Reznor, FSE, Installation Manual, EN 2020-02, D301160 Iss H
Model
FSE 40
FSE 60
FSE 75
FSE 100 FSE 145 FSE 175 FSE 225 FSE 300
Øi mm
115
145
145
165
165
165
165
200
L mm
90
90
90
120
120
120
120
125
Table 6 – Burner opening dimensions
Figure 12 Correct burner position
Figure 13 Incorrect burner position
Burner position
The burner must conform to the local
standards and legislations in place. The
RIELLO-burner has been designed to
operate in the position shown in Figure 11,
The positions shown in Figure 12, will not
allow the air damper to close when the
burner is on standby.
Gas Installation/
connection
WARNING
The installation must be purged
and tested for soundness prior to
commissioning.
Always ensure that appropriate
personal protective equipment is
used
Service pipework must terminate at an
approved isolating valve, and be adjacent to
the position of the heater. The connection
to the heater can be made by way of either
an approved flexible coupling, or rigid
connection. Threaded connections must
comply with ISO288/1 of ISO 7/1, further
information concerning the accepted
practice in European countries is detailed
in EN 1020. The diameter of the pipework
from the isolating valve to the burner
connection must not be less than the
diameter of the burner connection inlet.