background image

7

•  The unit requires both power and control circuit electrical 

connections. Refer to the wiring diagrams (

Figure 10 (page 

12)

 & 

Figure 11 (page 13)

) for identification and location 

of unit field wiring interfaces. Make all electrical connections 

in accordance with all applicable codes and ordinances.

•  Use only copper wire for the line voltage power supply to this 

unit. Use proper code agency listed conduit and a conduit 

connector for connecting the supply wires to the unit. Use of 

rain tight conduit is recommended.

•  208/230 Volt units are shipped from the factory wired for 230 

volt operation. For 208V operation, remove the lead from 

the transformer terminal marked 240V and connect it to the 

terminal marked 208V.

•  Optional equipment requiring connection to the power or 

control circuits must be wired in strict accordance of the NEC 

(ANSI/NFPA 70), applicable local codes, and the instructions 

provided with the equipment.

Grounding

 WARNING:

The unit cabinet must have an uninterrupted or 

unbroken electrical ground to minimize personal 

injury if an electrical fault should occur. Do not 

use gas piping as an electrical ground!

This unit must be electrically grounded in accordance with 

local codes or, in the absence of local codes, with the National 

Electrical Code (ANSI/NFPA 70) or CSA C22.1 Electrical Code. 

Ground the air conditioning unit using the green grounding screw 

provided in the control panel.

Overcurrent Protection

Overcurrent protection must be provided at the branch circuit 

distribution panel and sized as shown on the unit rating label and 

according to applicable local codes. Generally, the best fuse or 

breaker for any heat pump is the smallest size that will permit 

the equipment to run under normal usage and provide maximum 

equipment protection. Properly sized fuses and breakers also 

prevent nuisance trips during unit startup.

NOTE: If a fuse blows or a breaker trips, always determine 

the reason. Do not arbitrarily install a larger fuse or breaker 

and do not, in any case, exceed the maximum size listed 

on the data label of the unit.

Thermostat / Low Voltage Connections

•  The unit is designed to operate from a 24 VAC Class II control 

circuit. The control circuit wiring must comply with the current 

provisions of the NEC (ANSI/NFPA 70) and with applicable 

local codes having jurisdiction. Thermostat connections should 

Low Voltage

Line Voltage

be made in accordance with the instructions supplied with the 

thermostat and the indoor equipment.

•  The low voltage wires must be properly connected. Route 24V 

control wires through the sealing grommet near the power 

entrance. See 

Figure 7

. Recommended wire gauge and wire 

lengths for typical thermostat connections are listed in 

Table 

1

.

•  Single stage or two-stage heating thermostats can be used with 

this equipment depending on optional accessories installed 

with the unit. Select a thermostat that operates in conjunction 

with the installed accessories.

•  The thermostat should be mounted about 5 feet above the 

floor on an inside wall. DO NOT install the thermostat on an 

outside wall or any other location where its operation may be 

adversely affected by radiant heat from fireplaces, sunlight, 

lighting fixtures or convective heat from warm air registers or 

electrical appliances. Refer to the thermostat manufacturer’s 

instruction sheet for detailed mounting information.

Cooling Only Thermostat

Connect the 

red

 & 

yellow

 wires from the unit to the 

R

 & 

Y

 

terminals on the thermostat subbase. Connect the 

green

 wire 

to the 

yellow

 wire at the unit. See 

Figure 8

.

Heat / Cool Thermostat

For the highest efficiency, the use of a 2-stage Heating/Cooling 

thermostat is recommended. The heat/cool thermostat prevents 

simultaneous operation of the heating and cooling units and is 

equipped with an ON-AUTO fan mode that allows the home owner 

to operate the indoor blower when only air circulation is desired.

Connect the red, yellow, green and brown/orange low voltage 

wires to the 

R

 or 

RC

Y

G,

 

or 

W2 

(if applicable) terminals 

on the thermostat base. The black wire is the 24 volt common 

required on some thermostats. See 

Figure 8 (page 7)

.

Figure 7. Power Entry

Figure 8. Low Voltage Connections

RED

R

YELLOW

Y

GREEN

G

BROWN

*

W1

ORANGE

RED

R

YELLOW

Y

GREEN

G

BROWN

*

W

ORANGE

4 WIRE HEAT/COOL THERMOSTAT

Two Stage Heating T-Stat

Single Stage Electric Heat

RED

R

YELLOW

Y

GREEN

2 WIRE COOLING

(ONLY) THERMOSTAT

CONTROL WIRE LEGEND:
GREEN - Blower Relay
RED - Transformer (24V)
YELLOW - Cooling 1st Stage
BROWN - Heating 1st Stage
ORANGE - Heating 2nd Stage

*

W2

*Connected when Optional Electric Heating Kit is Installed.

Table 1. Control Wiring (24V)

WIRE GAUGE

RECOMMENDED MAXIMUM

WIRE LENGTH (FT) FROM UNIT

TO THERMOSTAT

22

45

20

70

18

115

16

180

Содержание VP7RE Series

Страница 1: ...plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require lic...

Страница 2: ...ate a degree or level of seriousness and should not be ignored WARNING indicates a potentially hazardous situation that if not avoided could result in personal injury or death CAUTION indicates a potentially hazardous situation that if not avoided may result in minor or moderate injury or property damage WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly co...

Страница 3: ...rom the airflow data found in Table 3 page 11 Place appropriate wire on the appropriate motor speed tap for the required airflow GENERAL INFORMATION This packaged air conditioner is designed only for outdoor ground level installations and can be readily connected to the high static duct system of a home This unit has been tested for capacity and efficiency in accordance with AHRI Standards and wil...

Страница 4: ...r visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of America ACCA The supply duct system including the number and type of registers will have much more effect on the performance of the system than any other factor The duct must be sufficiently large to conduct an adequate amount of air to each register See Figure 2 Duct work sho...

Страница 5: ...r greater than a 12 x 20 grille The return air grille can be placed in the wall of a closet and the air ducted into the filter box through a boxed in area at the closet floor level Figure 4 Verify the filter is readily accessible NOTE The return air box with grille and filter should not be located in heavy traffic areas like hallways or center of rooms A good spot is in a corner or under a table i...

Страница 6: ...ow safety warnings exactly could resultinseriousinjury deathorpropertydamage Improper servicing could result in dangerous operation serious injury death or property damage Beforeservicing disconnectallelectricalpower to the indoor blower When servicing controls label all wires prior to disconnecting Reconnect wires correctly Verify proper operation after servicing All electrical connections must b...

Страница 7: ...s of the NEC ANSI NFPA 70 and with applicable localcodeshavingjurisdiction Thermostatconnectionsshould Low Voltage Line Voltage be made in accordance with the instructions supplied with the thermostat and the indoor equipment Thelowvoltagewiresmustbeproperlyconnected Route24V control wires through the sealing grommet near the power entrance See Figure 7 Recommended wire gauge and wire lengths for ...

Страница 8: ...st 24 hours prior to running After unit startup the compressor must run for a minimum of 12 hours Start Up Procedure CAUTION If the unit is equipped with a crankcase heater allow 24 hours prior to continuing the start up procedures to allow for heating of the refrigerant compressor crankcase Failure to comply may result in damage and could cause premature failure of the system This warning should ...

Страница 9: ...nditions Under normal conditions the switch is closed If the liquid pressure rises above 650 psig the switch will open and de energize the unit The switch will close again when the liquid pressure decreases to 460 psig AIR CONDITIONER MAINTENANCE WARNING To prevent electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The...

Страница 10: ...n 1 12 13 1 38 3 2 3 2 5 29 Side View Figure 9 Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View 3 5 4 5 Ton MODEL NUMBER LENGTH L WIDTH W HEIGHT H A B RETURN DIAMETER IN SUPPLY DIAMETER IN 018K 49 35 22 2 35 02 2 48 12 12 024K 49 35 22 2 35 02 2 48 12 12 030K 49 35 22 2 35 02 2 48 12 12 036K 49 35 22 2 35 02 2 4...

Страница 11: ... 33 900 35 840 38 Tap T2 1313 24 1277 25 1236 26 1190 27 1153 27 1104 29 1051 30 992 32 Tap T3 1460 22 1415 22 1385 23 1335 24 1275 25 1225 26 1170 27 1120 28 Tap T4 1502 21 1466 22 1437 22 1388 23 1345 23 1305 24 1251 25 1204 26 Tap T5 1565 20 1525 21 1490 21 1450 22 1410 22 1370 23 1315 24 1270 25 042K Tap T1 1375 23 1345 23 1310 24 1275 25 1240 25 1205 26 1160 27 1120 28 Tap T2 1470 21 1435 22 ...

Страница 12: ...s en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See installati...

Страница 13: ... conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner Single Phase NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150 V to ground 4 For replacement wires use conductors suitable for 105 C 5 See...

Страница 14: ...14 ...

Страница 15: ...15 ...

Страница 16: ...ty correct YES NO Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO Rated Voltage __________________________________________________________________ VOLTS L1 L2 Volts ____________________________________________________________________ VOLTS INSTALLATION ADDRESS CITY__________________________________________ STATE_...

Отзывы: