background image

10

optional outdoor thermostat

An outdoor thermostat can be installed in the field with 

2-stage electric heat. To install the outdoor thermostat, 

remove the orange wire from the 

W1

 terminal on the 

terminal block, and connect to the outdoor thermostat. 

Connect the other side of the outdoor thermostat to 

W2

 

from the thermostat.

optional electric Heater kits

This packaged air conditioner is designed to allow optional 

electric heat to be field installed as required by the 

building’s particular heating load.

 

Optional field-installed 

electric heater kits are available in 5 kw to 20 kw heating 

capacities for single phase, and 9 kw to 15 kw heating 

capacities for three phase. Installation instructions for 

the electric heaters and their application are shipped 

separately with the heater kits. Part numbers for available 

heater kits are listed in the installation instructions supplied 

with the heater kit.

note: 

All temperature rise data shown in 

Table 5, (page 

9)

 was calculated using 10kW heaters. For other sized 

heater kits, use the following steps to determine the heat 

rise for your particular heater kit.
1. Determine the CFM by locating your blower motor tap 

settings in 

Table 5

.

2. Locate your heater kits kW value and Btu/h i

Table 4

.

3. Input the values into the following equation:

temp rise: 

Δ

t= (btu/h)/(cFM*1.08)

note:

 Generally the heat rise should be 30 -  40 degrees. 

Anything above 40 degrees should be avoided.
If electric heat is installed, a single-stage or two- stage 

heating thermostat will be required depending on the heater 

kit. Install the heater kits as directed by the instructions 

supplied with the heater kit. Follow all cautions and 

warnings as directed.

Start uP & SYSteM cHeck

Pre-Start check list

 Verify the unit is level and allows condensate to drain.

 Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/

control panels are in place.

  Verify that the duct work is sealed to prevent air leakage. 

 Verify that the line voltage power leads are securely 

connected and the unit is properly grounded.

   Verify that the low voltage wires are securely connected 

to the correct leads on the low voltage terminal strip.

 Verify that the outdoor fan turns freely.

 Verify that the power supply branch circuit overcurrent 

protection is sized properly.

 Verify that the thermostat is wired correctly. The 

thermostat system mode should be set to OFF and the 

thermostat fan mode should be set to AUTO.

Start-up Procedure

 Warning:

if the unit is equipped with a crankcase heater, 

allow 24 hours prior to continuing the start up 

procedures to allow for heating of the refrigerant 

compressor crankcase. Failure to comply may 

result in damage and could cause premature 

failure of the system. this warning should be 

followed at initial start up and any time the power 

has been removed for 12 hours or longer.

Air Circulation

Leave the thermostat system mode on OFF, and set the 

fan mode to ON. Blower should run continuously. Check 

the air delivery at the supply registers and adjust register 

openings for balanced air distribution. Examine ductwork 

for leaks or obstruction if insufficient air is detected. Set 

the thermostat fan mode to AUTO. The blower should 

stop running.

System Cooling

1. Set the thermostat’s system mode to COOL and the 

fan mode to AUTO. Gradually lower the thermostats 

setpoint below room temperature and verify the outdoor 

unit and indoor blower energize.

2. Feel the air being circulated by the indoor blower and 

verify that it is cooler than ambient temperature. Listen for 

any unusual noises. If unusual sounds occur, determine 

the source of the noise and correct as necessary.

3. Allow the cooling system to operate for several minutes 

and then set the temperature selector above room 

temperature. Verify the fan and compressor cycle off 

with the thermostat. 

note:

 The blower should also 

stop unless fan mode is set to ON.

System Heating

If the unit has been equipped with optional electric heater 

kits, set the thermostat's system mode to HEAT and the 

fan mode to AUTO. Verify the compressor and outdoor 

fan are not energized but that the blower and heaters are. 

Feel the air being circulated by the indoor blower and verify 

that it is warmer than ambient temperature. Listen for any 

unusual noises. If unusual sounds occur, determine the 

source of the noise and correct as necessary.

Содержание P8SE Series

Страница 1: ...n sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warn...

Страница 2: ...ced 3 Phase Supply Voltage 8 Grounding 8 Thermostat Connections 8 Blower Speed 9 Fixed Torque ECM Motor 9 Optional Outdoor Thermostat 10 Optional Electric Heater Kits 10 START UP SYSTEM CHECK 10 Pre S...

Страница 3: ...nit uses refrigerant R 410A DO NOT use any other refrigerant in this unit Use of another refrigerant may damage the unit WARNING The safety information listed below must be followed during the install...

Страница 4: ...des NFPA publications are avaialable by writing to National Fire Protection Association Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods des...

Страница 5: ...filter pressure drop must not exceed 0 08 inches WC When replacing the air filters a suitable air filter must be installed upstream of the evaporator coil of the return air system DownflowInstallatio...

Страница 6: ...return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Slide the first filter between bo...

Страница 7: ...Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit...

Страница 8: ...14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4 6 8 35 3 4 6 8 40 2 3 4 6 45 2 3 4 6 50 2 3 4 6 55 1 2 3 4 60 Wire Size based on N E C for 60 type copper conductors Table 2 Copper Wire Size lead from th...

Страница 9: ...6 24 38 1244 25 40 1169 27 03 1153 27 40 1089 29 01 1030 30 67 961 32 88 863 36 61 Tap T3 1525 20 72 1499 21 08 1448 21 82 1391 22 71 1338 23 61 1264 25 00 1221 25 88 1159 27 26 Tap T4 1641 19 25 1590...

Страница 10: ...the low voltage wires are securely connected to the correct leads on the low voltage terminal strip Verify that the outdoor fan turns freely Verify that the power supply branch circuit overcurrent pr...

Страница 11: ...the circulating air blower and the outdoor fan are pre lubricated at the factory No further oiling is required for the life of this product Refrigerant Charging WARNING Single Packaged Air Conditione...

Страница 12: ...stem contains refrigerant under high pressure Always use safe and environmen tallysoundmethodswhenhandlingrefrigeranthandling or servicing the unit Review the factory literature and safety warnings pr...

Страница 13: ...ove refrigerant if above curve Add refrigerant if below curve Figure 8 Charging Chart for 5 Ton Units 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Pressure psig Liquid Temperature F P8SE X48 Char...

Страница 14: ...hipping weight Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT OPENING 23 5 Back View 131 2 16 13 7 10 13 1 2 16 12...

Страница 15: ...1 Stage Cool 1 Stage Heat Typical Wiring Field Supplied for 2 Stage Cool 1 Stage Heat with an Optional Outdoor Thermostat Figure 10 Typical Air Conditioner Thermostat Connections 208 230V Optional Ou...

Страница 16: ...de plus de 150V a la terre 711034o 1 2 3 4 5 6 7 8 9 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 3 AMP FUSE CCH COMPRESSOR OUTDOOR FAN MOTOR HEATER PLUG BLOWER RELAY DUAL C...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...____________ INSTALLER NAME CITY__________________________________ STATE________________________ Unit Installed Minimum clearances shown on page 4 YES NO Has the owner s information been reviewed with...

Отзывы: