Airflow Data

Table 9. Nominal Airflow Rates & Temperature Rises (° F)

MODEL

NUMBER

HEATING

INPUT

(BTUH)

HEATING

OUTPUT

(BTUH)

CFM

RANGE

HEATING

RISE RANGE

(° F)

COOLING

OUTPUT

(BTUH)

BLOWER

SIZE

MOTOR

(HP)

X24K080XB

80,000

64,800

1100 - 1350

35-65

24,000

10 X 10

 1/2

52,000

42,120

750 - 1050

X36K100XB

100,000

81,000

1100 - 1400

40-70

35,200

10 X 10

 1/2

65,000

52,650

950 - 1100

X48K120XB

120,000

97,200

1500 - 2000

40-70

47,000

11 X 10

78,000

63,180

950 - 1250

X60K120XB

120,000

97,200

1500 - 2000

40-70

55,500

11 X 10

78,000

63,180

950 - 1250

NOTE:

 CFM and Rise are independent of ESP in a variable speed blower.

Table 10. Airflow Settings for Cooling

2 TON UNITS

3 TON UNITS

4 - 5 TON UNITS

BLOWER

SELECTOR

SETTING

RECOMMENDED

A/C AIRFLOW

RATE (CFM)

BLOWER

SELECTOR

SETTING

RECOMMENDED

A/C AIRFLOW

RATE (CFM)

BLOWER

SELECTOR

SETTING

RECOMMENDED

A/C AIRFLOW

RATE (CFM)

COOL

ADJUST

COOL

ADJUST

COOL

ADJUST

TAP “A”

-10%

2

T

O

N

720

TAP “A”

-10%

875

TAP “A”

-10%

4

T

O

N

1440

Normal

800

Normal

3

T

O

N

970

Normal

5

T

O

N

1600

+10%

880

+10%

1065

+10%

1760

TAP “B”

-10%

810

TAP “B”

-10%

1050

TAP “B”

-10%

1530

Normal

900

Normal

1170

Normal

1700

+10%

990

+10%

1290

+10%

1870

TAP “C”

-10%

900

TAP “C”

-10%

1140

TAP “C”

-10%

1620

Normal

1000

Normal

1270

Normal

1800

+10%

1100

+10%

1400

+10%

1980

TAP “D”

-10%

1080

TAP “D”

-10%

1260

TAP “D”

-10%

Normal

1200

Normal

1400

Normal

+10%

1320

+10%

1540

+10%

Table 11. Airflow Settings (CFM) & Rise (° F) for Heating

BLOWER

HEAT

SELECTOR

SETTING

2 TON

3 TON

4 & 5 TON

LOW INPUT

HIGH INPUT

LOW INPUT

HIGH INPUT

LOW INPUT

HIGH INPUT

52,000

80,000

65,000

100,000

78,000

120,000

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

TAP “A”

750

51

1100

54

950

51

1100

69

950

61

1500

61

TAP “B”

850

44

1150

53

1000

48

1200

63

1050

55

1700

54

TAP “C”

950

41

1250

47

1050

46

1300

58

1150

50

1800

51

TAP “D”

NOTES:

1. Recommended temperature rises are highlighted in BOLD. Use of any other setting may result in nuisance trips.

2. Temperature rises in the table are approximate. Actual temperature rises may vary.

3. Blower “ADJUST” tap non-functional in Heating mode.

4. To comply with government mandated efficiency standards, two openings are required for airflows above 1,600 CFM.

5. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.

6. To comply with government mandated efficiency standards, speed settings which do not have data are not allowed in heat and cooling mode.

Содержание R6GF Series

Страница 1: ...plier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Ne pas entreposer ni utiliser de l essence ni d autres vapeurs ou...

Страница 2: ...ion 17 System Cooling 17 System Heating 17 Verifying Adjusting Temperature Rise 17 Verifying Adjusting Firing Rate 18 Verifying Over Temperature Limit Control Operation 18 Verifying Burner Operation 1...

Страница 3: ...g is required If repairs make it necessary for evacuationandcharging itshouldonlybeattempted by qualified trained personnel thoroughly familiar with this equipment Some local codes require licensed in...

Страница 4: ...ctions and all applicable local codes Install this unit only in a location and position as specified on page 7 This unit is designed only for outdoor installations and should be located with considera...

Страница 5: ...D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d installation du fabricant Aclearanceofatleast36inchesfromthebloweraccesspanel andfromthe...

Страница 6: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes doivent t...

Страница 7: ...fault condition If this control must be replaced use only factory authorized replacement parts See the list of Replacement Parts on page 21 Vent Termination This unit has been equipped with an integr...

Страница 8: ...gned so that the return air to the unit is not less than 50 F 10 C during heating operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the...

Страница 9: ...g enough to support the unit s weight The slab height must be a minimum of 2 5cm above grade and with adequate drainage See Figure 3 Remove and discard the horizontal supply and return duct covers loc...

Страница 10: ...lectrique au g n rateur d air chaud avant de prod der aux travaux d entretein Au moment de l entretien des commandes tiquetez tous les fils avant de les d brancher S assurer de les raccorder correctem...

Страница 11: ...rdancewith the instructions supplied with the thermostat and the indoor equipment These units use a special 2 speed compressor to achieve a high level of efficiency in a compact frame A 2 stage coolin...

Страница 12: ...r system options With the blower installed and configured properly the furnace will gradually change speed in response to changes in system variables such as thermostat settings duct static filters et...

Страница 13: ...noid damage from overheating conditions L Terminal Wiring White RodgersCompatibleThermostats TheLconnection is used to communicate Comfort Alert codes to compatible White Rodgersthermostats TheLtermin...

Страница 14: ...al Electrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided in the control box for grounding the unit GAS SUPPLY PIPING WARNING FIRE OR EXPLOSION HAZARD Failure to...

Страница 15: ...ectors A soap and water solution can be applied on each joint or union using a small paintbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the t...

Страница 16: ...al Gas R6GF X24K080XB R6GF X36K100XB MANIFOLD PRESSURE FOR NATURAL GAS INSTALLATIONS IN W C ALTITUDE ABOVE SEA LEVEL HEATING VALUE BTU CU FT ORIFICE SIZE 800 TO 899 FT 900 TO 999 FT 1 000 TO 1 100 FT...

Страница 17: ...perly after 1 2 minutes lower the thermostat temperature set point an additional 3 4 degrees until the cooling system moves into 2nd stage or high cool operating mode The compressor and indoor blower...

Страница 18: ...operating sequence page 19 NOTE The over temperature limit control should turn off the gas valve within approximately four minutes exact time depends on the efficiency of the close off when blocking t...

Страница 19: ...on step 6 begins If no flame is sensed on the fifth try for ignition the furnace control is locked and the red LED will flash 4 times repetitively The thermostat must be opened for at least ten second...

Страница 20: ...eginning of each heating and cooling season or more frequently if required Inspectthecondensatedrainandoutdoorcoilatthebeginning of each cooling season Remove any debris Clean the outdoorcoilandlouver...

Страница 21: ...ches separate the ground joint union in the gas supply piping at the unit 7 Remove the piping between the gas valve and the ground joint union if applicable 8 Remove all screws securing the burner ass...

Страница 22: ...Speed Blower call OFF SYSTEM STATUS CFM LED STATUS YELLOW NOT USED OFF automatically opens and regulates the gas pressure in the manifold See Figure 8 page 18 Over Temperature Limit Control The over t...

Страница 23: ...rizontal Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 Unit Dimensions Table 8 Center of Gravity Unit Shipping Weights MODE...

Страница 24: ...ormal 1170 Normal 1700 10 990 10 1290 10 1870 TAP C 10 900 TAP C 10 1140 TAP C 10 1620 Normal 1000 Normal 1270 Normal 1800 10 1100 10 1400 10 1980 TAP D 10 1080 TAP D 10 1260 TAP D 10 Normal 1200 Norm...

Страница 25: ...9 86 42 209 419 88 41 205 409 90 40 200 400 92 39 196 391 94 38 191 383 96 38 188 375 98 37 184 367 100 36 180 360 102 35 176 353 104 35 173 346 106 34 170 340 108 33 167 333 110 33 164 327 112 32 161...

Страница 26: ...compagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais utiliser...

Страница 27: ...UNIT CONTROL BOARD W1 W2 C R G Y Y2 0 DEHUM P2 1 5 HUM LINE XMFR CONT EAC COOL PARK1 PARK2 HI HEAT LO HEAT NEUTRALS AUTO HEAT STAGE 10 5 NONE HOT SURFACE IGNITION VARIABLE SPEED BLOWER CONTROL BOARD C...

Страница 28: ...208 230 Volt Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIAGRAM NOTES 1 Disconnect power before servicing 2 For supply connections use copper conductors only...

Страница 29: ...Single Phase Packaged Two Stage Heat Two Stage Electric Air Conditioner 60Hz WIRING DIAGRAM NOTES 1 Disconnect power before servicing 2 For supply connections use copper conductors only 3 Not suitabl...

Страница 30: ...fective Condenser coil is dirty Liquid line restriction filter drier blocked if present in system Thermostat is malfunctioning Solenoid plug not connected Y2 not wired at Comfort Alert Check thermosta...

Страница 31: ...s flashing at same time means control circuit voltage is too low for operation Table 14 LED Diagnostics Continued Table 15 Module Wiring Troubleshooting MISWIRED MODULE INDICATION RECOMMENDED TROUBLES...

Страница 32: ...repeat steps 1 through 3 until the system is correctly charged Charging Charts Application Notes This equipments cooling system contains refrigerant under high pressure always use safe practices when...

Страница 33: ...igerant when below curve Remove refrigerant when above curve Figure 15 Charging Chart for 2 Ton Units Figure 16 Charging Chart for 3 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X36 Chargi...

Страница 34: ...igerant when below curve Remove refrigerant when above curve Figure 18 Charging Chart for 5 Ton Units Figure 17 Charging Chart for 4 Ton Units Liquid Pressure psig Liquid Temperature F R6GF X48 Chargi...

Страница 35: ...35...

Страница 36: ...nit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO Rated Voltage VOLTS L1 L2 Volts __________________________________________________________________...

Отзывы: