ambient temperature of the room. Take appropriate steps to ensure that the
device does not overheat.
For proper air circulation, the vents on the front and back of the device must
not be blocked or obstructed by cables, panels, rack frames, or other
materials.
Electrical safety
To avoid the possibility of serious personal injury or damage to equipment
due to electrical malfunction, follow these precautions.
•
Circuits and wiring must support the rated power draw of the equipment.
•
Total rack-power load is equal to a maximum of eighty percent of the
branch circuit rating.
•
Power cords are free of obstructions.
•
Power cords at plugs, convenience receptacles, and points of exit from
the SMC are carefully positioned.
Mechanical safety
For rack mounted installation, ensure that racks are stable and securely
installed.
DANGER OF ELECTRIC SHOCK
Use only power cords that have a grounding path.
Without a proper ground, a person who touches the SMC
is in danger of receiving an electrical shock. Lack of a
grounding path to the SMC may result in excessive
emissions.
CAUTION — Service Interruption
When mounting the SMC in a rack,
each
SMC must be
secured to the rack with appropriate mounting brackets.
Each bracket is designed to support the weight of
one SMC.
Содержание SMC 2450
Страница 2: ......
Страница 4: ...Page 4 of 260 Revision history 553 3001 225 Standard 1 00 May 2006...
Страница 10: ...Page 10 of 260 Contents 553 3001 225 Standard 1 00 May 2006 Format 251 Log message table 253...
Страница 16: ...Page 16 of 260 List of procedures 553 3001 225 Standard 1 00 May 2006...
Страница 20: ...Page 20 of 260 About this document 553 3001 225 Standard 1 00 May 2006...
Страница 27: ...Description Page 27 of 260 Secure Multimedia Controller Implementation Guide Figure 1 Basic subnet mappings...
Страница 51: ...Description Page 51 of 260 Secure Multimedia Controller Implementation Guide Figure 7 SMC campus redundancy...
Страница 56: ...Page 56 of 260 Description 553 3001 225 Standard 1 00 May 2006...
Страница 76: ...Page 76 of 260 Hardware installation 553 3001 225 Standard 1 00 May 2006...
Страница 120: ...Page 120 of 260 Firewall deployment 553 3001 225 Standard 1 00 May 2006...
Страница 126: ...Page 126 of 260 Secure UNIStim deployment 553 3001 225 Standard 1 00 May 2006 Figure 22 Sample policy page...
Страница 160: ...Page 160 of 260 Secure UNIStim deployment 553 3001 225 Standard 1 00 May 2006...
Страница 182: ...Page 182 of 260 Maintenance 553 3001 225 Standard 1 00 May 2006...
Страница 196: ...Page 196 of 260 The Command Line Interface CLI 553 3001 225 Standard 1 00 May 2006...
Страница 212: ...Page 212 of 260 Logging 553 3001 225 Standard 1 00 May 2006...
Страница 228: ...Page 228 of 260 Appendix C Regulatory information 553 3001 225 Standard 1 00 May 2006 DenAn regulatory notice for Japan...
Страница 250: ...Page 250 of 260 Appendix D Software licenses 553 3001 225 Standard 1 00 May 2006...
Страница 260: ...Page 260 of 260 Appendix E SMC packet filter log messages 553 3001 225 Standard 1 00 May 2006...
Страница 261: ......