background image

3

 CAUTION:

This unit uses R-410A refrigerant. DO NOT use 

any other refrigerant in this unit. Use of another 

refrigerant will damage the unit.

 WARNING:

The information listed below must be followed 

during the installation, service, and operation 

of this unit. Unqualified individuals should not 

attempt to interpret these instructions or install 

this equipment. If you do not posses mechanical 

skills or tools, call your local dealer for assistance. 

Failure to follow safety recommendations could 

result in possible damage to the equipment, 

serious personal injury or death.

•  Before beginning the installation, verify that the unit model is 

correct for the job. The unit model number is printed on the 

data label.

• This equipment contains liquid and gaseous refrigerant 

under high pressure. 

DO NOT USE ANY PORTION OF THE 

CHARGE FOR PURGING OR LEAK TESTING.

 Installation 

or servicing should only be performed by qualified trained 

personnel thoroughly familiar with this type equipment.

•  Installation of equipment may require brazing operations. 

Installer must comply with safety codes and wear appropriate 

safety equipment (safety glasses, work gloves, fire extinguisher, 

etc.) when performing brazing operations.

•  This unit is designed for outdoor installations only and should be 

located in a position as shown on 

page 4

Unit dimensions 

are shown in 

Figure 9 

Table 2, (page 10)

.

•  The installer should become familiar with the units wiring 

diagram before making any electrical connections to the unit. 

See the unit wiring label or 

Figure 10 (page 12)

 and 

Figure 

11 (page 13)

.

•  Follow all precautions in the literature, on tags, and on labels 

provided with the equipment. Read and thoroughly understand 

the instructions provided with the equipment prior to performing 

the installation and operational checkout of the equipment.

• Use caution when handling this appliance or removing 

components. Personal injury can occur from sharp metal 

edges present in all sheet metal constructed equipment.

REQUIREMENTS & CODES

•  All electrical wiring must be completed in accordance with 

local, state and national codes and regulations and with the 

National Electric Code (ANSI/NFPA 70) or in Canada the 

Canadian Electric Code Part 1 CSA C.22.1.

•  The installer must comply with all local codes and regulations 

which govern the installation of this type of equipment. 

Local codes and regulations take precedence over any 

recommendations contained in these instructions. Consult 

local building codes and the National Electrical Code (ANSI 

CI) for special installation requirements.

•  Air Ducts must be installed in accordance with the standards 

of the National Fire Protection Association “Standards for 

Installation of Air Conditioning and Ventilation Systems” (NFPA 

90A), “Standard for Installation of Residence Type Warm Air 

Heating and Air Conditioning Systems” (NFPA 90B), these 

instructions, and all applicable local codes.

•  Verify the required speed from the airflow data found in 

Table 

3, (page 11)

. Place appropriate wire on the appropriate 

motor speed tap for the required airflow.

GENERAL INFORMATION

This packaged air conditioner is designed only for outdoor 

ground level installations and can be readily connected to the 

high static duct system of a home. This unit has been tested 

for capacity and efficiency in accordance with AHRI Standards 

and will provide many years of safe and dependable comfort, 

providing it is properly installed and maintained. Abuse, improper 

use, and/or improper maintenance can shorten the life of the 

appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment failure, 

it is recommended that periodic maintenance be performed on 

this unit. The ability to properly perform maintenance on this 

equipment requires certain mechanical skills and tools.

Before You Install this Unit

 The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. It is 

recommended that the area to be conditioned be completely 

insulated and vapor sealed.

 Check the electrical supply and verify the power supply is 

adequate for unit operation. If there is any question concerning 

the power supply, contact the local power company.

 All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage prior 

to installing the equipment at the job site. Verify coil fins are 

straight. If necessary, comb fins to remove flattened or bent 

fins. Claims for damage (apparent or concealed) should be 

filed immediately with the carrier.

 Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read all 

instructions before installing the unit.

Locating the Air Conditioner

•  Survey the job site to determine the best location for mounting 

the outdoor unit. Select a solid, level position, preferably on 

a concrete slab, slightly above the grade level, and parallel 

to the home. If possible, select a site for the unit that is as 

close as possible to the proposed return grille location. Unit 

dimensions are shown in 

Figure 9 

Table 2, (page 10)

DO NOT PLACE UNIT UNDER THE HOME.

•  The unit should be located with consideration of minimizing 

the length of the supply and return ducts. If practical, place 

the air conditioner and its ducts in an area where they will be 

shaded from the afternoon sun, when the heat load is greatest.

•  The length of the supply and return ducts should be kept to 

a minimum with no sharp radius bends.

•  Overhead obstructions, poorly ventilated areas, and areas 

subject to accumulation of debris should be avoided. The 

hot condenser air must be discharged up and away from the 

home, and if possible, in a direction with the prevailing wind. 

Do not place the unit in a confined space. See 

Figure 9 

Table 2, (page 10)

 for unit dimensions.

• Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to achieve rated 

performance.

•  Consideration should also be given to availability of electric 

power, service access, noise, and shade.

Содержание VP7RE Series

Страница 1: ...plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require lic...

Страница 2: ...ate a degree or level of seriousness and should not be ignored WARNING indicates a potentially hazardous situation that if not avoided could result in personal injury or death CAUTION indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury or property damage WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly co...

Страница 3: ...rom the airflow data found in Table 3 page 11 Place appropriate wire on the appropriate motor speed tap for the required airflow GENERAL INFORMATION This packaged air conditioner is designed only for outdoor ground level installations and can be readily connected to the high static duct system of a home This unit has been tested for capacity and efficiency in accordance with AHRI Standards and wil...

Страница 4: ...r visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of America ACCA The supply duct system including the number and type of registers will have much more effect on the performance of the system than any other factor The duct must be sufficiently large to conduct an adequate amount of air to each register See Figure 2 Duct work sho...

Страница 5: ...r greater than a 12 x 20 grille The return air grille can be placed in the wall of a closet and the air ducted into the filter box through a boxed in area at the closet floor level Figure 4 Verify the filter is readily accessible NOTE The return air box with grille and filter should not be located in heavy traffic areas like hallways or center of rooms A good spot is in a corner or under a table i...

Страница 6: ...ow safety warnings exactly could resultinseriousinjury deathorpropertydamage Improper servicing could result in dangerous operation serious injury death or property damage Beforeservicing disconnectallelectricalpower to the indoor blower When servicing controls label all wires prior to disconnecting Reconnect wires correctly Verify proper operation after servicing All electrical connections must b...

Страница 7: ...s of the NEC ANSI NFPA 70 and with applicable localcodeshavingjurisdiction Thermostatconnectionsshould Low Voltage Line Voltage be made in accordance with the instructions supplied with the thermostat and the indoor equipment Thelowvoltagewiresmustbeproperlyconnected Route24V control wires through the sealing grommet near the power entrance See Figure 7 Recommended wire gauge and wire lengths for ...

Страница 8: ...st 24 hours prior to running After unit startup the compressor must run for a minimum of 12 hours Start Up Procedure CAUTION If the unit is equipped with a crankcase heater allow 24 hours prior to continuing the start up procedures to allow for heating of the refrigerant compressor crankcase Failure to comply may result in damage and could cause premature failure of the system This warning should ...

Страница 9: ...nditions Under normal conditions the switch is closed If the liquid pressure rises above 650 psig the switch will open and de energize the unit The switch will close again when the liquid pressure decreases to 460 psig AIR CONDITIONER MAINTENANCE WARNING To prevent electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The...

Страница 10: ...n 1 12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton MODEL NUMBER LENGTH L WIDTH W HEIGHT H A B RETURN DIAMETER IN SUPPLY DIAMETER IN 018K 49 35 22 2 35 02 2 48 12 12 024K 49 35 22 2 35 02 2 48 12 12 030K 49 35 22 2 35 02 2 48 12 12 036K 49 35 22 2 35 02 2 4...

Страница 11: ... 33 900 35 840 38 Tap T2 1313 24 1277 25 1236 26 1190 27 1153 27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1450 22 1410 22 1370 23 1315 24 1270 25 042K Tap T1 1375 23 1345 23 1310 24 1275 25 1240 25 1205 26 1160 27 1120 28 Tap T2 1470 21 1435 22 ...

Страница 12: ...s en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See installati...

Страница 13: ... conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...ty correct YES NO Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO Rated Voltage __________________________________________________________________ VOLTS L1 L2 Volts ____________________________________________________________________ VOLTS INSTALLATION ADDRESS CITY__________________________________________ STATE_...

Отзывы: