Norton LEO 5710 Series Скачать руководство пользователя страница 1

Series 5710–Door Openings 85° to 110° or 111° to 180°
Rigid Arm and Slide Track Application
Maximum Hinge Side Frame Reveal to 1/8” (3mm)
Hinge (Pull) Side of Door Installation

80-9357-0110-020 Rev. A

80-9357-0110-020 Rev. A

WARNING

120 VOLT POTENTIAL PRESENT. MAKE SURE

POWER IS TURNED OFF DURING

INSTALLATION PROCEDURE.

An incorrectly installed or improperly

adjusted door operator can cause property

damage or personal injury. These

instructions should be followed to avoid the

possibility of misapplication or

misadjustment.

CAUTION

CAUTION

Right Hand Door

Left Hand Door

Left

Hand

Door

Right
Hand

Door

5700 LEO

Low Energy Power Operator

Installation Instructions

• U.L. labeled fire or smoke barrier door assemblies require that

the 120VAC (60Hz) power input to the

door operator be

supplied through normally closed alarm contacts of the alarm
system/alarm panel.

• Power input to

door operator must be 120 VAC (60Hz) to

terminals HOT and COM at terminal strip T1. Earthground
(GND) to green screw on Backplate.

• All wiring must conform to standard wiring practice in

accordance with national and local wiring codes.

• Note: Unless otherwise noted, all dimensions are given in

inches (millimeters).

• Minimum suggested and required material thickness for hollow

metal frames (skin plus reinforcement) is charted on Page 2.

• For wiring refer to Wiring Instructions on Pages 5 thru 8.

• Unit is Non-Handed.

• Door must be hung on butt hinges [5" (127mm) max. width] or

3/4" (19mm) offset pivots. A separate door and frame
preparation template will be supplied for other conditions.

• Door must swing freely through the entire opening and closing

cycle before beginning the installation.

• Use of a supplemental door stop is always recommended.

LEO

LEO

Requirements

Requirements

Installation Template

Component Layout

Installation Sequence

General Templating Information

Installation Sequence Continued

General Electrical Data

Input Power Configuration

Inverter Details

Wiring Diagram - Standard Function with Switches

Wiring Diagram - Optional Radio Frequency Function

Wiring Diagram - Fail Safe / Fail Secure Electric Strike

Wiring Diagram - Fail Safe Electromagnetic Lock

A.D.A / UL Information

1

2

2

3

3

4

5

5

6

6

7

7

8

8

1-1/2” (38mm)

Min. Frame

Face

Frame

Reveal

Door

6” (152mm)

Min. Ceiling

Clearance

1-3/4” (44mm) Min.

2-1/4” (57mm) Max.

Door Thickness

Содержание LEO 5710 Series

Страница 1: ...ctice in accordance with national and local wiring codes Note Unless otherwise noted all dimensions are given in inches millimeters Minimum suggested and required material thickness for hollow metal f...

Страница 2: ...ches mm Thickness recommended for reinforcements in hollow metal doors and frames is charted at the left of this page Do not scale drawing Left hand door shown Maximum frame reveal is 6 7 8 175mm for...

Страница 3: ...r unreinforced hollow metal frames or for aluminum frames six 6 Connect conduit to frame side of backplate Fasten unit to door frame seven screws Fasten unit to door frame seven screws Mount conduit b...

Страница 4: ...door Allow door to close Loosen and readjust Open Position Ring as necessary to obtain desired door open position Tighten set screw Make all connections necessary for any accessories to the 4 positio...

Страница 5: ...talled on the bracket Optional Bracket for surface wiring Ground Lead Power Leads Ground Screw Green Cable Clamps Conduit by Others from top T1 Power Input Terminal 80 9357 0110 020 Rev A 5 Ground Wir...

Страница 6: ...lapsed 1 2 3 4 1 2 3 4 Door 1 Door 2 POT FUNCTION DESCRIPTION CL Obstruction Detection on Open CW Increase CCW Decrease MAX Door Open Speed CW Increase CCW Decrease MIN Motor Reversing Speed CW Increa...

Страница 7: ...Supplied by Others 24VDC Out 24 VDC Electric Strike Wall Switch Card Reader Key Switch etc Normally Open Momentary dry contacts Notes 1 Power input to Door Operator Unit is at T1 Power Input Terminal...

Страница 8: ...e requirements for the Power Assist Door POR Function is designed to meet or exceed all of the requirements for the Low Energy Power Operated Door C US UL An ASSAABLOY Group Co 1902 Airport Road Monro...

Страница 9: ...hinges This template not for use with offset pivots Ceiling clearance of 6 152 mm from frame rabbet is required for this application Maximum frame reveal is 1 8 3 mm for this application Conduit hole...

Страница 10: ...11 11 16 297 3 8 19 14 3 16 360 13 13 16 351 Door Opening Angle Dim A Dim B Up to 110 111 to 170 12 305 9 1 2 241 13 1 4 337 15 3 4 400 Frame Rabbet REVEAL Notes Do not scale drawing Left hand door sh...

Страница 11: ...cordance with national and local wiring codes Note Unless otherwise noted all dimensions are given in inches millimeters Minimum suggested and required material thickness for hollow metal frames skin...

Страница 12: ...mm Thickness recommended for reinforcements in hollow metal doors and frames is charted at the left of this page Do not scale drawing Left hand door shown Maximum frame reveal is 7 178mm for this app...

Страница 13: ...ith the flat corner of the pinion shaft square See Fig 1 upper right Frame Door A Prepare holes for 1 4 20 machine screws or No 14 x 2 3 4 70mm wood screws Blind rivet nuts by others are suggested for...

Страница 14: ...en door reaches 20 switch Breaker Switch to position cutting power to the unit Allow door to fully close door may be manually pulled closed Once door has fully closed manually open door slightly and i...

Страница 15: ...talled on the bracket Optional Bracket for surface wiring Ground Lead Power Leads Ground Screw Green Cable Clamps Conduit by Others from top T1 Power Input Terminal 80 9357 0130 020 Rev A 5 Ground Wir...

Страница 16: ...apsed 1 2 3 4 1 2 3 4 Door 1 Door 2 POT FUNCTION DESCRIPTION CL Obstruction Detection on Open CW Increase CCW Decrease MAX Door Open Speed CW Increase CCW Decrease MIN Motor Reversing Speed CW Increas...

Страница 17: ...Supplied by Others 24VDC Out 24 VDC Electric Strike Wall Switch Card Reader Key Switch etc Normally Open Momentary dry contacts View of Jumper in Normally Open Position For Use With Fail Safe Strike...

Страница 18: ...e requirements for the Power Assist Door POR Function is designed to meet or exceed all of the requirements for the Low Energy Power Operated Door C US UL An ASSAABLOY Group Co 1902 Airport Road Monro...

Отзывы: