background image

6

• 

The appropriate accessory roof curb (Figure 4) must be 

installed prior to unit installation. The roof curb must be 

square and level to ensure proper condensate drainage. 

Please follow all instructions provided with the kit

.

•  Secure  roof  curb  or  frame  to  roof  using  acceptable 

mechanical methods per local codes. 

note:

 

Make sure 

the two supports beneath the unit have been removed. 

Roof

Curb

Figure 3. roof top installation

2”

Figure 2. ground level installation

Horizontal to downflow conversion

The unit is shipped ready for horizontal duct connections. 

If down flow ducts are required, the unit must be converted 

following the steps below for the supply and return ducts.

1. Locate the duct cap inside the duct openings and 

remove the screw holding it in place.

2  Lift the cap out of the unit. (

Hint: 

The cap can be pushed 

up from the bottom by reaching through the fork slot).

3. Cover the horizontal duct opening with the horizontal 

duct cap. The insulation will be on the indoor side.

4. Fasten the cover with screws to seal.

removal of internal Filter rack

(3 Phase Only)

1. Remove the return air panel from the unit.

2. Remove the height adjustment screw from the inside 

of the rack.

3. Remove (1) screw securing the assembly to the coil 

located on the left leg of the rack. 

note:

 The assembly 

can now be easily collapsed and removed from the unit. 

See 

Figure 4

 for filter rack securing screw locations.

installing Filters in the Filter rack

(3 Phase Only)

1. Remove access panel screws from return air panel. 

(

Hint:

 Loosen the unit’s top panel screws near the 

top edge of the access panel. The access panel was 

designed to be captured underneath the top panel.)

2. Slide the first filter between both guide channels of filter 

rack and allow the filter to drop easily into place.

3. Verify the bottom of the filter is within the channels of 

the rack.

4. Slide the 2nd filter between both guide channels of filter 

rack.

5. Verify the bottom of the filter is within the channels of 

the rack.

6. Replace access cover by sliding the top edge of panel 

under the lip of the unit’s top panel. Secure access 

panel by replacing the screws.

removing Filters from Filter rack

(3 Phase Only)

1. Remove access panel screws from return air panel. 

(

Hint:

 Loosen the unit’s top panel screws near the 

top edge of the access panel. The access panel was 

designed to be captured underneath the top panel.)

2. Remove upper filter by gently pulling filter through the 

access panel opening.

3. Remove lower filter by lifting media to top of filter rack. 

Remove in the same manner as described in step 2.

4. Install new filter in the filter rack as described in the 

previous section.

condensate drain

Condensate is removed from the unit through the 3/4” 

female pipe fitting located on the front side of the unit. 

Install a 2 inch condensate trap in the drain line of the 

same size and prime with water. When connecting rigid 

drain line, hold the female fitting with a wrench to prevent 

twisting. 

do not over tighten!

 Refer to local codes and 

restrictions for proper condensate disposal requirements. 

See 

Figure 5, (page 7)

.

Securing

Screws

Figure 4. internal Filter rack location

Содержание P8SE Series

Страница 1: ...n sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warn...

Страница 2: ...ced 3 Phase Supply Voltage 8 Grounding 8 Thermostat Connections 8 Blower Speed 9 Fixed Torque ECM Motor 9 Optional Outdoor Thermostat 10 Optional Electric Heater Kits 10 START UP SYSTEM CHECK 10 Pre S...

Страница 3: ...nit uses refrigerant R 410A DO NOT use any other refrigerant in this unit Use of another refrigerant may damage the unit WARNING The safety information listed below must be followed during the install...

Страница 4: ...des NFPA publications are avaialable by writing to National Fire Protection Association Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods des...

Страница 5: ...filter pressure drop must not exceed 0 08 inches WC When replacing the air filters a suitable air filter must be installed upstream of the evaporator coil of the return air system DownflowInstallatio...

Страница 6: ...return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Slide the first filter between bo...

Страница 7: ...Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit...

Страница 8: ...14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4 6 8 35 3 4 6 8 40 2 3 4 6 45 2 3 4 6 50 2 3 4 6 55 1 2 3 4 60 Wire Size based on N E C for 60 type copper conductors Table 2 Copper Wire Size lead from th...

Страница 9: ...6 24 38 1244 25 40 1169 27 03 1153 27 40 1089 29 01 1030 30 67 961 32 88 863 36 61 Tap T3 1525 20 72 1499 21 08 1448 21 82 1391 22 71 1338 23 61 1264 25 00 1221 25 88 1159 27 26 Tap T4 1641 19 25 1590...

Страница 10: ...the low voltage wires are securely connected to the correct leads on the low voltage terminal strip Verify that the outdoor fan turns freely Verify that the power supply branch circuit overcurrent pr...

Страница 11: ...the circulating air blower and the outdoor fan are pre lubricated at the factory No further oiling is required for the life of this product Refrigerant Charging WARNING Single Packaged Air Conditione...

Страница 12: ...stem contains refrigerant under high pressure Always use safe and environmen tallysoundmethodswhenhandlingrefrigeranthandling or servicing the unit Review the factory literature and safety warnings pr...

Страница 13: ...ove refrigerant if above curve Add refrigerant if below curve Figure 8 Charging Chart for 5 Ton Units 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Pressure psig Liquid Temperature F P8SE X48 Char...

Страница 14: ...hipping weight Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT OPENING 23 5 Back View 131 2 16 13 7 10 13 1 2 16 12...

Страница 15: ...1 Stage Cool 1 Stage Heat Typical Wiring Field Supplied for 2 Stage Cool 1 Stage Heat with an Optional Outdoor Thermostat Figure 10 Typical Air Conditioner Thermostat Connections 208 230V Optional Ou...

Страница 16: ...de plus de 150V a la terre 711034o 1 2 3 4 5 6 7 8 9 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 3 AMP FUSE CCH COMPRESSOR OUTDOOR FAN MOTOR HEATER PLUG BLOWER RELAY DUAL C...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...____________ INSTALLER NAME CITY__________________________________ STATE________________________ Unit Installed Minimum clearances shown on page 4 YES NO Has the owner s information been reviewed with...

Отзывы: