background image

9

If the outdoor temperature is above 65 degrees F or higher:

Charge the system following the steps below:

1. With the system operating at steady state, measure the 

superheat at suction line service valve for fixed orifice systems, 

like P7RE-018K/024K/030K/036K/042K/ 048KA, or measure 

the subcooling at the liquid service valve for TXV systems, 

like P7RE X60 KA model.

2. Measure the outdoor dry bulb temperature ( F) and indoor 

wet bulb temperature ( F).

 

NOTE:

 The charging tables are on the inside of the unit’s 

electrical control access panel. The tables provide superheat 

targets for th e units with fixed orifice and subcooling targets 

for TXV systems.

3. Adjust the charge to match the target superheat or target 

subcooling.

4. The system should be charged so that the measured superheat/

subcooling is / 1 F of the target listed in the table.

For fixed orifice system:

•  If your measured superheat at the suction valve is 

LESS

 

THAN

 the recommended superheat value in the table then 

REMOVE

 refrigerant.

•  If your measured superheat at the suction valve is 

GREATER

 

THAN

 the recommended superheat value in the table then 

ADD

 refrigerant.

For TXV systems:

•  If your measured subcooling at the liquid valve is 

LESS THAN

 

the recommended subcooling value in the table then 

ADD

 

refrigerant.

•  If your measured subcooling at the liquid valve is 

GREATER

 

THAN

 the recommended subcooling value in the table then 

REMOVE

 refrigerant.

If the outdoor temperature is below 65 degrees F:

After leak checking the system, and evacuating the system,

perform the following steps:

1. weigh in the charge amounts recommended and printed on 

the unit rating plate, the rating plate can be found on the 

exterior panel of the unit.

2. Return to the system when the outdoor temperature is 65 

degrees F or higher and follow the steps defined at “If the 

outdoor temperature is 65 degrees F or higher” section above.

Safety switches

The high-pressure switch is factory-installed and located in the 

liquid line internal to the unit. The switch is designed to protect 

the system when very high pressures occur during abnormal 

conditions. Under normal conditions, the switch is closed. If the 

liquid pressure rises above 650 psig, the switch will open and 

de-energize the unit. The switch will close again when the liquid 

pressure decreases to 460 psig.

AIR CONDITIONER MAINTENANCE

 WARNING:

To prevent electrical shock, personal injury, or 

death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

The unit may have more than one electrical 

supply.

Proper maintenance is important to achieve optimum 

performance from the air conditioner. The ability to properly 

perform maintenance on this equipment requires certain 

mechanical skills and tools. If you do not possess these skills, 

contact your dealer for maintenance. Consult your local dealer 

about the availability of maintenance contracts. 
Routine maintenance should include the following:
•  Inspect and clean or replace air filters at the beginning of each 

heating and cooling season, or more frequently if required.

•  Inspect the condensate drain and outdoor coil at the beginning 

of each cooling season. Remove any debris. Clean the outdoor 

coil and louvers as necessary using a mild detergent and 

water. Rinse thoroughly with water.

•  Inspect the electrical connections for tightness at the beginning 

of each heating and cooling season. Service as necessary.

 CAUTION:

The unit should never be operated without a 

filter in the return air system. Replace disposable 

filters with the same type and size.

•  Do not add additional oil to motors unequipped with oil tubes. 

The compressor is hermetically sealed at the factory and does 

not require lubrication.

REFRIGERANT CHARGING

Charging the Unit

 CAUTION:

This air conditioner contains liquid and gaseous 

refrigerant under pressure. Adjustment of 

refrigerant charge should only be attempted 

by qualified, trained personnel thoroughly 

familiar with the equipment and safe responsible 

refrigerant handling procedures. Under no 

circumstances should the homeowner attempt 

to install and/or service this equipment. Failure 

to comply with this warning could result in 

equipment damage, personal injury, or death.

NOTE:

 The refrigerant charge can be checked and adjusted 

through the service ports provided external to the unit. Use 

only gage line sets which have a “Schrader” depression device 

present to actuate the valve.

Содержание VP7RE Series

Страница 1: ...plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require lic...

Страница 2: ...ate a degree or level of seriousness and should not be ignored WARNING indicates a potentially hazardous situation that if not avoided could result in personal injury or death CAUTION indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury or property damage WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly co...

Страница 3: ...rom the airflow data found in Table 3 page 11 Place appropriate wire on the appropriate motor speed tap for the required airflow GENERAL INFORMATION This packaged air conditioner is designed only for outdoor ground level installations and can be readily connected to the high static duct system of a home This unit has been tested for capacity and efficiency in accordance with AHRI Standards and wil...

Страница 4: ...r visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of America ACCA The supply duct system including the number and type of registers will have much more effect on the performance of the system than any other factor The duct must be sufficiently large to conduct an adequate amount of air to each register See Figure 2 Duct work sho...

Страница 5: ...r greater than a 12 x 20 grille The return air grille can be placed in the wall of a closet and the air ducted into the filter box through a boxed in area at the closet floor level Figure 4 Verify the filter is readily accessible NOTE The return air box with grille and filter should not be located in heavy traffic areas like hallways or center of rooms A good spot is in a corner or under a table i...

Страница 6: ...ow safety warnings exactly could resultinseriousinjury deathorpropertydamage Improper servicing could result in dangerous operation serious injury death or property damage Beforeservicing disconnectallelectricalpower to the indoor blower When servicing controls label all wires prior to disconnecting Reconnect wires correctly Verify proper operation after servicing All electrical connections must b...

Страница 7: ...s of the NEC ANSI NFPA 70 and with applicable localcodeshavingjurisdiction Thermostatconnectionsshould Low Voltage Line Voltage be made in accordance with the instructions supplied with the thermostat and the indoor equipment Thelowvoltagewiresmustbeproperlyconnected Route24V control wires through the sealing grommet near the power entrance See Figure 7 Recommended wire gauge and wire lengths for ...

Страница 8: ...st 24 hours prior to running After unit startup the compressor must run for a minimum of 12 hours Start Up Procedure CAUTION If the unit is equipped with a crankcase heater allow 24 hours prior to continuing the start up procedures to allow for heating of the refrigerant compressor crankcase Failure to comply may result in damage and could cause premature failure of the system This warning should ...

Страница 9: ...nditions Under normal conditions the switch is closed If the liquid pressure rises above 650 psig the switch will open and de energize the unit The switch will close again when the liquid pressure decreases to 460 psig AIR CONDITIONER MAINTENANCE WARNING To prevent electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The...

Страница 10: ...n 1 12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton MODEL NUMBER LENGTH L WIDTH W HEIGHT H A B RETURN DIAMETER IN SUPPLY DIAMETER IN 018K 49 35 22 2 35 02 2 48 12 12 024K 49 35 22 2 35 02 2 48 12 12 030K 49 35 22 2 35 02 2 48 12 12 036K 49 35 22 2 35 02 2 4...

Страница 11: ... 33 900 35 840 38 Tap T2 1313 24 1277 25 1236 26 1190 27 1153 27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1450 22 1410 22 1370 23 1315 24 1270 25 042K Tap T1 1375 23 1345 23 1310 24 1275 25 1240 25 1205 26 1160 27 1120 28 Tap T2 1470 21 1435 22 ...

Страница 12: ...s en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See installati...

Страница 13: ... conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...ty correct YES NO Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO Rated Voltage __________________________________________________________________ VOLTS L1 L2 Volts ____________________________________________________________________ VOLTS INSTALLATION ADDRESS CITY__________________________________________ STATE_...

Отзывы: