background image

8

Blower Speed

For optimum system performance and comfort, it may be 

necessary to change the factory speed setting. See 

Table 3, 

(page 11)

 for factory settings.

 WARNING:

To avoid electric shock, personal injury, or death, 

turn off the electric power at the disconnect or the 

main service panel before making any electrical 

connections.

 CAUTION:

Label all wires prior to disconnection when 

servicing controls. Wiring errors can cause 

improper and dangerous operation. Verify proper 

operation after servicing.

 CAUTION:

To avoid personal injury or property damage, 

make certain that the motor leads cannot come 

into contact with any metal components of the 

unit.

1. Disconnect all electrical power to the unit and remove the 

service panel.

2. Locate the orange and red wires terminated to the blower 

motor. 

NOTE: 

The orange wire controls cooling operation 

and the red wire controls the heating operation.

3. Verify the required speed from the airflow data found in 

Table 

3, (page 11)

. Place appropriate wire on the appropriate 

motor speed tap for the required airflow.

4. Check all factory wiring as shown in the wiring diagram and 

inspect the connections to make sure none of them loosened 

during shipping or installation.

START UP & ADJUSTMENTS

Pre-Start Checklist

The following check list should be observed prior to starting 

the unit.

  Verify the unit is level and allows proper condensate drainage.

 Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/control 

panels are in place. Unit must be installed with the proper 

clearances shown in 

Figure 1 (page 4)

.

  Verify that the duct work is sealed to prevent air leakage.

  Verify that the line voltage power leads are securely connected 

and the unit is properly grounded. Check the condenser fan 

to make sure it turns freely.

  Verify the thermostat is wired correctly and installed in a 

proper location. Make sure the low voltage wires are securely 

connected to the correct leads on the low voltage terminal 

strip.

 Verify that the power supply branch circuit overcurrent 

protection is sized properly.

  To achieve rated capacity and efficiency the compressor must 

be exposed to refrigerant for at least 24 hours prior to running. 

After unit startup, the compressor must run for a minimum of 

12 hours.

Start-Up Procedure

 CAUTION:

If the unit is equipped with a crankcase heater, 

allow 24 hours prior to continuing the start up 

procedures to allow for heating of the refrigerant 

compressor crankcase. Failure to comply may 

result in damage and could cause premature 

failure of the system. This warning should be 

followed at initial start up and any time the power 

has been removed for 12 hours or longer.

The control circuit thermostat may consist of an anti-short cycle 

timer that will not let the compressor re-start before 5 minutes 

have elapsed.

1. Set the system mode to OFF and the temperature mode to 

its highest setting.

2. Turn power on at the disconnect switch.

3. Set the system mode to ON or COOL.

4. Set the temperature mode below room temperature. Verify 

that the indoor blower, outdoor fan, and compressor energize 

and the cooling function starts.

5. Verify the discharge air grilles are adjusted and the system 

air is balanced.

6. Verify the duct work has no air leaks.

7. Verify the condensate drain is installed correctly and functions 

properly.

8. Set the temperature mode above room temperature. The unit 

should stop.

9. Instruct the homeowner on unit and thermostat operation and 

filter servicing.

Air Circulation

Leave the thermostat system mode on OFF, and set the fan 

mode to ON. Blower should run continuously. Check the air 

delivery at the supply registers and adjust register openings for 

balanced air distribution. Examine ducts for leaks or obstruction 

if insufficient air is detected.
Set the thermostat fan mode to AUTO. The blower should stop 

running.

System Cooling

Set the thermostat’s system mode to COOL and the fan mode 

to AUTO. Lower the thermostat temperature selector below the 

existing room temperature. Allow the cooling system to operate 

for several minutes and check for the discharge of cool air at 

the supply registers.

System Heating

(Available only when Electric heat is supplied) Set the 

thermostat’s system mode to HEAT and the fan mode to either 

AUTO (intermittent air) or to ON (continuous air). Raise the 

thermostat’s temperature selector above the existing room 

temperature and check the following:
1. The compressor and outdoor fan should not run.

2. The blower will run according to the thermostat’s fan mode 

setting.

Содержание VP7RE Series

Страница 1: ...plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require lic...

Страница 2: ...ate a degree or level of seriousness and should not be ignored WARNING indicates a potentially hazardous situation that if not avoided could result in personal injury or death CAUTION indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury or property damage WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly co...

Страница 3: ...rom the airflow data found in Table 3 page 11 Place appropriate wire on the appropriate motor speed tap for the required airflow GENERAL INFORMATION This packaged air conditioner is designed only for outdoor ground level installations and can be readily connected to the high static duct system of a home This unit has been tested for capacity and efficiency in accordance with AHRI Standards and wil...

Страница 4: ...r visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of America ACCA The supply duct system including the number and type of registers will have much more effect on the performance of the system than any other factor The duct must be sufficiently large to conduct an adequate amount of air to each register See Figure 2 Duct work sho...

Страница 5: ...r greater than a 12 x 20 grille The return air grille can be placed in the wall of a closet and the air ducted into the filter box through a boxed in area at the closet floor level Figure 4 Verify the filter is readily accessible NOTE The return air box with grille and filter should not be located in heavy traffic areas like hallways or center of rooms A good spot is in a corner or under a table i...

Страница 6: ...ow safety warnings exactly could resultinseriousinjury deathorpropertydamage Improper servicing could result in dangerous operation serious injury death or property damage Beforeservicing disconnectallelectricalpower to the indoor blower When servicing controls label all wires prior to disconnecting Reconnect wires correctly Verify proper operation after servicing All electrical connections must b...

Страница 7: ...s of the NEC ANSI NFPA 70 and with applicable localcodeshavingjurisdiction Thermostatconnectionsshould Low Voltage Line Voltage be made in accordance with the instructions supplied with the thermostat and the indoor equipment Thelowvoltagewiresmustbeproperlyconnected Route24V control wires through the sealing grommet near the power entrance See Figure 7 Recommended wire gauge and wire lengths for ...

Страница 8: ...st 24 hours prior to running After unit startup the compressor must run for a minimum of 12 hours Start Up Procedure CAUTION If the unit is equipped with a crankcase heater allow 24 hours prior to continuing the start up procedures to allow for heating of the refrigerant compressor crankcase Failure to comply may result in damage and could cause premature failure of the system This warning should ...

Страница 9: ...nditions Under normal conditions the switch is closed If the liquid pressure rises above 650 psig the switch will open and de energize the unit The switch will close again when the liquid pressure decreases to 460 psig AIR CONDITIONER MAINTENANCE WARNING To prevent electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The...

Страница 10: ...n 1 12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton MODEL NUMBER LENGTH L WIDTH W HEIGHT H A B RETURN DIAMETER IN SUPPLY DIAMETER IN 018K 49 35 22 2 35 02 2 48 12 12 024K 49 35 22 2 35 02 2 48 12 12 030K 49 35 22 2 35 02 2 48 12 12 036K 49 35 22 2 35 02 2 4...

Страница 11: ... 33 900 35 840 38 Tap T2 1313 24 1277 25 1236 26 1190 27 1153 27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1450 22 1410 22 1370 23 1315 24 1270 25 042K Tap T1 1375 23 1345 23 1310 24 1275 25 1240 25 1205 26 1160 27 1120 28 Tap T2 1470 21 1435 22 ...

Страница 12: ...s en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See installati...

Страница 13: ... conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...ty correct YES NO Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO Rated Voltage __________________________________________________________________ VOLTS L1 L2 Volts ____________________________________________________________________ VOLTS INSTALLATION ADDRESS CITY__________________________________________ STATE_...

Отзывы: