background image

5

•  Duct work should be attached directly to the unit flanges 

for horizontal applications.

•  If roof curb is installed, the ducts must be attached to 

the curb hangers, not the unit.

Unconditioned Spaces

All duct work passing through unconditioned space must 

be properly insulated to minimize duct losses and prevent 

condensation. Use insulation with an outer vapor barrier. 

Refer to local codes for insulation material requirements.

Acoustical Duct Work

Certain installations may require the use of acoustical 

lining inside the supply duct work.

•  Acoustical insulation must be in accordance with the 

current revision of the Sheet Metal and Air Conditioning 

Contractors National Association (SMACNA) application 

standard for duct liners.

•  Duct lining must be UL classified batts or blankets with 

a fire hazard classification of FHC-25/50 or less.

•  Fiber duct work may be used in place of internal duct 

liners if the fiber duct work is in accordance with the 

current revision of the SMACNA construction standard 

on fibrous glass ducts. Fibrous duct work and internal 

acoustical lining must be NFPA Class 1 air ducts when 
tested per UL Standard 181 for Class 1 ducts.

air Filter requirements

 Warning:

never operate the unit without a filter in place. 

dust and lint could accumulate on internal parts, 

resulting in loss of efficiency, equipment damage 

and possible fire. replace disposable filters with 

the same type and size.

•  Air filter(s) are not supplied and must be installed in 

the unit or in the return air system by the installer. Only 

three phase units are equipped with an internal filter 

rack assembly.

•  If using an economizer or fresh air equipment, the factory 

installed filter rack must be removed prior to installation. 
See 

page 6

 for removal instructions.

•  All return air must pass through the filters before entering 

the unit. Recommended filter sizes are listed in 

Table 1

note:

 It is important that all filters be kept clean and 

replaced frequently to ensure proper operation of unit. 

Dirty or clogged filters will reduce the efficiency of the 

unit and result in unit shutdowns.

•  Air filter pressure drop must not exceed 0.08 inches 

WC. When replacing the air filters, a suitable air filter 

must be installed upstream of the evaporator coil of the 

return air system.

•  Downflow Installations require an internal filter accessory 

kit to be installed.

•  Horizontal Installations require the air filter system be 

installed in the return air ductwork.

air conditioner inStallation

Packaging removal

Remove the shipping carton and User’s Manual from 

the equipment. Take care not to damage the tubing 

connections when removing the carton. For rooftop 

installations, remove and discard the two supports attached 

beneath the unit.

rigging and Hoisting

 Warning:

to avoid the risk of property damage, personal 

injury, or death, it is the rigger’s responsibility 

to ensure that whatever means are used to hoist 

the unit are safe and adequate:

•  The lifting equipment must be adequate for the 

load. refer to 

table 5, (page 9)

 for unit weights.

•  The unit must be lifted from the holes in the 

base rails using cables or chains.

•  Spreader bars are required to protect the unit 

and ensure even loading.

•  Keep the unit in an upright position at all times. 

the rigging must be located outside the units 

center of gravity. refer to 

Figure 9, (page 14)

 for 

locating the center of gravity.

•  All  panels  must  be  securely  in  place  during 

rigging and hoisting.

ground level

Ground level installations must be located according to 

local building codes or ordinances and these requirements:

•  Clearances must be in accordance with those shown 

in 

Figure 1, (page 4)

.

•  A suitable mounting pad must be provided and separate 

from the building foundation. The pad must be level to 

ensure proper condensate disposal and strong enough 

to support the unit’s weight. The slab height must be a 

minimum of 2” (5cm) above grade and with adequate 

drainage. See 

Figure 2, (page 6)

.

•  Allow sufficient clearances for access to the internal 

filter rack.

rooftop

Rooftop installations must be located according to local 

building codes or ordinances and these requirements:

• 

The roof must be capable of handling the weight of the 

unit. For unit weights, see 

Table 5, (page 9)

. Reinforce 

the roof if necessary.

unit SiZe

internal Filter SiZe

P8SE-X36

P8SE-X48

(2) 14” x 25”

or

(2) 14” x 25”

P8SE-X60

(2) 18” x 25”

or

(2) 18” x 25”

table 1. internal Filter Size requirements.

Содержание P8SE Series

Страница 1: ...n sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warn...

Страница 2: ...ced 3 Phase Supply Voltage 8 Grounding 8 Thermostat Connections 8 Blower Speed 9 Fixed Torque ECM Motor 9 Optional Outdoor Thermostat 10 Optional Electric Heater Kits 10 START UP SYSTEM CHECK 10 Pre S...

Страница 3: ...nit uses refrigerant R 410A DO NOT use any other refrigerant in this unit Use of another refrigerant may damage the unit WARNING The safety information listed below must be followed during the install...

Страница 4: ...des NFPA publications are avaialable by writing to National Fire Protection Association Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods des...

Страница 5: ...filter pressure drop must not exceed 0 08 inches WC When replacing the air filters a suitable air filter must be installed upstream of the evaporator coil of the return air system DownflowInstallatio...

Страница 6: ...return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Slide the first filter between bo...

Страница 7: ...Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit...

Страница 8: ...14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4 6 8 35 3 4 6 8 40 2 3 4 6 45 2 3 4 6 50 2 3 4 6 55 1 2 3 4 60 Wire Size based on N E C for 60 type copper conductors Table 2 Copper Wire Size lead from th...

Страница 9: ...6 24 38 1244 25 40 1169 27 03 1153 27 40 1089 29 01 1030 30 67 961 32 88 863 36 61 Tap T3 1525 20 72 1499 21 08 1448 21 82 1391 22 71 1338 23 61 1264 25 00 1221 25 88 1159 27 26 Tap T4 1641 19 25 1590...

Страница 10: ...the low voltage wires are securely connected to the correct leads on the low voltage terminal strip Verify that the outdoor fan turns freely Verify that the power supply branch circuit overcurrent pr...

Страница 11: ...the circulating air blower and the outdoor fan are pre lubricated at the factory No further oiling is required for the life of this product Refrigerant Charging WARNING Single Packaged Air Conditione...

Страница 12: ...stem contains refrigerant under high pressure Always use safe and environmen tallysoundmethodswhenhandlingrefrigeranthandling or servicing the unit Review the factory literature and safety warnings pr...

Страница 13: ...ove refrigerant if above curve Add refrigerant if below curve Figure 8 Charging Chart for 5 Ton Units 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Pressure psig Liquid Temperature F P8SE X48 Char...

Страница 14: ...hipping weight Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT OPENING 23 5 Back View 131 2 16 13 7 10 13 1 2 16 12...

Страница 15: ...1 Stage Cool 1 Stage Heat Typical Wiring Field Supplied for 2 Stage Cool 1 Stage Heat with an Optional Outdoor Thermostat Figure 10 Typical Air Conditioner Thermostat Connections 208 230V Optional Ou...

Страница 16: ...de plus de 150V a la terre 711034o 1 2 3 4 5 6 7 8 9 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 3 AMP FUSE CCH COMPRESSOR OUTDOOR FAN MOTOR HEATER PLUG BLOWER RELAY DUAL C...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...____________ INSTALLER NAME CITY__________________________________ STATE________________________ Unit Installed Minimum clearances shown on page 4 YES NO Has the owner s information been reviewed with...

Отзывы: