Nortek R6GF Series Скачать руководство пользователя страница 18

18

IN

ON

OFF

Inlet

Pressure

Tap

Inlet

Pressure

Tap

Manifold

pressure

Tap

Manifold

pressure

Tap

2-STAGE GAS VALVES

Model VR8205Q2381

Model VR9205Q1028

ON / OFF

Knob

ON / OFF

Switch

HI Input 

Adjusting

Screw

Lo Input 

Adjusting

Screw

HI Input

Adjusting

Screw

Lo Input 

Adjusting

Screw

Figure 8. HI & LO Input Adjusting Screws

Verifying & Adjusting Firing Rate

 CAUTION:

Do not re-drill the burner orifices. If the orifice size 

must be changed, use only new orifices.

The firing rate must be verified for each installation to prevent 

over-firing of the furnace. 

The firing rate must not exceed 

the rate shown on the unit data label. 

To determine the firing 

rate, follow the steps below:

1. Obtain the gas heating value (HHV) from the gas supplier.

2. Shut off all other gas fired appliances.

3. Start the unit in heating mode and allow it to run for at least 

3 minutes.

4. Measure the time (in seconds) required for the gas meter to 

complete one revolution.

5. Convert the time per revolution to cubic feet of gas per hour 

using 

Table 13 (page 25)

.

6. Multiply the gas flow rate in cubic feet per hour by the heating 

value of the gas in Btu per cubic foot to obtain the firing rate 

in Btu per hour. See Example.

Example

:

•  Time for 1 revolution of a gas meter with a 1 cubic foot 

dial = 40 seconds.

• From 

Table 13

, read 90 cubic feet gas per hour.

•  Local heating value of the gas (obtained from gas supplier) 

= 1,040 Btu per cubic foot.

•  Input rate = 1,040 x 90 = 93,600 Btuh.

7. Adjust the manifold pressure if necessary. See 

page  18

For additional information about elevations above 2,000 feet, 
see 

page 15

.

Verifying Over-Temperature Limit Control 
Operation

1. Verify the louvered control access panel is in place and that 

there is power to the unit.

2. Block the return airflow to the unit by installing a close-off 

plate in place of or upstream of the filter.

3. Set the thermostat above room temperature and verify the 

units operating sequence (

page 19

).

 NOTE:

 The over-temperature limit control should turn off 

the gas valve within approximately four minutes (exact time 

depends on the efficiency of the close-off when blocking the 

return air). The circulating air and combustion blowers should 

continue to run when the over-temperature limit control switch 

opens.

4. Remove the close-off plate immediately after the over-

temperature limit control opens. If the unit operates for more 

than four minutes with no return air, set the thermostat below 

room temperature, shut off power to the unit, and replace 
the over-temperature limit control.

Verifying Burner Operation

 WARNING:

Uninsulated live components are exposed when 

louvered control access panel is removed.

1.  Remove the louvered control access panel and verify there 

is power to the unit.

2. Set thermostat above room temperature and observe the 

ignition sequence. 

NOTE:

 The burner flame should carry over 

immediately between all burners without lifting off, curling, 

or floating. The flames should be blue, without yellow tips. 

Make sure the flame is drawn into the center of the heat 

exchanger tube. In a properly adjusted burner assembly, 

the flame bends down and to the right at the end of the heat 

exchanger tube. The end of the flame will be out of sight 

around the bend.

3.  After validating flame characteristics, set the thermostat below 

room temperature and verify the burner flame extinguishes 

completely.

Manifold Pressure Adjustment

The manifold pressure must be set to the appropriate value for 

your installation. To adjust the manifold pressure:
1. Obtain the required manifold pressure setting. Use 

Table 

5 (page 16)

 for natural gas or 

Table 6 (page 16)

 for 

LP/propane gas. 

NOTE:

 The values listed in the tables are 

based on sea level values. At higher altitudes, the heating 

value of gas is lower than the sea level heating value.

2.  Remove the regulator cap. Turn the high fire adjusting screw 

clockwise to increase the pressure or counterclockwise 
to reduce the pressure. See 

Figure 8

 for adjusting screw 

locations.

3. Replace the regulator cap after adjustments are complete.

Содержание R6GF Series

Страница 1: ...plier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Ne pas entreposer ni utiliser de l essence ni d autres vapeurs ou...

Страница 2: ...ion 17 System Cooling 17 System Heating 17 Verifying Adjusting Temperature Rise 17 Verifying Adjusting Firing Rate 18 Verifying Over Temperature Limit Control Operation 18 Verifying Burner Operation 1...

Страница 3: ...g is required If repairs make it necessary for evacuationandcharging itshouldonlybeattempted by qualified trained personnel thoroughly familiar with this equipment Some local codes require licensed in...

Страница 4: ...ctions and all applicable local codes Install this unit only in a location and position as specified on page 7 This unit is designed only for outdoor installations and should be located with considera...

Страница 5: ...D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d installation du fabricant Aclearanceofatleast36inchesfromthebloweraccesspanel andfromthe...

Страница 6: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes doivent t...

Страница 7: ...fault condition If this control must be replaced use only factory authorized replacement parts See the list of Replacement Parts on page 21 Vent Termination This unit has been equipped with an integr...

Страница 8: ...gned so that the return air to the unit is not less than 50 F 10 C during heating operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the...

Страница 9: ...g enough to support the unit s weight The slab height must be a minimum of 2 5cm above grade and with adequate drainage See Figure 3 Remove and discard the horizontal supply and return duct covers loc...

Страница 10: ...lectrique au g n rateur d air chaud avant de prod der aux travaux d entretein Au moment de l entretien des commandes tiquetez tous les fils avant de les d brancher S assurer de les raccorder correctem...

Страница 11: ...rdancewith the instructions supplied with the thermostat and the indoor equipment These units use a special 2 speed compressor to achieve a high level of efficiency in a compact frame A 2 stage coolin...

Страница 12: ...r system options With the blower installed and configured properly the furnace will gradually change speed in response to changes in system variables such as thermostat settings duct static filters et...

Страница 13: ...noid damage from overheating conditions L Terminal Wiring White RodgersCompatibleThermostats TheLconnection is used to communicate Comfort Alert codes to compatible White Rodgersthermostats TheLtermin...

Страница 14: ...al Electrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided in the control box for grounding the unit GAS SUPPLY PIPING WARNING FIRE OR EXPLOSION HAZARD Failure to...

Страница 15: ...ectors A soap and water solution can be applied on each joint or union using a small paintbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the t...

Страница 16: ...al Gas R6GF X24K080XB R6GF X36K100XB MANIFOLD PRESSURE FOR NATURAL GAS INSTALLATIONS IN W C ALTITUDE ABOVE SEA LEVEL HEATING VALUE BTU CU FT ORIFICE SIZE 800 TO 899 FT 900 TO 999 FT 1 000 TO 1 100 FT...

Страница 17: ...perly after 1 2 minutes lower the thermostat temperature set point an additional 3 4 degrees until the cooling system moves into 2nd stage or high cool operating mode The compressor and indoor blower...

Страница 18: ...operating sequence page 19 NOTE The over temperature limit control should turn off the gas valve within approximately four minutes exact time depends on the efficiency of the close off when blocking t...

Страница 19: ...on step 6 begins If no flame is sensed on the fifth try for ignition the furnace control is locked and the red LED will flash 4 times repetitively The thermostat must be opened for at least ten second...

Страница 20: ...eginning of each heating and cooling season or more frequently if required Inspectthecondensatedrainandoutdoorcoilatthebeginning of each cooling season Remove any debris Clean the outdoorcoilandlouver...

Страница 21: ...ches separate the ground joint union in the gas supply piping at the unit 7 Remove the piping between the gas valve and the ground joint union if applicable 8 Remove all screws securing the burner ass...

Страница 22: ...Speed Blower call OFF SYSTEM STATUS CFM LED STATUS YELLOW NOT USED OFF automatically opens and regulates the gas pressure in the manifold See Figure 8 page 18 Over Temperature Limit Control The over t...

Страница 23: ...rizontal Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 Unit Dimensions Table 8 Center of Gravity Unit Shipping Weights MODE...

Страница 24: ...ormal 1170 Normal 1700 10 990 10 1290 10 1870 TAP C 10 900 TAP C 10 1140 TAP C 10 1620 Normal 1000 Normal 1270 Normal 1800 10 1100 10 1400 10 1980 TAP D 10 1080 TAP D 10 1260 TAP D 10 Normal 1200 Norm...

Страница 25: ...9 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 327 112 32 161...

Страница 26: ...compagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais utiliser...

Страница 27: ...UNIT CONTROL BOARD W1 W2 C R G Y Y2 0 DEHUM P2 1 5 HUM LINE XMFR CONT EAC COOL PARK1 PARK2 HI HEAT LO HEAT NEUTRALS AUTO HEAT STAGE 10 5 NONE HOT SURFACE IGNITION VARIABLE SPEED BLOWER CONTROL BOARD C...

Страница 28: ...208 230 Volt Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIAGRAM NOTES 1 Disconnect power before servicing 2 For supply connections use copper conductors only...

Страница 29: ...Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIAGRAM NOTES 1 Disconnect power before servicing 2 For supply connections use copper conductors only 3 Not suitabl...

Страница 30: ...fective Condenser coil is dirty Liquid line restriction filter drier blocked if present in system Thermostat is malfunctioning Solenoid plug not connected Y2 not wired at Comfort Alert Check thermosta...

Страница 31: ...s flashing at same time means control circuit voltage is too low for operation Table 14 LED Diagnostics Continued Table 15 Module Wiring Troubleshooting MISWIRED MODULE INDICATION RECOMMENDED TROUBLES...

Страница 32: ...repeat steps 1 through 3 until the system is correctly charged Charging Charts Application Notes This equipments cooling system contains refrigerant under high pressure always use safe practices when...

Страница 33: ...igerant when below curve Remove refrigerant when above curve Figure 15 Charging Chart for 2 Ton Units Figure 16 Charging Chart for 3 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X36 Chargi...

Страница 34: ...igerant when below curve Remove refrigerant when above curve Figure 18 Charging Chart for 5 Ton Units Figure 17 Charging Chart for 4 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X48 Chargi...

Страница 35: ...35...

Страница 36: ...nit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO Rated Voltage VOLTS L1 L2 Volts __________________________________________________________________...

Отзывы: