PAGE 44 Reznor, FSE, Installation Manual, EN 2020-02, D301160 Iss H
Information requirements for warm air heaters Commission Regulation (EU) 2018
B1 warm air heater:
[NO]
C2 warm air heater:
[NO]
C4 warm air heater:
[NO]
Type of fuel:
Propane Gas
Model:
FSE
FSE40
P
FSE60
P
FSE75
P
FSE100
P
FSE145
P
FSE175
P
FSE225
P
FSE300
P
Item:
Symbol
Units
Capacity:
Rated heating capacity:
Prated,h
[kW]
38.4
57.4
67.5
98.2
139.6
176.51
222.95
294.61
Minimum capacity:
Pmin
[kW]
27.9
38.9
52.3
67.3
98.7
124.25
156.04
227.02
Electric power consumption:
At rated heating capacity:
elmax
[kW]
0.183
0.195
0.197
0.403
0.408
0.43
0.53
0.598
At minimal capacity:
elmin
[kW]
0.156
0.164
0.17
0.371
0.38
0.375
0.53
0.565
In standby mode:
elsb
[kW]
0.003
0.003
0.003
0.003
0.003
0.003
0.003
0.003
Useful efficiency:
Useful efficiency at rated
heating capacity:
ƞ
nom
[%]
82%
84%
82%
82%
81%
83%
82%
82%
Useful efficiency at minimum
capacity:
ƞ
pl
[%]
85%
87%
85%
86%
85%
87%
87%
85%
Other items:
Envelope loss factor:
Fenv
[%]
0.0
0.0
0.0
0.0
0.0
0
0
0
Flame consumption:
Pign
[kW]
0.0
0.0
0.0
0.0
0.0
0.00
0.00
0.00
Emissions of nitrogen oxides
[input energy (GCV)]:
NOx
[mg/
kWh]
84
96
99
89
98
90
97
96
Emission efficiency:
ƞ
s,flow
[%]
91%
91%
91%
91%
90%
90%
91%
90%
ErP seasonal space heating
energy efficiency:
ƞ
s
[%]
73%
75%
72%
73%
72%
74%
74%
72%
Thermal efficiency at rated
heating capacity [NCV]:
ƞ
[%]
89%
91%
90%
89%
88%
91%
90%
90%
ErP Data chart propane gas