Nortek P8SE Series Скачать руководство пользователя страница 12

12

•  A low-pressure switch is factory-installed and located 

in the suction line internal to the outdoor unit. The 

switch is designed to protect the compressor from a 

loss of charge. Under normal conditions, the switch is 

closed. If the suction pressure falls below 5 psig, then 

the switch will open and de-energize the outdoor unit. 

The switch will close again once the suction pressure 

increases above 20 psig. Please note that the switch 

interrupts the thermostat inputs to the unit. When the 

switch opens and then closes, there will be a 5 minute 

short cycling delay before the outdoor unit will energize.

•  To achieve rated capacity and efficiency the compressor 

must be exposed to refrigerant for at least 24 hours prior 

to running and then must be run for a minimum of 12 

hours.

charging the unit in ac mode

At outdoor temperatures above 65° F

1. With the system operating at steady-state, measure 

the liquid refrigerant pressure (in psig) at the outdoor 

unit service valve.

2. Measure the liquid refrigerant temperature (in 

Fahrenheit) at the service valve.

3. Determine the required liquid refrigerant pressure 

from 

Figure 6

Figure 7, (page 13)

, or 

Figure 8, (page 

13)

.

•  If the pressure measured in Step 1 is greater than 

the required liquid refrigerant pressure determined 

in Step 3, then there is too much charge in the 

system. Remove refrigerant and repeat Steps 1 

through 3 until the system is correctly charged.

•  If the pressure measured in Step 1 is less than the 

required liquid refrigerant pressure determined in 

Step 3, there is too little charge in the system. Add 

refrigerant and repeat Steps 1 through 3 until the 

system is correctly charged.

charging charts & application notes

•  This equipment’s cooling system contains refrigerant 

under high pressure. Always use safe and environmen-

tally sound methods when handling refrigerant handling 

or servicing the unit. Review the factory literature and 

safety warnings prior to servicing.

•  When repairing system leaks, always use a nitrogen 

(inert) gas to protect the refrigerant system and pressure 

check the repair before re-charging. Always replace 

the filter-dryers when performing any repair to the 

refrigeration system with one capable of acid removal. 

After completing the repairs, evacuate the system to 

350 - 500 microns and weigh in the refrigerant to the 

amount specified on the unit rating label.

•  The refrigerant charging charts, 

Figure 6

Figure 7

, or 

Figure 

8

 are applicable only to matched assemblies and listed 

airflows for the indoor coil. NOTE: Before using these 

charts, make sure the unit is in a stable operating mode. 

As shown in the charts, the ideal system sub-cooling 

can vary over the range of operation. Reference the 

charts to determine the ideal amount of sub-cooling for 

a given liquid pressure. Units charged to other values 

will not perform at the rated unit efficiency (EER).

•  For systems that are operating with more than a 5% 

deviation, inspect the unit for the proper voltage and 

phase balance and the refrigeration system for leaks.

•  Units that are operating at less then 95% of the nominal 

voltage or with a 2% phase imbalance may see a more 

significant deviation than the amount stated above.

•  DO NOT use the charts in systems that have a fan cycling 

under low-ambient control. Refer to the low-ambient kit 

instructions for more information (If applicable).

75

80

85

90

95

100

105

110

115

120

125

130

Liquid Pressure (psig

)

Liquid Temperature (° F)

P8SE-X36 Charging Chart - Cooling

200

220

240

260

280

300

320

340

360

380

400

420

440

460

480

500

520

540

560

580

600

135

Remove refrigerant if above curve

 Add refrigerant if below curve

Figure 6. charging chart for 3 ton units

Содержание P8SE Series

Страница 1: ...n sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warn...

Страница 2: ...ced 3 Phase Supply Voltage 8 Grounding 8 Thermostat Connections 8 Blower Speed 9 Fixed Torque ECM Motor 9 Optional Outdoor Thermostat 10 Optional Electric Heater Kits 10 START UP SYSTEM CHECK 10 Pre S...

Страница 3: ...nit uses refrigerant R 410A DO NOT use any other refrigerant in this unit Use of another refrigerant may damage the unit WARNING The safety information listed below must be followed during the install...

Страница 4: ...des NFPA publications are avaialable by writing to National Fire Protection Association Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods des...

Страница 5: ...filter pressure drop must not exceed 0 08 inches WC When replacing the air filters a suitable air filter must be installed upstream of the evaporator coil of the return air system DownflowInstallatio...

Страница 6: ...return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Slide the first filter between bo...

Страница 7: ...Make all electrical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit...

Страница 8: ...14 15 4 6 8 12 20 4 6 8 10 25 4 4 6 10 30 3 4 6 8 35 3 4 6 8 40 2 3 4 6 45 2 3 4 6 50 2 3 4 6 55 1 2 3 4 60 Wire Size based on N E C for 60 type copper conductors Table 2 Copper Wire Size lead from th...

Страница 9: ...6 24 38 1244 25 40 1169 27 03 1153 27 40 1089 29 01 1030 30 67 961 32 88 863 36 61 Tap T3 1525 20 72 1499 21 08 1448 21 82 1391 22 71 1338 23 61 1264 25 00 1221 25 88 1159 27 26 Tap T4 1641 19 25 1590...

Страница 10: ...the low voltage wires are securely connected to the correct leads on the low voltage terminal strip Verify that the outdoor fan turns freely Verify that the power supply branch circuit overcurrent pr...

Страница 11: ...the circulating air blower and the outdoor fan are pre lubricated at the factory No further oiling is required for the life of this product Refrigerant Charging WARNING Single Packaged Air Conditione...

Страница 12: ...stem contains refrigerant under high pressure Always use safe and environmen tallysoundmethodswhenhandlingrefrigeranthandling or servicing the unit Review the factory literature and safety warnings pr...

Страница 13: ...ove refrigerant if above curve Add refrigerant if below curve Figure 8 Charging Chart for 5 Ton Units 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Pressure psig Liquid Temperature F P8SE X48 Char...

Страница 14: ...hipping weight Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT OPENING 23 5 Back View 131 2 16 13 7 10 13 1 2 16 12...

Страница 15: ...1 Stage Cool 1 Stage Heat Typical Wiring Field Supplied for 2 Stage Cool 1 Stage Heat with an Optional Outdoor Thermostat Figure 10 Typical Air Conditioner Thermostat Connections 208 230V Optional Ou...

Страница 16: ...de plus de 150V a la terre 711034o 1 2 3 4 5 6 7 8 9 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 3 AMP FUSE CCH COMPRESSOR OUTDOOR FAN MOTOR HEATER PLUG BLOWER RELAY DUAL C...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...____________ INSTALLER NAME CITY__________________________________ STATE________________________ Unit Installed Minimum clearances shown on page 4 YES NO Has the owner s information been reviewed with...

Отзывы: