

insert a 1/8” allen wrench (provided with screw pack) into the
clutch assembly as shown below to create a small gap
between the two clutch components.

Manually close door and remove allen wrench from clutch

assembly.

Adjust Closing Ring Position (See Fig. 8) - Loosen 8-32 set

screw located on Close Position Ring with 5/64” hex wrench
provided. Rotate Assembly until Closed Position Magnet
aligns with Reed Switch.

Adjust Open Ring Position - Loosen 8-32 set screw located

on Open Position Ring with 5/64” hex wrench provided.
Rotate Ring Assembly until Open Position Magnet is
approximately 180° from Closed Position Magnet.

Flip Breaker Switch to “RESET” to turn power on. Jump

terminals 1 and 2 (as shown in Step 13) to activate door.
Note open position of the door. Allow door to close.

Loosen and readjust Open Position Ring as necessary to

obtain desired door open position. Tighten set screw.

Make all connections necessary for any accessories to the

4-position terminal on “T1” bracket (see Pages 6 - 8).

Make necessary adjustments to inverter (see Page 6).

Replace cover and cover screws.

°

Breaker
Switch

Unit Power Switch

Figure 3

Figure 4

Note: A.D.A. requires that from an open position of
70°, the door will take at least 3 seconds to move to
a point 3” (75mm) from the latched position
measured at the leading edge of the door.

Step 11:

,

Make wiring connections using Wiring Instructions
on Page 5.

Step 12: Turn on facility’s main circuit breaker.

Figure 5

1
2
3
4

1
2
3
4

Figure 6

1/8” Allen Wrench

Clutch Assembly

Figure 7

Reed Switch

Closed Position
Magnet

Close Position Ring

Open Position

Magnet

Open Position Ring

Figure 8

Содержание LEO 5710 Series

Страница 1: ...ctice in accordance with national and local wiring codes Note Unless otherwise noted all dimensions are given in inches millimeters Minimum suggested and required material thickness for hollow metal f...

Страница 2: ...ches mm Thickness recommended for reinforcements in hollow metal doors and frames is charted at the left of this page Do not scale drawing Left hand door shown Maximum frame reveal is 6 7 8 175mm for...

Страница 3: ...r unreinforced hollow metal frames or for aluminum frames six 6 Connect conduit to frame side of backplate Fasten unit to door frame seven screws Fasten unit to door frame seven screws Mount conduit b...

Страница 4: ...door Allow door to close Loosen and readjust Open Position Ring as necessary to obtain desired door open position Tighten set screw Make all connections necessary for any accessories to the 4 positio...

Страница 5: ...talled on the bracket Optional Bracket for surface wiring Ground Lead Power Leads Ground Screw Green Cable Clamps Conduit by Others from top T1 Power Input Terminal 80 9357 0110 020 Rev A 5 Ground Wir...

Страница 6: ...lapsed 1 2 3 4 1 2 3 4 Door 1 Door 2 POT FUNCTION DESCRIPTION CL Obstruction Detection on Open CW Increase CCW Decrease MAX Door Open Speed CW Increase CCW Decrease MIN Motor Reversing Speed CW Increa...

Страница 7: ...Supplied by Others 24VDC Out 24 VDC Electric Strike Wall Switch Card Reader Key Switch etc Normally Open Momentary dry contacts Notes 1 Power input to Door Operator Unit is at T1 Power Input Terminal...

Страница 8: ...e requirements for the Power Assist Door POR Function is designed to meet or exceed all of the requirements for the Low Energy Power Operated Door C US UL An ASSAABLOY Group Co 1902 Airport Road Monro...

Страница 9: ...hinges This template not for use with offset pivots Ceiling clearance of 6 152 mm from frame rabbet is required for this application Maximum frame reveal is 1 8 3 mm for this application Conduit hole...

Страница 10: ...11 11 16 297 3 8 19 14 3 16 360 13 13 16 351 Door Opening Angle Dim A Dim B Up to 110 111 to 170 12 305 9 1 2 241 13 1 4 337 15 3 4 400 Frame Rabbet REVEAL Notes Do not scale drawing Left hand door sh...

Страница 11: ...cordance with national and local wiring codes Note Unless otherwise noted all dimensions are given in inches millimeters Minimum suggested and required material thickness for hollow metal frames skin...

Страница 12: ...mm Thickness recommended for reinforcements in hollow metal doors and frames is charted at the left of this page Do not scale drawing Left hand door shown Maximum frame reveal is 7 178mm for this app...

Страница 13: ...ith the flat corner of the pinion shaft square See Fig 1 upper right Frame Door A Prepare holes for 1 4 20 machine screws or No 14 x 2 3 4 70mm wood screws Blind rivet nuts by others are suggested for...

Страница 14: ...en door reaches 20 switch Breaker Switch to position cutting power to the unit Allow door to fully close door may be manually pulled closed Once door has fully closed manually open door slightly and i...

Страница 15: ...talled on the bracket Optional Bracket for surface wiring Ground Lead Power Leads Ground Screw Green Cable Clamps Conduit by Others from top T1 Power Input Terminal 80 9357 0130 020 Rev A 5 Ground Wir...

Страница 16: ...apsed 1 2 3 4 1 2 3 4 Door 1 Door 2 POT FUNCTION DESCRIPTION CL Obstruction Detection on Open CW Increase CCW Decrease MAX Door Open Speed CW Increase CCW Decrease MIN Motor Reversing Speed CW Increas...

Страница 17: ...Supplied by Others 24VDC Out 24 VDC Electric Strike Wall Switch Card Reader Key Switch etc Normally Open Momentary dry contacts View of Jumper in Normally Open Position For Use With Fail Safe Strike...

Страница 18: ...e requirements for the Power Assist Door POR Function is designed to meet or exceed all of the requirements for the Low Energy Power Operated Door C US UL An ASSAABLOY Group Co 1902 Airport Road Monro...

Отзывы: