Nortek R6GF Series Скачать руководство пользователя страница 5

5

GENERAL INFORMATION

This single package gas heating / electric cooling unit is designed 

only for outdoor rooftop or ground level slab installations and 

can be readily connected to the high static duct system of a 

home. This unit has been tested for capacity and efficiency 

in accordance with AHRI standards and will provide many 

years of safe and dependable comfort, providing it is properly 

installed and maintained. With regular maintenance, this unit 

will operate satisfactorily year after year. Abuse, improper 

use, and/or improper maintenance can shorten the life of the 

appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment 

failure, it is recommended that periodic maintenance be 

performed on this unit. The ability to properly perform 

maintenance on this equipment requires certain tools and 

mechanical skills.

Before you install this unit

  The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. It is 

recommended that the area to be conditioned be completely 

insulated and vapor sealed.

  Check the electrical supply and verify the power supply is 

adequate for unit operation. Consideration should be given 

to availability of electric power, service access, noise, and 

shade. If there is any question concerning the power supply, 

contact the local power company.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage prior 

to installing the equipment at the job site. Verify coil fins are 

straight. If necessary, comb fins to remove flattened or bent 

fins. Claims for damage (apparent or concealed) should be 

filed immediately with the carrier.

  Please consult your dealer for maintenance information and 

availability of maintenance contracts. Read all instructions 
before installing the unit.

Locating the Equipment

•  Clearance in accordance with local installation codes, the 

requirements of the gas supplier and the manufacturer’s 

installation instructions.

•  Dégaugement conforme aux codes d’installation locaux, 

aux exigences du fournisseur de gaz et aux instructions 

d’installation du fabricant.

•  A clearance of at least 36 inches from the blower access panel 

and from the louvered control access panel is recommended 

for servicing and maintenance. 

Where accessibility 

clearances are greater than clearances to combustibles, 

accessibility clearances must take preference.

•  Select a solid, level position, preferably on a concrete slab, 

slightly above the grade level, and parallel to the home. 

DO 

NOT PLACE UNIT UNDER THE HOME.

•  Overhead obstructions, poorly ventilated areas, and areas 

subject to accumulation of debris should be avoided. Do not 

place the unit in a confined space or recessed area where 

discharge air from the unit could re-circulate back through 

the condenser coil.

•  Survey the job site to determine the best location for the 

packaged unit. The unit should be located with consideration 

of minimizing the length of the supply and return ducts. 

Consideration should also be given to the accessibility of 

fuel, electric power, service access, noise, and shade.

•  Sufficient clearance for unobstructed airflow through the 

louvered control access panel and outdoor coil must be 

maintained in order to achieve rated performance. See 

Figure 1

 for minimum clearance requirements.

•  The hot condenser air must be discharged up and away 

from the home.

•  If practical, place the air conditioner and its ducts in an area 

where they will be shaded from the afternoon sun, when the 

heat load is greatest.

Heating Load

This unit should be sized to provide the design heating load 

requirement. Heating load estimates can be made using 

approved methods available from Air Conditioning Contractors of 

America (Manual J); American Society of Heating, Refrigerating, 

and Air Conditioning Engineers; or other approved engineering 

methods. For installations above 2,000 ft., the unit should have 

a sea level input rating large enough that it will meet the heating 

load after deration for altitude.

Minimum Required 

Clearances to Combustibles

36"

36"

36"

TOP OF UNIT

TO

 BE

UNOBSTR

UCTED

See Note 1

See Note 2

NOTE 1:

 6” When coil is present on duct side.

NOTE 2:

 1” When no coil is present on duct side.

Figure 1. Clearance Requirements

Содержание R6GF Series

Страница 1: ...plier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Ne pas entreposer ni utiliser de l essence ni d autres vapeurs ou...

Страница 2: ...ion 17 System Cooling 17 System Heating 17 Verifying Adjusting Temperature Rise 17 Verifying Adjusting Firing Rate 18 Verifying Over Temperature Limit Control Operation 18 Verifying Burner Operation 1...

Страница 3: ...g is required If repairs make it necessary for evacuationandcharging itshouldonlybeattempted by qualified trained personnel thoroughly familiar with this equipment Some local codes require licensed in...

Страница 4: ...ctions and all applicable local codes Install this unit only in a location and position as specified on page 7 This unit is designed only for outdoor installations and should be located with considera...

Страница 5: ...D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d installation du fabricant Aclearanceofatleast36inchesfromthebloweraccesspanel andfromthe...

Страница 6: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes doivent t...

Страница 7: ...fault condition If this control must be replaced use only factory authorized replacement parts See the list of Replacement Parts on page 21 Vent Termination This unit has been equipped with an integr...

Страница 8: ...gned so that the return air to the unit is not less than 50 F 10 C during heating operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the...

Страница 9: ...g enough to support the unit s weight The slab height must be a minimum of 2 5cm above grade and with adequate drainage See Figure 3 Remove and discard the horizontal supply and return duct covers loc...

Страница 10: ...lectrique au g n rateur d air chaud avant de prod der aux travaux d entretein Au moment de l entretien des commandes tiquetez tous les fils avant de les d brancher S assurer de les raccorder correctem...

Страница 11: ...rdancewith the instructions supplied with the thermostat and the indoor equipment These units use a special 2 speed compressor to achieve a high level of efficiency in a compact frame A 2 stage coolin...

Страница 12: ...r system options With the blower installed and configured properly the furnace will gradually change speed in response to changes in system variables such as thermostat settings duct static filters et...

Страница 13: ...noid damage from overheating conditions L Terminal Wiring White RodgersCompatibleThermostats TheLconnection is used to communicate Comfort Alert codes to compatible White Rodgersthermostats TheLtermin...

Страница 14: ...al Electrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided in the control box for grounding the unit GAS SUPPLY PIPING WARNING FIRE OR EXPLOSION HAZARD Failure to...

Страница 15: ...ectors A soap and water solution can be applied on each joint or union using a small paintbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the t...

Страница 16: ...al Gas R6GF X24K080XB R6GF X36K100XB MANIFOLD PRESSURE FOR NATURAL GAS INSTALLATIONS IN W C ALTITUDE ABOVE SEA LEVEL HEATING VALUE BTU CU FT ORIFICE SIZE 800 TO 899 FT 900 TO 999 FT 1 000 TO 1 100 FT...

Страница 17: ...perly after 1 2 minutes lower the thermostat temperature set point an additional 3 4 degrees until the cooling system moves into 2nd stage or high cool operating mode The compressor and indoor blower...

Страница 18: ...operating sequence page 19 NOTE The over temperature limit control should turn off the gas valve within approximately four minutes exact time depends on the efficiency of the close off when blocking t...

Страница 19: ...on step 6 begins If no flame is sensed on the fifth try for ignition the furnace control is locked and the red LED will flash 4 times repetitively The thermostat must be opened for at least ten second...

Страница 20: ...eginning of each heating and cooling season or more frequently if required Inspectthecondensatedrainandoutdoorcoilatthebeginning of each cooling season Remove any debris Clean the outdoorcoilandlouver...

Страница 21: ...ches separate the ground joint union in the gas supply piping at the unit 7 Remove the piping between the gas valve and the ground joint union if applicable 8 Remove all screws securing the burner ass...

Страница 22: ...Speed Blower call OFF SYSTEM STATUS CFM LED STATUS YELLOW NOT USED OFF automatically opens and regulates the gas pressure in the manifold See Figure 8 page 18 Over Temperature Limit Control The over t...

Страница 23: ...rizontal Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 Unit Dimensions Table 8 Center of Gravity Unit Shipping Weights MODE...

Страница 24: ...ormal 1170 Normal 1700 10 990 10 1290 10 1870 TAP C 10 900 TAP C 10 1140 TAP C 10 1620 Normal 1000 Normal 1270 Normal 1800 10 1100 10 1400 10 1980 TAP D 10 1080 TAP D 10 1260 TAP D 10 Normal 1200 Norm...

Страница 25: ...9 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 327 112 32 161...

Страница 26: ...compagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais utiliser...

Страница 27: ...UNIT CONTROL BOARD W1 W2 C R G Y Y2 0 DEHUM P2 1 5 HUM LINE XMFR CONT EAC COOL PARK1 PARK2 HI HEAT LO HEAT NEUTRALS AUTO HEAT STAGE 10 5 NONE HOT SURFACE IGNITION VARIABLE SPEED BLOWER CONTROL BOARD C...

Страница 28: ...208 230 Volt Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIAGRAM NOTES 1 Disconnect power before servicing 2 For supply connections use copper conductors only...

Страница 29: ...Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIAGRAM NOTES 1 Disconnect power before servicing 2 For supply connections use copper conductors only 3 Not suitabl...

Страница 30: ...fective Condenser coil is dirty Liquid line restriction filter drier blocked if present in system Thermostat is malfunctioning Solenoid plug not connected Y2 not wired at Comfort Alert Check thermosta...

Страница 31: ...s flashing at same time means control circuit voltage is too low for operation Table 14 LED Diagnostics Continued Table 15 Module Wiring Troubleshooting MISWIRED MODULE INDICATION RECOMMENDED TROUBLES...

Страница 32: ...repeat steps 1 through 3 until the system is correctly charged Charging Charts Application Notes This equipments cooling system contains refrigerant under high pressure always use safe practices when...

Страница 33: ...igerant when below curve Remove refrigerant when above curve Figure 15 Charging Chart for 2 Ton Units Figure 16 Charging Chart for 3 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X36 Chargi...

Страница 34: ...igerant when below curve Remove refrigerant when above curve Figure 18 Charging Chart for 5 Ton Units Figure 17 Charging Chart for 4 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X48 Chargi...

Страница 35: ...35...

Страница 36: ...nit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO Rated Voltage VOLTS L1 L2 Volts __________________________________________________________________...

Отзывы: