background image

 Reznor, FSE, Installation Manual, EN 2020-02, D301160 Iss H

consequences of any operations carried 
out and not specifically provided for or for 
translations open to misinterpretation.

The electrical system must feature suitable 
individual and independent electrical 
protection for each appliance which, in 
case of accidental failure, will be activated 
on the single appliance without prejudice 
to the proper operation of the other units 
present on the installation.

Note: 

The appliance is designed to be operated 
with the heating capacity and the air flow 
rate specified in the Data Sheet. If the 
heating capacity is too low and/or the air 
flow rate is too high, combustion products 
may condensate, resulting in the irreparable 
corrosion of the heat exchanger. If the 
heating capacity is too high and/ or the air 
flow rate is too low, overheating of the 
heat exchanger may occur, resulting in the  
activation of the high temperature safety 
devices and could cause damage to the 
exchanger

Disposal instructions

Disposing of the appliance must be done by 
an authorised company and in compliance 
with  the applicable laws. Before taking 
waste to Authorised Collection Centres, 
dismantle and separate the various 
materials that compose it which in 
summary are: 

•  Ferrous materials
•  Aluminium and copper
•  Electrical wiring
•  Seals and insulating materials
•  Plastic materials
•  Electronic cards

Compliance notices

•  The heater range detailed herewith 

are manufactured within a strictly 
controlled  quality environment within 
the parameters of ISO 9001.

These instructions are only valid if the 
following country code is on the appliance 
GB. IE. If this code is not present on the 
appliance, it is necessary to refer to the 
technical instructions which will provide 
the necessary information concerning 
the modification of the appliance to the 
conditions of use for the country. 

The manufacturer has taken reasonable and 
practical steps to ensure that all heaters are 
safe and without risk when properly used. 
These heaters should therefore only be used 
in the manner and purpose for which they 
were intended, and in accordance with the 
recommendations detailed herewith. The 
manufacturer supports all new products 
being supplied to their customers with 
a comprehensive information pack; this 
clearly defines mandatory instructions for 
the safe installation, use, and maintenance, 
of the appliance(s). 

Where proprietary items are incorporated 
into any of the heaters, detailed 
information and instructions are also 
provided as part of the information pack. It 
is the responsibility of the installer, owner, 
user, or hirer of the heater to ensure that 
they are familiar with the appropriate 
information/manuals supplied by the 
manufacturer and the safety instructions. In 
addition, operators must be suitably trained 
in the use of the appliance so as to ensure 
its continued safe and efficient use.

The manufacturer has a commitment to 
continuous improvement and therefore 
reserve the right to amend or change the 
specification of Warm Air Heater subject to 
compliance with the appropriate European, 
national and local regulations

Содержание Reznor FSE 100

Страница 1: ...oning and or servicing Leave it with the end user site agent to be placed in their premises technical file after installation WARNING Improper installation adjustment alteration service or maintenance...

Страница 2: ......

Страница 3: ...Air intake and supply ducted units only 20 Burner position 21 Gas Installation connection 21 Oil Installation connection 23 Storage tank 23 Pipe work and fittings 25 Burner technical details 27 Elect...

Страница 4: ...ired cabinet heaters are suitable for use with Natural Gas G20 most units can also be specified for Propane G31 Oil fired cabinet heaters are suitable for use with Class D gas oil 35 sec most units ca...

Страница 5: ...n adjustment alteration service or maintenance can cause property damage injury or death Read the installation operation and maintenance instructions thoroughly before installing or servicing this equ...

Страница 6: ...elocities may affect burner operation Suitable protection should be provided for the appliance when it is located in a position where it may be susceptible to external mechanical damage for example fo...

Страница 7: ...rical supply must not be switched off or disconnected as a method for stopping the heater the exception to this is in an emergency or during servicing where the heat exchanger has been given sufficien...

Страница 8: ...the appliance is to remain unused for long periods it is recommended that the following operations are carried out Turn the appliances electrical supply off via the local isolator Close the main fuel...

Страница 9: ...hin a strictly controlled quality environment within the parameters of ISO 9001 These instructions are only valid if the following country code is on the appliance GB IE If this code is not present on...

Страница 10: ...EU 2016 2281 Gas Appliance Regulations EU 2016 426 Warranty The heater is supplied with a 1 year parts and labour warranty and a further year on all parts excluding consumables The warranty commences...

Страница 11: ...charged and a credit supplied upon subsequent validation of the warranty claim Consumable items are specifically not included within the scope of the warranty Note Notification is required the immedia...

Страница 12: ...upply pre calibrated and electrically connected in the factory with the following functions FAN function FAN thermostat calibration 25 35 C Activates the fans max 60 seconds after the burner has start...

Страница 13: ...nce infill panels Burner casing Structure Legend 1 Secondary heat exchangers 2 Combustion chamber 3 Rear flue manifold 4 Front flue manifold 5 Heat exchanger inspection door 6 Flue connection 7 Burner...

Страница 14: ...Net weight Flue mm Flue nom FSE 40 600 770 1500 145 130 5 FSE 60 650 950 1650 225 150 6 FSE 75 650 950 1650 245 150 6 FSE 100 800 1200 1900 310 180 7 FSE 145 800 1200 1900 345 180 7 FSE 175 1000 1500...

Страница 15: ...al gas G20 consumption m h 4 6 6 7 8 0 11 6 16 7 20 6 26 2 34 7 Nominal inlet pressure G31 LPG gas mbar 37 Nominal inlet pressure G31 NL LPG gas mbar 30 LPG gas G31 consumption litres 6 8 9 8 11 3 17...

Страница 16: ...ature 1 C 155 155 170 185 195 145 145 155 Kerosene 28 sec consumption kg h 3 6 4 8 6 2 8 9 12 4 16 0 18 7 26 1 Model FSE 40 FSE 60 FSE 75 FSE 100 FSE 145 FSE 175 FSE 225 FSE 300 Fan thermostat calibra...

Страница 17: ...H3 ll2H3P MT I3B P I3P DE II2ELL3B P NL II2L3P DK II2H3B P NO I3P EE II2H3B P PL II2E3PB P ES II2H3 PT PT II2H3 FI II2H3B P RO RO II2H3B P II2H3P FR II2ER3P SE II2H3B P GB II2H3P YES II2H3B P ll2H3P G...

Страница 18: ...ations All heaters are supplied fused and pre wired all must be earthed Final connections for any additional external controls must be completed on site and must be carried out according to local and...

Страница 19: ...to the heater tripping on high limit Should this occur please reset the limit device and gradually open nozzles until the heater no longer trips Please note that fully closing the louvres on the nozzl...

Страница 20: ...surface whose deflection and strength is such that it can prevent vibrations from reaching underneath Respect the clearance distances in order to allow for a correct flow of air and normal cleaning an...

Страница 21: ...the unit Remove blocks before start up Safety area The unit must be easily and safely accessible without the need for special equipment ladders mobile platforms etc It is important to keep at least th...

Страница 22: ...e setting for the room Fuel connection The heater should be connected to the fuel supply by a qualified engineer only complying with the relevant regulations As far as gas burners are concerned we sug...

Страница 23: ...connector of the heater or larger Avoid narrow bends and section reductions Having a trap to take and analyse the combustion products Anchoring the flue gas discharge pipe Having a proper end cover t...

Страница 24: ...uit to the side opening the appliance is set up for both right and left connections To change the air inlet side simply swap the grille and blanking panels around To attach an air inlet duct remove th...

Страница 25: ...ose when the burner is on standby Gas Installation connection WARNING The installation must be purged and tested for soundness prior to commissioning Always ensure that appropriate personal protective...

Страница 26: ...ctory Before installation check carefully that it matches to the appliance on which it will be mounted The position of the silicon tube must be such as to ensure an inclination between the pressure sw...

Страница 27: ...romote trouble free operating it is necessary that the oil within the storage tank and oil line does not fall below the cold filter plugging point cfpp in the UK and with class D fuel also referred to...

Страница 28: ...gravity feed may be used The draw off point for the supply to the burner must not be positioned any lower than 100mm above the bottom of the tank Where a return valve is fitted this must be tamper pr...

Страница 29: ...rt 1 All joints must be sealed properly if necessary using PTFE tape or other approved sealing media The pipe work must be effectively sealed so as to prevent the ingress of air The fire check valve m...

Страница 30: ...ate within the oil tank at the same level as the suction line in this case a non return valve is not required The return line should terminate within the oil tank at the same level as the suction line...

Страница 31: ...2 9 2 2 6 0 0 6 2 0 Measured CO2 9 4 8 9 9 1 9 3 9 5 9 0 9 4 Measured CO ppm 1 14 3 3 2 32 30 Gas connections inch Rp 1 2 Rp 3 4 Rp 3 4 Rp 3 4 NOTE Head pressure is the differential pressure between...

Страница 32: ...0 7 50 12 50 Burner head position No 5 0 3 0 3 0 4 0 Air damper position No 1 0 3 0 1 5 3 8 40 0 80 0 40 0 85 0 Measured CO2 9 52 9 38 9 58 9 60 9 75 9 60 9 40 9 60 Measured CO ppm 1 5 1 0 3 3 0 0 Gas...

Страница 33: ...5 4 5 3 0 2 0 7 0 Pump pressure bar 8 0 10 0 7 0 10 0 11 0 11 0 7 0 11 0 Burner head position No 5 0 5 4 0 1 0 Air damper position No 0 7 2 0 0 8 3 0 0 5 6 0 40 0 70 0 Measured CO2 12 04 12 08 12 55...

Страница 34: ...ake sure that the direction of rotation of the fans is correct The unit must be connected to an efficient earthing system The manufacturer shall not be held responsible for any damage caused by failur...

Страница 35: ...inals shown may not be in numerical order Unused terminals may not be shown at all 900688 FSE Control Interconnections NEUTRAL LIVE 1 Phase 230v 50Hz L N 1 Phase Permanent Mains Supply 3 Phase 400v 50...

Страница 36: ...l be disposed of before the fan stops TR safety thermostat The appliance is equipped with an automatic reset TR safety thermostat with the element positioned on the air supply It has the function of s...

Страница 37: ...ions as standard Begin by checking when the burner is operating on the nominal thermal output the temperature rise between the air outlet and inlet temperature and compare with the specifications of T...

Страница 38: ...t is shipped from the factory connected at the minimum speed which corresponds to the nominal air flow without residual useful static pressure if it is necessary to increase its performance simply con...

Страница 39: ...d in the heat exchanger may cause dangerous overheating situations with possible damage to the air heater Moreover the LIMIT thermostat could be triggered and it might be necessary to release it manua...

Страница 40: ...t exchanger for condensation This check should be performed by turning off the burner after half an hour of continuous use checking simultaneously through the flue connection if there is any trace of...

Страница 41: ...itch off If long periods of unusual operation occur it is advisable to contact the manufacturer on how to restart operation Regularly check that all the screws used to assemble the heater are properly...

Страница 42: ...ations Disconnect the flue Open the inspection door 3 Remove inspection door with flue connection 4 Remove the burner 1 Remove the panel 2 Remove the panel 5 Remove the inspection door 6 Remove turbul...

Страница 43: ...ntrol type supplied Refer to individual controller operating manual The burner will turn off The fan will continue to run until heat dissipation allows the fan and limit thermostat to shut down the fa...

Страница 44: ...854 30 07 854 30 078 54 30 07 854 30 07 854 Fire valve 28 30 102 28 30 102 28 30 102 28 30 102 28 30 102 Oil filter 29 15 017 29 15 017 29 15 017 29 15 017 29 15 012 Table 15b Parts list FSE 40 100 BU...

Страница 45: ...2 Pulley taper bush 2012 30 FSE 1 1 2 2 2 1801095 Pulley B212 FSE 1 2 1801546 Pulley variable 121 FSE 2 1801147 Pulley taper bush 1108 24 FSE 2 1801543 Pulley B236 FSE 2 2 1030162 Relay Finder 40 52 8...

Страница 46: ...PAGE 42 Reznor FSE Installation Manual EN 2020 02 D301160 Iss H...

Страница 47: ...lmax kW 0 183 0 195 0 197 0 403 0 408 0 43 0 53 0 598 At minimal capacity elmin kW 0 156 0 164 0 17 0 371 0 38 0 375 0 53 0 565 In standby mode elsb kW 0 003 0 003 0 003 0 003 0 003 0 003 0 003 0 003...

Страница 48: ...0 197 0 403 0 408 0 43 0 53 0 598 At minimal capacity elmin kW 0 156 0 164 0 17 0 371 0 38 0 375 0 53 0 565 In standby mode elsb kW 0 003 0 003 0 003 0 003 0 003 0 003 0 003 0 003 Useful efficiency U...

Страница 49: ...405 0 405 0 43 0 53 0 53 At minimal capacity elmin kW 0 247 0 175 0 176 0 396 0 396 0 375 0 53 0 53 In standby mode elsb kW 0 003 0 003 0 003 0 003 0 003 0 003 0 003 0 003 Useful efficiency Useful ef...

Страница 50: ...405 0 405 0 45 0 439 0 53 At minimal capacity elmin kW 0 247 0 175 0 176 0 396 0 396 0 409 0 4 0 53 In standby mode elsb kW 0 003 0 003 0 003 0 003 0 003 0 003 0 003 0 003 Useful efficiency Useful ef...

Страница 51: ......

Страница 52: ......

Страница 53: ...C is a registered trademark of the Nortek Global HVAC limited Because of the continuous product innovation Nortek Global HVAC reserves the right to change product specification without due notice This...

Отзывы: